York H*RA018 THRU 060, H*RA036 THRU 090 warranty Physical and Electrical Data - 1 Phase, Model

Models: H*RA036 THRU 090 H*RA018 THRU 060

1 20
Download 20 pages 10.07 Kb
Page 2
Image 2

036-21121-002 Rev. A (0602)

Physical and Electrical Data - 1 Phase

MODEL

 

 

H1RA018S06

H1RA024S06

H2RA030S06

 

H2RA036S06

 

H1RA042S06

H1RA048S06

H3RA060S06

Unit Supply Voltage

 

 

 

 

 

208/230 – 1 – 60

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Voltage Range 1

 

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

12.5

15.6

17.5

 

21.5

 

26.1

30.1

37.3

 

 

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

20

25

30

 

35

 

40

45

60

Compressor Type 3

 

Recip

Recip

Recip

 

Recip

 

Recip

Recip

Scroll B

Compressor Amps

Rated Load

9.6

12.1

13.6

 

16.1

 

19.8

23

28.8

Locked Rotor

54

57

73

 

82

 

97

110

160

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No

No

No

 

No

 

No

No

No

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

0.5

0.5

0.5

 

1.4

 

1.4

1.3

1.3

 

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

 

18

18

18

 

18

 

18

22

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/12

1/12

1/12

 

1/4

 

1/4

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

Nominal RPM

1,100

1,100

1,100

 

1,100

 

1,100

850

850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal CFM

1,850

1,850

1,900

 

2,750

 

2,750

3,250

3,300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

8.00

8.00

9.15

 

9.15

 

12.58

15.72

15.72

Coil

 

 

 

 

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

 

1

 

1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

14

14

18

 

18

 

18

18

22

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Line

OD

 

3/8

3/8

3/8

 

3/8

 

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

 

Vapor Line OD

 

5/8

5/8

3/4

 

3/4

 

3/4

7/8

7/8

 

 

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 4

3 - 6

3 - 11

3 - 14

 

3 - 15

 

5 - 4

7 - 5

6 - 2

Charge Per Foot, Oz. 4

0.66

0.66

0.68

 

0.68

 

0.68

0.70

.070

Operating Weight Lbs.

118

123

135

 

137

 

161

176

188

 

 

 

 

 

 

 

 

 

 

 

 

 

Physical and Electrical Data - 3 Phase

MODEL

 

 

 

H1RA

H1RA

H1RA

H1RA

H1RA

H1RA

H1RA

H1RA

H1RA

H1RA

H1RA

H1RA

 

 

 

036S25

042S25

048S25

060S25

076S25

090S25

036S25

042S46

048S46

060S46

076S46

090S46

 

 

 

 

Unit Supply Voltage

 

 

 

208/230 – 3 – 60

 

 

 

 

460 -

3 - 60

 

 

Normal Voltage Range 1

 

 

187 to 252

 

 

 

 

432 to 504

 

 

Minimum Circuit Ampacity

15.0

17.4

17.3

21.3

25.8

37.7

8.0

8.4

8.3

10.8

13.0

18.1

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

25

30

30

35

40

50

15

15

15

15

20

25

Compressor Type 3

 

Recip

Recip

Recip

ScrollB

ScrollB

Dual

Recip

Recip

Recip

ScrollB

ScrollB

Dual

Compressor Amps

 

Rated Load

10.9

12.8

11.7

16.0

18.9

29.4

5.8

6.1

6.1

8.0

9.5

14.0

 

Locked Rotor

78

78

78

125

146

260

40

39

39

67

73

128

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

No

No

No

No

No

Yes

No

No

No

No

No

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

 

Rated Load

1.4

1.4

1.3

1.3

2.2

4.6

.8

.8

.7

.8

1.2

2.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

 

18

18

22

22

24

24

18

18

22

22

24

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/4

1/4

1/4

1/4

1/3

3/4

1/4

1/4

1/5

1/4

1/3

3/4

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal RPM

1,100

1,100

850

850

1100

1100

1,100

1,100

850

850

1100

1100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal CFM

2,750

2,750

3,250

3,450

4000

5000

2,750

2,750

3,250

3,450

4000

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

9.15

12.58

15.72

23.58

18.0

22.5

9.15

12.58

15.72

23.58

18.0

22.5

Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

1

2

2

1

1

1

1

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

18

18

18

18

16

16

18

18

18

18

16

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Line OD

 

3/8

3/8

3/8

3/8

1/2

1/2

3/8

3/8

3/8

3/8

1/2

1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vapor Line OD

 

3/4

3/4

7/8

7/8

1-1/8

1-1/8

3/4

3/4

7/8

7/8

1-1/8

1-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 4

3 - 15

5 - 4

7 - 5

9 - 7

12-3

15-3

3 - 15

5 - 4

7 - 5

9 - 7

12-3

15-3

Charge Per Foot, Oz.4

.68

.68

.70

.70

1.26

1.26

.68

.68

.70

.70

1.26

1.26

Operating Weight Lbs.

170

176

206

228

219

368

170

176

206

228

219

368

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker.

3.All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub- tract the amount of refrigerant, using the difference in length multiplied by the per foot valve.

2

Unitary Products Group

Page 2
Image 2
York H*RA018 THRU 060 warranty Physical and Electrical Data - 1 Phase, Physical and Electrical Data - 3 Phase, Model