York H*DA012 specifications Physical and Electrical Data, Model H*Da, Unit

Models: H*DA012

1 8
Download 8 pages 13.14 Kb
Page 2
Image 2
Physical and Electrical Data

036-21105-004 Rev. A (0902)

Physical and Electrical Data

MODEL H*DA

 

18

24

30

36

48

 

60

076

 

 

 

 

 

 

 

 

 

Unit Supply Voltage

 

 

230 – 1 – 50

 

 

380/415

-3-50

 

 

 

 

 

 

 

 

 

 

Normal Voltage Range *

 

216 to 252

 

 

 

342-456

 

Minimum Circuit Ampacity

12.4

16.2

18.4

8.1

12.0

 

12.7

20.2

 

 

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps

20.0

25.0

30.0

15.0

20.0

 

20.0

30.0

Compressor Type

 

Recip

Recip

Recip

Recip

Recip

 

Scroll

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Amps

Rated Load

9.2

12.2

13.4

5.8

7.5

 

9.5

14.7

 

 

 

 

 

 

 

 

 

Locked Rotor

53.0

72.0

85.0

39.0

62.0

 

73.0

95.0

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No**

No**

Yes

Yes

Yes

 

No**

No**

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

0.9

0.9

1.4

0.8

0.8

 

0.8

1.0

 

 

 

 

 

 

 

 

 

Locked Rotor

1.4

1.4

3.12

1.8

1.8

 

2.0

1.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

18

18

18

18

18

 

24

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/8

1/8

1/4

1/4

1/4

 

1/4

1/3

 

 

 

 

 

 

 

 

 

 

 

Fan Motor

 

Nominal RPM

1075

1075

1100

1075

1075

 

850

940

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Voltage

230

230

230

460

460

 

460

415

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

9.4

9.4

11.3

11.3

14.1

 

20

20.0

 

 

 

 

 

 

 

 

 

 

 

Coil

 

Rows Deep

1

1

1

1

1

 

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

16

16

20

20

16

 

18

13

 

 

 

 

 

 

 

 

 

 

 

Liquid Line OD

 

3/8

3/8

3/8

3/8

3/8

 

3/8

1/2

 

 

 

 

 

 

 

 

 

 

Vapor Line OD

 

5/8

5/8

3/4

3/4

7/8

 

7/8

1-1/8

 

 

 

 

 

 

 

 

 

Operating Weight Lbs.

124

134

135

140

176

 

210

285

 

 

 

 

 

 

 

 

 

 

 

 

*. Rated in accordance with ARI Standard 110, utilization range “A”. †. Dual element fuses or HACR circuit breaker.

** No crankcase heat required due to the compressor’s high pressure housing and internal design.

All dimensions are in inches. They are subject to change without

notice. Certified dimensions will be provided upon request.

48" OVERHEAD

CLEARANCE

 

 

 

 

 

 

C

 

 

 

 

Refrigerant

B

Unit

Dimensions

 

Connection

 

Model

 

(Inches)

 

Line Size

 

H*DA

A

B

C

Liquid

Vapor

 

 

 

018

20-1/8

24

24

 

 

AIR IN

 

5/8

4 SIDES

024

20-1/8

24

24

 

 

 

 

A

030

24-1/8

24

24

3/8

3/4

 

036

24-1/8

24

24

 

 

 

 

048

30-1/8

24

24

 

7/8

 

060

31-1/8 34-1/2

34-1/2

 

 

 

 

 

076

34-1/2

34-1/2

31-7/8

1/2

1-1/8

 

 

5-1/2

VAPOR

 

CONNECTION

2-3/8

LIQUID CONNECTION

 

 

3-1/8

2

Unitary Products Group

Page 2
Image 2
York H*DA012 specifications Physical and Electrical Data, Model H*Da, Unit