TABLE 15: ADDITIONAL STATIC PRESSURE RESISTANCE
|
|
|
|
|
| RESISTANCE, IWG |
|
|
|
| ||
DESCRIPTION |
|
|
|
|
| CFM |
|
|
|
| ||
|
| 1,100 | 1,200 | 1,300 | 1,400 | 1,500 |
| 1,600 | 1,700 | 1,800 | 1,900 | 2,000 |
WET EVAPORATOR COIL | .02 | .03 | .04 | .05 | .06 |
| .07 | .07 | .08 | .09 | .09 | |
ECONOMIZER2 | .02 | .02 | .02 | .03 | .03 |
| .04 | .04 | .04 | .05 | .05 | |
FILTER FRAME KIT | .04 | .04 | .05 | .05 | .06 |
| .07 | .08 | .09 | .10 | .11 |
1.Deduct these resistance values from the available external static pressure shown in Table 10, 11, 12, and 13
2.The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
THERMOSTAT | UNIT TERMINAL STRIP | ||
** = Minimum wire size of 18 AWG | R | ** | R |
wire should be used for all |
|
|
|
field installed 24 volt wire. | G |
| G |
|
| ||
| Y |
| Y |
| W |
| W |
| C |
| C |
NOTE:
HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.
24VOLT TRANSFORMER
PROGRAMMABLE
THERMOSTAT ONLY
FIGURE 2 - FIELD WIRING DIAGRAM CONTROL WIRING
C O N T A C T O R |
| C O N T A C T O R | ||
F I E L D - S U P P L I E D |
|
| ||
D I S C O N N E C T |
|
| F I E L D - S U P P L I E | |
|
|
| ||
S I N G L E |
|
| D I S C O N N E C T | |
|
|
| ||
P H A S E |
|
| T H R E E | |
P O W E R |
|
| P H A S E | |
G R O URNEDF E R T O E L E C T R I C A L |
|
| P O W E R | |
S U P P L Y |
|
| ||
| G R O U N D |
| ||
L U G D A T A T A B L E S T O S I Z E |
|
| S U P P L Y | |
T H E D I S C O N N E C T | L U G | R E F E R T O E L E C T R I C A L | ||
|
| D A T A T A B L E S T O S I Z E | ||
|
|
|
T H E D I S C O N N E C T
FIGURE 3 - POWER WIRING FIELD DIAGRAM
Unitary Products Group | 19 |