3 RED FLASHES: This indicates the normally open pressure switch contact did not close after the inducer was energized. This could be caused by a number of problems: faulty inducer, blocked vent pipe, bro- ken pressure switch hose or faulty pressure switch.

4 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. With this fault code the control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor.

5 RED FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the fail- ure condition.

6 RED FLASHES: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat. If the main blower is in a “Delay on” mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

7 RED FLASHES: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out. Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle. This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

9 RED FLASHES: Indicates reversed line voltage polarity or grounding problem. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

10 RED FLASHES: Gas flow with no call for heat. Check gas valve and gas valve wiring.

11 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes. This condition is usually caused by a failed blower motor or blower wheel. Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.

12 RED FLASHES: This code indicates an open igniter circuit, which could be caused by a disconnected or loose wire or by a cracked or bro- ken igniter.

STEADY ON RED: Control failure. Replace control board.

60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control

includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6,7,8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored, at some point the “watchdog” would restart the unit and pro- vide heat for the house.

NOTE: If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.

IGNITION CONTROL

Normal flame sense current is approximately

3.7 microamps DC (µa)

Low flame signal warning starts at 1.5 microamps.

Low flame signal control lockout point is

0.1 microamps DC (µa)

DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL

The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily. This memory will be retained even if power to the furnace

is lost. This feature should only be used by a qualified service tech- nician.

The control stores up to five separate error codes. If more than five error codes have occurred since the last reset, only the five most recent will be retained. The furnace control board has a button, labeled "LAST ERROR" that is used to retrieve error codes. This function will only work if there are no active thermostat signals. So any call for heating, cooling or continuous fan must be terminated before attempting to retrieve error codes.

To retrieve the error codes, push the LAST ERROR button. The LED on the control will then flash the error codes that are in memory, starting with the most recent. There will be a two-second pause between each flash code. After the error codes have all been displayed, the LED will resume the normal slow green flash after a five second pause. To repeat the series of error codes, push the button again.

If there are no error codes in memory, the LED will flash two green flashes. To clear the memory, push the LAST ERROR button and hold it for more than five seconds. The LED will flash three green flashes when the memory has been cleared, then will resume the normal slow green flash after a five-second pause.

(Seconds)

 

 

 

 

 

 

 

Thermostat Calling for Heat

 

 

 

 

Thermostat Satisfied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 2

17

 

22

52

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan on Delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30 Seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTAT

OFF

 

 

 

ON

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDUCER

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

15 Sec.

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

Post

 

 

 

 

 

 

 

 

 

 

 

 

 

Purge

 

IGNITOR

OFF

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAIN VALVE

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

HUMIDIFIER

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

ELECTRONIC

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR CLEANER

OFF

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCULATING

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

OFF

 

 

 

 

OFF

 

 

 

 

 

60, 90, 120, 180 SEC.

OFF

 

 

 

 

 

 

 

 

 

 

Selectable Fan Off Delay

FIGURE 11: Furnace Control Event Schedule

8

Unitary Products Group

Page 8
Image 8
York GY8S160E30UH21 Diagnostic Fault Code Storage and Retrieval, Minute Automatic Reset from Lockout This control

GY8S160E30UH21 specifications

The York GY8S160E30UH21 is a cutting-edge air conditioning unit that has been designed to meet the demands of both residential and commercial spaces. This model stands out due to its efficient cooling capabilities and advanced technologies, making it a popular choice for various applications.

One of the main features of the York GY8S160E30UH21 is its high energy efficiency rating. Equipped with an inverter-driven compressor, this unit adjusts its speed according to the cooling demand, thus significantly reducing energy consumption. This not only helps in lowering utility bills but also contributes positively to environmental sustainability by minimizing greenhouse gas emissions.

Another standout characteristic is the unit's superior temperature control. The GY8S160E30UH21 comes with a smart thermostat that offers precise temperature and humidity control, ensuring optimal comfort in the indoor environment. With advanced sensors, it can detect changes in ambient conditions and adjust its operation accordingly, providing a consistent and comfortable climate all year round.

Noise reduction is also a key focus in the design of the York GY8S160E30UH21. This model incorporates sound-dampening technology, allowing it to operate quietly without disrupting nearby activities. This feature makes it particularly appealing for residential users who prioritize tranquility in their living spaces.

The construction of the GY8S160E30UH21 leverages durable materials that enhance its longevity. With a corrosion-resistant cabinet and high-quality internal components, this air conditioning unit is designed to withstand harsh conditions and deliver reliable performance over time.

Ease of installation and maintenance are additional benefits of this model. The unit is designed for straightforward installation, which reduces labor costs for installers. Furthermore, it features a user-friendly interface that simplifies the maintenance process, allowing users to easily access and clean important components.

Lastly, the York GY8S160E30UH21 is compatible with smart home systems, allowing for convenient remote control and monitoring via mobile devices. This integration into home automation systems adds an extra layer of convenience for users, enabling them to manage their indoor climate effortlessly.

Overall, the York GY8S160E30UH21 combines efficiency, comfort, and user-friendly features, making it an excellent choice for anyone looking to upgrade their air conditioning system.