York H*RA036 THRU 090, H*RA018 THRU 060 Cooling Performance Data, Phase, Air Conditioner Model No

Models: H*RA036 THRU 090 H*RA018 THRU 060

1 20
Download 20 pages 10.07 Kb
Page 13
Image 13
Manual background

036-21121-002 Rev. A (0602)

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

H1RA042S06, H1RA042S(25,46)

 

 

 

 

 

INDOOR COIL MODEL NO.

 

G1FA048S21,24

 

 

 

 

 

 

 

CONDENSER

ID CFM

 

1200

 

 

1400

 

 

1600

 

ENTERING AIR

ID DB (°F)

85

80

70

85

80

70

85

80

70

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

72

67

57

72

67

57

72

67

57

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

47.2

44.1

41.2

47.5

44.6

41.9

47.9

45.1

42.6

75

 

 

 

 

 

 

 

 

 

 

S.C.

30.2

29.6

29.4

31.9

31.1

31.0

33.6

32.6

32.6

 

 

 

 

 

 

 

 

 

 

 

 

K.W

3.90

3.85

3.78

4.05

3.99

3.94

4.19

4.14

4.09

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

45.5

42.1

38.5

45.9

42.8

39.3

46.3

43.4

40.2

85

 

 

 

 

 

 

 

 

 

 

S.C.

29.8

28.9

28.1

31.4

30.7

30.0

33.0

32.5

31.9

 

 

 

 

 

 

 

 

 

 

 

 

K.W

4.13

4.06

3.96

4.28

4.21

4.13

4.43

4.36

4.29

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

43.9

40.2

35.7

44.3

41.0

36.8

44.8

41.8

37.8

95

 

 

 

 

 

 

 

 

 

 

S.C.

29.5

28.2

26.9

30.9

30.3

29.1

32.4

32.4

31.2

 

 

 

 

 

 

 

 

 

 

 

 

K.W

4.36

4.27

4.14

4.52

4.43

4.31

4.67

4.59

4.49

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

40.5

36.3

32.0

41.2

37.1

32.8

42.0

38.0

33.7

105

 

 

 

 

 

 

 

 

 

 

S.C.

28.1

26.7

25.1

29.9

28.8

27.2

31.7

30.9

29.3

 

 

 

 

 

 

 

 

 

 

 

 

K.W

4.58

4.44

4.30

4.74

4.60

4.47

4.89

4.77

4.64

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

37.1

32.3

28.3

38.2

33.3

28.9

39.2

34.2

29.6

115

 

 

 

 

 

 

 

 

 

 

S.C.

26.8

25.1

23.3

29.0

27.2

25.4

31.1

29.4

27.4

 

 

 

 

 

 

 

 

 

 

 

 

K.W

4.81

4.62

4.45

4.96

4.78

4.62

5.10

4.95

4.79

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

33.7

28.4

24.5

35.1

29.4

25.0

36.4

30.4

25.4

125

 

 

 

 

 

 

 

 

 

 

S.C.

25.5

23.5

21.5

28.0

25.7

23.5

30.5

27.9

25.5

 

 

 

 

 

 

 

 

 

 

 

 

K.W

5.04

4.79

4.61

5.18

4.96

4.78

5.32

5.13

4.94

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

1 Phase

 

 

 

 

Air Handler

Coil

T.C.

S.C.

KW

N1AHC1606

G2FD042S21

0.96

0.96

0.99

 

 

 

 

 

N1AHC1606

G2FD048S21

1.00

1.00

1.01

 

 

 

 

 

F2RP/F2FP042

 

0.96

0.95

0.99

 

 

 

 

 

F2FP048

 

0.99

0.99

0.99

 

 

 

 

 

 

G1FA048S17

0.98

1.00

1.00

 

 

 

 

 

 

G1FA060S21,24

1.02

1.02

1.00

 

 

 

 

 

 

G1HD048

0.99

0.99

1.01

 

 

 

 

 

 

G1NA036S21C

0.98

0.93

0.99

 

 

 

 

 

 

G1NA048S21D

0.99

0.94

1.00

 

 

 

 

 

 

G1UA048S17

0.98

1.00

1.00

 

 

 

 

 

 

G1UA048S21,24

1.00

1.00

1.00

 

 

 

 

 

 

G1UA060S21,24

1.02

1.03

1.00

 

 

 

 

 

 

G2FD042S21

0.96

0.96

0.99

 

 

 

 

 

 

G2FD046S17

0.98

0.98

1.00

 

 

 

 

 

 

G2FD048S21,24

1.00

1.00

1.01

 

 

 

 

 

 

G2FD060S24

1.02

1.02

1.00

 

 

 

 

 

 

MDD48DSD

0.99

0.94

1.00

 

 

 

 

 

3 Phase

Air Handler

Coil

T.C.

S.C.

KW

N1AHC1646

G2FD042S21

0.98

0.99

1.00

 

 

 

 

 

N1AHC1646

G2FD048S21

0.99

1.01

1.01

 

 

 

 

 

F2RP/F2FP042

 

0.95

0.95

0.99

 

 

 

 

 

F2FP048

 

0.99

0.99

0.99

 

 

 

 

 

 

G1FA060S21,24

1.02

1.02

1.00

 

 

 

 

 

 

G1NA036S21C

0.98

0.93

0.99

 

 

 

 

 

 

G1NA048S21D

0.99

0.94

1.00

 

 

 

 

 

 

G1UA048S21,24

1.00

1.00

1.00

 

 

 

 

 

 

G1UA060S21,24

1.02

1.03

1.00

 

 

 

 

 

 

G2FD042S21

0.96

0.96

0.99

 

 

 

 

 

 

G2FD046S17

0.98

0.98

1.00

 

 

 

 

 

 

G2FD048S21,24

1.00

1.00

1.01

 

 

 

 

 

Unitary Products Group

13

Page 13
Image 13
York H*RA036 THRU 090, H*RA018 THRU 060 warranty Cooling Performance Data, Phase, Air Conditioner Model No