FIG. 5 – CWE SERIES WALL/ CLOSET FAN COILS

FORM 115.20-NOM6 (1106)

INSTALLATION

Drain Piping

Condensate drain lines must be installed with adequate slope away from the unit to assure positive drainage. Since the drain pan is located on the suction side of the blower, a negative pressure exists at the drain pan and a minimum trap of 1-1/2" must be provided in the drain line to assure proper drainage.

Drain connections, primary and secondary, are 3/4" MPT (see Fig. 5 for details).

On units with plastic drain pans the drain connections must be made hand tight only.

LD12278

CONDENSATE DRAIN CONNECTIONS

(With drain cover removed) (Thermoplastic pan shown)

FIG. 5 – CWE SERIES WALL/ CLOSET FAN COILS

Chilled Water with Electric Heat

8