036-21105-004 Rev. A (0902)

COOLING PERFORMANCE

 

SUCT.T/P @ COMPR.

 

 

 

 

AIR TEMP ON CONDENSER

 

 

 

 

MODEL

 

 

75 °F

 

95°F

115°F

 

 

125°F

 

 

 

 

 

 

 

 

TEMP

PSIG

MBH

 

KW

MBH

 

KW

MBH

 

KW

MBH

 

KW

 

35

61.5

 

13.0

 

1.31

10.9

 

1.41

9.0

 

1.53

8.0

 

1.59

H3DA012

40

68.5

 

14.5

 

1.36

12.3

 

1.49

10.2

 

1.62

9.1

 

1.69

45

76.0

 

16.1

 

1.41

13.7

 

1.54

11.3

 

1.69

10.1

 

1.76

 

 

 

 

 

 

 

50

84.0

 

17.7

 

1.44

15.2

 

1.58

12.4

 

1.74

11.1

 

1.82

 

35

61.5

 

18.7

 

1.83

15.6

 

1.99

12.5

 

2.09

10.9

 

2.13

H3DA018

40

68.5

 

20.8

 

1.90

17.6

 

2.07

14.3

 

2.20

12.6

 

2.24

45

76.0

 

22.9

 

1.97

19.6

 

2.17

16.2

 

2.31

14.5

 

2.37

 

 

 

 

 

 

 

50

84.0

 

25.2

 

2.05

21.8

 

2.27

18.3

 

2.43

16.5

 

2.49

 

35

61.5

 

21.9

 

2.34

18.7

 

2.54

15.6

 

2.71

14.0

 

2.77

H3DA024

40

68.5

 

24.3

 

2.41

20.9

 

2.63

17.6

 

2.84

15.9

 

2.91

45

76.0

 

26.7

 

2.47

23.2

 

2.73

19.7

 

2.97

18.0

 

3.06

 

 

 

 

 

 

 

50

84.0

 

29.3

 

2.53

25.6

 

2.82

21.9

 

3.10

20.0

 

3.20

 

35

61.5

 

27.6

 

2.64

23.9

 

2.88

20.2

 

3.11

18.3

 

3.20

H3DA030

40

68.5

 

30.4

 

2.71

26.5

 

2.99

22.5

 

3.24

20.5

 

3.34

45

76.0

 

33.3

 

2.78

29.2

 

3.08

25.0

 

3.37

22.8

 

3.48

 

 

 

 

 

 

 

50

84.0

 

36.3

 

2.85

31.9

 

3.18

27.5

 

3.49

25.5

 

3.62

 

35

61.5

 

33.6

 

3.07

28.8

 

3.43

24.0

 

3.82

21.6

 

4.01

H3DA036

40

68.5

 

37.3

 

3.09

32.1

 

3.48

26.9

 

3.88

24.3

 

4.08

45

76.0

 

40.9

 

3.23

35.2

 

3.69

30.2

 

4.13

27.5

 

4.36

 

 

 

 

 

 

 

50

84.0

 

44.8

 

3.37

39.1

 

3.85

33.3

 

4.35

30.4

 

4.60

 

35

61.5

 

46.7

 

3.87

39.1

 

4.82

31.9

 

57.8

28.3

 

6.39

H3DA048

40

68.5

 

51.7

 

4.07

43.5

 

5.08

35.7

 

6.14

31.8

 

6.83

45

76.0

 

56.8

 

4.28

48

 

5.34

39.6

 

6.51

35.4

 

7.28

 

 

 

 

 

 

 

50

84.0

 

62

 

4.49

52.7

 

5.6

43.7

 

6.89

39.2

 

7.73

 

35

61.5

 

53.8

 

5.16

48.7

 

6.09

43.4

 

7.25

40.8

 

7.92

H3DA060

40

68.5

 

58.9

 

5.33

53.1

 

6.25

47.5

 

7.41

44.7

 

8.08

45

76.0

 

64.1

 

5.51

57.8

 

6.43

51.8

 

7.58

48.7

 

8.25

 

 

 

 

 

 

 

50

84.0

 

69.6

 

5.71

62.5

 

6.61

56.1

 

7.76

52.9

 

8.43

 

35

61.5

 

73.9

 

5.55

66.2

 

6.60

58.3

 

7.98

54.4

 

8.82

H3DA076

40

68.5

 

80.7

 

5.69

72.5

 

6.75

64.3

 

8.14

60.2

 

8.98

45

76.0

 

87.7

 

5.84

79.1

 

6.91

70.5

 

8.30

66.2

 

9.15

 

 

 

 

 

 

 

50

84.0

 

95.1

 

5.99

86.1

 

7.07

76.9

 

8.48

72.4

 

9.32

NOTES:

1.For condensing unit only. Does not include effect of evaporator motor power or heat.

2.Performance based on 1superheat and 1sub-cooling at condensing unit.

a.Increase capacity 1% for each increase in sub-cooling.

b.Decrease capacity 1% for each decrease in sub-cooling.

3.Sub-cooling in excess of 2may result in excessively high condensing temperature with air on condenser above 115°F. Maximum recommended condensing temperature is 140°F.

SOUND RATINGS

H*DA

SOUND RATING

MODEL

DECIBELS

 

 

H3DA012

7.8

H3DA018

7.8

H3DA024

7.8

H3DA030

7.8

H3DA036

7.8

H3DA048

8.0

H3DA060

8.2

H3DA076

8.2

ACCESSORIES

Refer to Price Manual for specific model numbers.

Off Cycle Timer - Provides a 5 minute off cycle to prevent rapid recycling of the compressor.

Room Thermostats - A wide selection of matching thermo- stats is available to provide features required for any installa- tion.

Start Assist Kit - Provides increased starting torque for areas with low voltage conditions.

Compressor Blanket - Designed to further reduce the nor- mal operating sounds of H3DA units.