ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE
|
|
|
|
| Field Wiring |
|
|
| |
Model | Heater Model1,* | Heater Amps | Ampacity Min. Circuit | Max. O.C.P.2 Amps/Type | Wire Size - AWG 75°C | ||||
|
| 240V | 208V | 240V | 208V |
| 240V | 208V | 240V |
| 4HK*6500506 | 20.0 | 27.54 | 30.38 | 30 |
| 35 | 10 | 8 |
MV12B | 4HK*6500806 | 31.3 | 39.73 | 44.50 | 40 |
| 45 | 8 | 8 |
4HK*6501006 | 40.0 | 49.21 | 55.38 | 50 |
| 60 | 8 | 6 | |
|
| ||||||||
| 4HK165N1506 | 60.0 | 70.88 | 80.38 | 90 |
| 90 | 4 | 3 |
| 4HK*6500506 | 20.0 | 27.54 | 30.38 | 30 |
| 35 | 10 | 8 |
| 4HK*6500806 | 31.3 | 39.73 | 44.50 | 40 |
| 45 | 8 | 8 |
MV12D | 4HK*6501006 | 40.0 | 49.21 | 55.38 | 50 |
| 60 | 8 | 6 |
4HK16501506 | 60.0 | 70.88 | 80.38 | 90 |
| 90 | 4 | 3 | |
|
| ||||||||
| 4HK16501806 | 73.3 | 85.32 | 97.00 | 90 |
| 100 | 4 | 3 |
| 4HK16502006 | 80.0 | 92.54 | 105.38 | 100 |
| 125 | 3 | 1 |
| 4HK*6500506 | 20.0 | 29.29 | 31.88 | 30 |
| 35 | 10 | 8 |
| 4HK*6500806 | 31.3 | 41.48 | 46.00 | 45 |
| 50 | 8 | 8 |
MV16C | 4HK*6501006 | 40.0 | 50.96 | 56.88 | 60 |
| 60 | 6 | 6 |
4HK16501506 | 60.0 | 72.63 | 81.88 | 90 |
| 90 | 3 | 3 | |
|
| ||||||||
| 4HK16501806 | 73.3 | 87.07 | 98.50 | 90 |
| 100 | 3 | 2 |
| 4HK16502006 | 80.0 | 94.29 | 106.88 | 100 |
| 125 | 3 | 1 |
| 4HK*6501006 | 40.0 | 53.08 | 58.75 | 60 |
| 60 | 6 | 6 |
| 4HK16501506 | 60.0 | 74.75 | 83.75 | 90 |
| 90 | 3 | 3 |
MV20D |
|
|
|
|
|
|
|
|
|
4HK16501806 | 73.3 | 89.19 | 100.38 | 90 |
| 110 | 3 | 2 | |
| 4HK16502006 | 80.0 | 96.42 | 108.75 | 100 |
| 125 | 3 | 1 |
| 4HK16502506 | 100.0 | 118.08 | 133.75 | 125 |
| 150 | 1 | 1/0 |
1.30 KW 3 phase not approved for single source power supply.
2.OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. * May be 0 (no breaker) or 1 (with breaker).
ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE
| Heat Kit - | Heater |
|
| Field Wiring |
|
| ||
|
|
|
|
|
|
| |||
Models | Amps | Min. Circuit Ampacity | Max. O.C.P.1 Amps/Type | 75°C Wire Size - AWG | |||||
Three Phase | |||||||||
| 240V |
|
|
|
|
|
| ||
|
| 208V | 240V | 208V | 240V | 208V | 240V | ||
|
|
| |||||||
|
|
|
|
|
|
|
|
| |
12B | 4HK06501025 | 23.1 | 30.9 | 34.3 | 35 | 35 | 8 | 8 | |
| 4HK06501025 | 23.1 | 30.9 | 34.3 | 35 | 35 | 8 | 8 | |
12D |
|
|
|
|
|
|
|
| |
4HK06501525 | 34.7 | 43.4 | 48.8 | 45 | 50 | 8 | 8 | ||
| 4HK06501825 | 41.4 | 50.6 | 57.1 | 50 | 60 | 8 | 6 | |
| 4HK06501025 | 23.1 | 32.6 | 35.1 | 35 | 35 | 8 | 8 | |
16C |
|
|
|
|
|
|
|
| |
4HK06501525 | 34.7 | 45.1 | 49.6 | 45 | 50 | 8 | 8 | ||
| 4HK06501825 | 41.4 | 52.4 | 58.0 | 60 | 60 | 6 | 6 | |
20D | 4HK06501025 | 23.1 | 34.8 | 37.6 | 35 | 40 | 8 | 8 | |
4HK06501525 | 34.7 | 47.3 | 52.1 | 50 | 60 | 8 | 6 | ||
|
1.O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. TABLE 1: Electrical Data - (For
|
| Minimum Circuit Ampacity | Max. O.C.P.1 Amps/Type | 75°C Wire Size - AWG | |||||||
Models | Heater |
|
|
|
| Circuit |
|
|
|
| |
Model |
|
|
|
|
|
|
|
|
|
| |
| 1st | 2nd | 3rd | 1st |
| 2nd | 3rd | 1st | 2nd | 3rd | |
|
|
| |||||||||
|
| 208/240 | 208/240 | 208/240 | 208/240 |
| 208/240 | 208/240 | 208/240 | 208/240 | 208/240 |
20D | 4HK16502525 | 41.0 / 44.9 | 31.3 / 36.1 | 45 / 45 |
| 35 / 40 | 8 / 8 | 8 / 8 |
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
6 | Unitary Products Group |