York MV Power Wiring, Kw & Mbh Conversions, ELECTRICAL DATA - COOLING UNIT ONLY 60 Hz, Line Power

Models: MV

1 12
Download 12 pages 44.69 Kb
Page 7
Image 7
KW & MBH CONVERSIONS

255427-YTG-F-1006

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60

 

 

Min. Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Model

Heater

 

Circuit

 

 

Circuit

 

 

Circuit

 

Model

 

 

 

 

 

 

 

 

 

 

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

 

 

 

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

 

 

 

 

 

 

 

 

 

 

 

 

MV12B

4HK165N1506

49.2 / 55.4

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10

/ 10

 

4HK16501506

49.2 / 55.4

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10

/ 10

MV12D

 

 

 

 

 

 

 

 

 

 

 

4HK16501806

45.6 / 51.2

39.7 / 45.8

50 / 60

40 / 50

8 / 6

8

/ 8

 

4HK16502006

49.2 / 55.4

43.3 / 50.0

50 / 60

45 / 50

8 / 6

8

/ 8

 

4HK16501506

51.0 / 56.9

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10

/ 10

MV16C

 

 

 

 

 

 

 

 

 

 

 

4HK16501806

17.3 / 52.7

39.7 / 45.8

50 / 60

40 / 50

8 / 6

8

/ 8

 

4HK16502006

51.0 / 56.9

43.3 / 50.0

50 / 60

45 / 50

8 / 6

8

/ 8

 

4HK16501506

53.1 / 58.8

21.7 / 25.0

60 / 60

25 / 25

6 / 6

10

/ 10

MV20D

4HK16501806

49.5 / 54.6

39.7 / 45.8

50 / 60

40 / 50

8 / 6

8

/ 8

4HK16502006

53.1 / 58.8

43.3 / 50.0

60 / 60

45 / 50

6 / 6

8

/ 8

 

 

4HK16502506

49.3 / 56.5

43.3 / 50.0

21.7 / 25.0

50 / 60

45 / 50

25 / 25

8 / 6

8

/ 8

10 / 10

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

KW & MBH CONVERSIONS

FOR

208-VOLT

230-VOLT

OPERATION MULTIPLY

240-VOLT

240-VOLT

TABULATED KW & MBH BY

.751

.918

ELECTRICAL DATA - COOLING UNIT ONLY (60 Hz)

 

Total Motor Amps

Minimum Circuit Ampacity

 

Minimum Wire Size

 

 

 

 

 

 

 

Max. O.C.P.1 Amps/Type

MODEL

 

60 Hertz

60 Hertz

 

 

 

AWG @ 75°C

 

208V

 

230V

208V

 

230V

 

 

MV12B

4.7

 

4.3

5.9

 

5.4

15

14

MV12D

4.7

 

4.3

5.9

 

5.4

15

14

MV16C

6.1

 

5.0

7.6

 

6.9

15

14

MV20D

7.8

 

7.0

9.7

 

8.8

15

14

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

POWER WIRING

TYPICAL WIRING WITHOUT ELECTRIC HEAT

GND. LUG

GND.

LUG

 

POWER

SUPPLY

1 PHASE ELECTRIC HEAT

WITH CIRCUIT BREAKER

& BREAKER BAR REMOVED

MULTI-SOURCE (15 - 25 KW) - 25 KW SHOWN

GND. LUG

GND.

 

LUG

POWER

 

SUPPLY 1

 

POWER

 

SUPPLY 2

 

POWER

 

SUPPLY 3

 

MAY BE 1, 2, OR 3

 

CIRCUIT BREAKERS

 

ELECTRIC HEAT

WITHOUT CIRCUIT BREAKER

3 PHASE (10 - 15 KW)

GND. LUG

GND.

 

LUG

POWER

SUPPLY

TERMINAL BLOCK

ELECTRIC HEAT

WITHOUT CIRCUIT BREAKER

SINGLE SOURCE (2.5 - 10 KW)

GND. LUG

GND.

 

LUG

POWER SUPPLY

TERMINAL BLOCK

CONNECT LEADS WITH WIRE NUTS (TYPICAL ALL HEAT KITS)

1 PHASE ELECTRIC HEAT WITH CIRCUIT BREAKER AS SHIPPED FROM FACTORY SINGLE SOURCE

(2.5 - 25 KW) - 25 KW SHOWN

GND. LUG

 

 

GND.

 

 

 

 

LUG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

SUPPLY

(JUMPER BAR)

MAY BE 1, 2, OR 3

CIRCUIT BREAKERS

POWER WIRING (208/230-1-60)

NOTE: USE ONLY COPPER CONDUCTORS

Line Power

Unitary Products Group

7

Page 7
Image 7
York MV specifications Power Wiring, Kw & Mbh Conversions, ELECTRICAL DATA - COOLING UNIT ONLY 60 Hz, Line Power