APPLYING FILTER PRESSURE DROP TO DETERMINE SYSTEM AIRFLOW
To determine the approximate airflow of the unit with a filter in place, follow the steps below:
1.Select the filter type.
2.Select the number of return air openings or calculate the return opening size in square inches to determine the proper filter pressure drop.
3.Determine the External System Static Pressure (ESP) without the filter.
4.Select a filter pressure drop from the table based upon the number of return air openings or return air opening size and add to the ESP from Step 3 to determine the total system static.
5.If total system static matches a ESP value in the airflow table (i.e. 0.20 w.c. (50 Pa), 0.60 w.c. (150 Pa), etc,) the system airflow corresponds to the intersection of the ESP column and Model/Blower Speed row.
6.If the total system static falls between ESP values in the table (i.e. 0.58 w.c. (144 Pa), 0.75 w.c. (187 Pa), etc.), the static pressure may be rounded to the nearest value in the table determining the airflow using Step 5 or calcu- late the airflow by using the following example.
Example: For a 60,000 BTUH (17.58 kW) furnace with a bot- tom return opening and operating on
Obtain the airflow values at 0.50 w.c. (125 Pa) & 0.60 w.c. (150 Pa) ESP.
Airflow @ 0.50”: 1250 CFM (35.4 m3/min)
Airflow @ 0.60”: 1180 CFM (33.4 m3/min)
Subtract the airflow @ 0.50 w.c. (125 Pa) from the airflow @ 0.60 w.c. (150 Pa) to obtain airflow difference.
1180 - 1250 =
Subtract the total system static from 0.50 w.c. (125 Pa) and divide this difference by the difference in ESP values in the
table, 0.60 w.c. | (150 Pa) - 0.50 w.c. (125 Pa), to obtain a |
percentage. |
|
(0.58 - 0.50) / (0.60 - 0.50) = 0.8
Multiply percentage by airflow difference to obtain airflow reduction.
(0.8) X
Subtract airflow reduction value to airflow @ 0.50 w.c. (125 Pa) to obtain actual airflow @ 0.58 in. w.c. (144 Pa) ESP.
1250 - 56 = 1194
Subject to change without notice. Printed in U.S.A.
Copyright © by York International Corp. 2007. All rights reserved.
ACCESSORIES
PROPANE (LP) CONVERSION KIT -
1NP0347 - All Models
This accessory conversion kit may be used to convert natural gas (N) units for propane (LP) operation. Conversions must be made by qualified distributor or dealer personnel.
SIDE RETURN FILTER -
1SR0302 - All Models
1SR0200 - All Models
BOTTOM RETURN FILTER -
1BR0114 or 1BR0214 - For
INTERNAL FILTER WITH FIBER FILTER -
1HF0801 - All Models
HIGH ALTITUDE PRESSURE SWITCHES -
For installation where the altitude is less than 8,000 feet it is not required that the pressure switch be changed. For alti- tudes above 8,000 feet see kits below. Conversion must be made by qualified distributor or dealer personnel.
1PS0301 - 040, 060 MBH 1PS0302 - 080 MBH 1PS0311 - 100, 115, 130 MBH
ROOM THERMOSTATS - A wide selection of compatible thermosets are available to provide optimum performance and features for any installation.
1H/1C, manual
1H/1C, auto/manual changeover, electronic programmable, deluxe
1H/1C, auto/manual changeover, electronic programmable.
*For the most current accessory information, refer to the price book or consult factory.