COOLING AIRFLOW DATA - MV MODELS

255427-YTG-F-1006

COOLING AIRFLOW DATA - MV MODELS

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

 

 

12B Air Handler

 

 

 

 

12D Air Handler

 

 

JUMPER SETTINGS

 

CFM

 

m3/min

CFM

 

 

m3/min

 

 

 

 

 

 

High

 

Low

High

 

Low

High

 

Low

High

 

Low

COOL Tap

ADJ Tap*

1307

 

882

37.0

 

25.0

1366

 

869

38.7

 

24.6

A

B

1080

 

756

30.6

 

21.4

1097

 

717

31.1

 

20.3

B

B

1270

 

862

36.0

 

24.4

1312

 

856

37.2

 

24.2

A

A

943

 

689

26.7

 

19.5

957

 

646

27.1

 

18.3

B

A

1146

 

786

32.5

 

22.3

1167

 

761

33.0

 

21.5

A

C

1050

 

726

29.7

 

20.6

1051

 

703

29.8

 

19.9

C

B

870

 

632

24.6

 

17.9

863

 

580

24.4

 

16.4

B

C

771

 

594

21.8

 

16.8

739

 

520

20.9

 

14.7

D

B

931

 

668

26.4

 

18.9

927

 

629

26.2

 

17.8

C

A

693

 

565

19.6

 

16.0

658

 

495

18.6

 

14.0

D

A

851

 

624

24.1

 

17.7

830

 

567

23.5

 

16.1

C

C

655

 

567

18.5

 

16.1

594

 

488

16.8

 

13.8

D

C

 

 

16C Air

Handler

 

 

 

 

20D Air

Handler

 

 

JUMPER SETTINGS

 

CFM

 

m3/min

CFM

 

 

m3/min

 

 

 

 

 

 

High

 

Low

High

 

Low

High

 

Low

High

 

Low

COOL Tap

ADJ Tap*

1920

 

1321

54.4

 

37.4

2209

 

1394

62.6

 

39.5

A

B

1699

 

1189

48.1

 

33.7

2022

 

1394

57.3

 

39.5

B

B

1884

 

1296

53.3

 

36.7

2178

 

1381

61.7

 

39.1

A

A

1558

 

1094

44.1

 

31.0

1798

 

1378

50.9

 

39.0

B

A

1714

 

1193

48.5

 

33.8

1965

 

1226

55.6

 

34.7

A

C

1451

 

1037

41.1

 

29.4

1843

 

1143

52.2

 

32.4

C

B

1403

 

1009

39.7

 

28.6

1596

 

1226

45.2

 

34.7

B

C

1288

 

947

36.5

 

26.8

1700

 

1066

48.1

 

30.2

D

B

1336

 

978

37.8

 

27.7

1608

 

1023

45.5

 

29.0

C

A

1214

 

888

34.4

 

25.1

1493

 

967

42.3

 

27.4

D

A

1239

 

915

35.1

 

25.9

1430

 

911

40.5

 

25.8

C

C

1098

 

839

31.1

 

23.8

1334

 

877

37.8

 

24.8

D

C

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.

NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details.

* The ADJ “D” tap should not be used.

HEATING AIRFLOW DATA - MV MODELS

HIGH / LOW SPEED COOLING AND HEAT PUMP CFM

 

 

12B Air Handler

 

 

 

 

12D Air Handler

 

 

JUMPER SETTINGS

CFM

 

 

m3/min

CFM

 

 

m3/min

 

 

 

 

 

 

High

 

Low

High

 

Low

High

 

Low

High

 

Low

COOL Tap

ADJ Tap*

1270

 

791

36.0

 

22.4

1312

 

762

37.2

 

21.6

A

A

943

 

714

26.7

 

20.2

957

 

668

27.1

 

18.9

B

A

931

 

643

26.4

 

18.2

927

 

591

26.2

 

16.7

C

A

693

 

567

19.6

 

16.1

658

 

488

18.6

 

13.8

D

A

 

 

16C Air

Handler

 

 

 

 

20D Air

Handler

 

 

JUMPER SETTINGS

CFM

 

 

m3/min

CFM

 

 

m3/min

 

 

 

 

 

 

High

 

Low

High

 

Low

High

 

Low

High

 

Low

COOL Tap

ADJ Tap*

1884

 

1217

53.3

 

34.5

2178

 

1217

61.7

 

34.5

A

A

1558

 

1065

44.1

 

30.2

1798

 

1036

50.9

 

29.3

B

A

1336

 

823

37.8

 

23.3

1608

 

748

45.5

 

21.2

C

A

1214

 

727

34.4

 

20.6

1493

 

551

42.3

 

15.6

D

A

All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.

NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details.

* The ADJ “D” tap should not be used.

10