Additional
OUTDOOR UNIT |
| E4TS030 | E4TS036 | E4TS048 | E4TS060 | |
|
|
|
|
|
| |
UNIT ORIFICE(S)** |
| — | — | — | — | |
|
|
|
|
|
| |
FACTORY CHARGE, LBS. - OZ. |
| 9 - 9 | 10 - 1 | 12 - 1 | 13 - 1 | |
|
|
|
|
|
| |
INDOOR COIL |
| COIL ORIFICE1 | REQUIRED SYSTEM EXPANSION DEVICE + ADDITIONAL CHARGE, OZ. | |||
G1FA/G1UA048S17,21 |
| 78 | 701 + 0 | 702 + 0 | — | — |
|
|
|
|
|
|
|
G1FA/G1UA060S21,24 |
| 84 | — | 702 + 10 | 703 + 0 | 703 + 0 |
|
|
|
|
|
|
|
G1FA060S21,24T |
| 84 | — | — | 703 + 0 | 703 + 0 |
|
|
|
|
|
|
|
G2FD046(S,H)17 |
| 78 | 701 + 0 | 702 + 0 | — | — |
|
|
|
|
|
|
|
G2FD042(S,H)21 |
| 78 | 701 + 0 | — | — | — |
|
|
|
|
|
|
|
G2FD048(S,H)21, 24 |
| 84 | 701 + 6 | 702 + 0 | — | — |
|
|
|
|
|
|
|
G2FD060(S,H)24 |
| 90 | — | 702 + 10 | 703 + 0 | 703 + 0 |
|
|
|
|
|
|
|
G2FD060H24T |
| 90 | — | — | 703 + 0 | 703 + 0 |
|
|
|
|
|
|
|
G2FD061H24 |
| 90 | — | — | 703 + 8 | 703 + 4 |
|
|
|
|
|
|
|
REFRIGERANT LINE ADDER OZ. / FT. |
| .70 | .70 | .70 | .70 | |
|
|
|
|
|
|
|
Airflow
VARIABLE SPEED INDOOR
N1VSB12 | Hi/Low CFM | 1050/630 | — | — | — |
|
|
|
|
|
|
N1VSC16 | Hi/Low CFM | 1065/650 | 1185/770 | — | — |
|
|
|
|
|
|
N1VSD20 | Hi/Low CFM | — | 1200/780 | 1605/1040 | 1860/1200 |
|
|
|
|
|
|
P1XDB12V075 | Hi/Low CFM | 1040/580 | 1220/690 | — | — |
|
|
|
|
|
|
P1XUB12V055 | Hi/Low CFM | 1020/570 | 1200/660 | — | — |
|
|
|
|
|
|
P1DUB16V080 | Hi/Low CFM | 1050/540 | 1200/650 | — | — |
|
|
|
|
|
|
P1XUC16V075 | Hi/Low CFM | 1000/550 | 1200/650 | 1605/880 | — |
|
|
|
|
|
|
P1DUC20V080 | Hi/Low CFM | — | 1220/660 | 1620/900 | 1870/1030 |
|
|
|
|
|
|
P1DUC20V096 | Hi/Low CFM | — | 1200/650 | 1610/900 | 1850/1080 |
|
|
|
|
|
|
P1XUC20V095 | Hi/Low CFM | — | 1200/630 | 1590/850 | 1880/1000 |
|
|
|
|
|
|
P1XUD20V112 | Hi/Low CFM | — | 1260/720 | 1620/920 | 1800/990 |
|
|
|
|
|
|
P1XDD20V112 | Hi/Low CFM | — | 1200/690 | 1610/850 | 1870/1010 |
|
|
|
|
|
|
F(2,3)FV060 | Hi/Low CFM | — | — | 1600/1040 | 1875/1200 |
|
|
|
|
|
|
Hi CFM | — | 1000 | 1200 | 1600 | 1900 |
|
|
|
|
|
|
Max Low CFM | — | 850 | 1000 | 1350 | 1600 |
|
|
|
|
|
|
Recommended Low CFM | — | 600 | 750 | 900 | 1050 |
|
|
|
|
|
|
1.Unit factory charge listed on the unit nameplate includes refrigerant for the condensor, the smallest evaporator and for 15 feet of interconnecting line tubing.
2.Verify the TXV kit and the additional charge required for the specific evaporator coil in the system using the table above.
3.Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge.
5.Total System Charge = Base charge (as shipped) + adder for evaporator + adder for line set.
4 | Unitary Products Group |