036-21346-001 Rev. A (202)

CAPACITY & PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

 

UNIT MODEL

COOLING

UNIT CHARGE

RATED CFM

SENSIBLE

SOUND RATING

NUMBER

CAPACITY 95°F

WEIGHT HCFC-22

TOTAL RATIO

 

 

 

 

 

 

 

 

PAC036H1081A

33,000

3.7 Lbs.

1,200

0.74

8.4

 

 

 

 

 

 

PAC048H1081A

47,000

7.0 Lbs.

1,500

0.68

8.4

 

 

 

 

 

 

PAC060H1081A

55,000

7.6 Lbs.

1,600

0.65

8.4

 

 

 

 

 

 

BLOWER PERFORMANCE DATA

UNIT SPEED

 

 

 

STATIC PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

PAC036H1081A

 

 

 

 

 

 

 

 

PAC048H1081A

.1

.2

.3

.4

.5

.6

.7

.8

PAC060H1081A

 

 

 

 

 

 

 

 

1837

1781

1720

1672

1607

1534

1443

1352

1243

 

 

 

 

 

 

 

 

 

1489

1468

1441

1412

1378

1336

1279

1204

1120

 

 

 

 

 

 

 

 

 

1238

1228

1216

1207

1180

1138

1088

1024

938

 

 

 

 

 

 

 

 

 

COMPRESSOR DATA

UNIT MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

 

 

 

 

MANUFACTURER

Bristol

Bristol

Bristol

 

 

 

 

COMPRESSOR MODEL

H23A383DBEA

H23A543DBEA

H26A68QDBEA

 

 

 

 

RPM (50 Hz)

3,000

3,000

3,000

 

 

 

 

RATED LOAD AMPS

6.1

8.0

9.6

 

 

 

 

LOCK ROTOR AMPS

39.0

53.0

79.0

 

 

 

 

BRANCH CIRCUIT SELECTION

6.1

8.0

9.6

CURRENT (BCSC)

 

 

 

 

 

 

 

ELECTRICAL DATA - Packaged A/C (No Electric Heat)

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

 

 

 

 

Power Supply Volts / Phase / Hertz

 

380--415 / 3 / 50

 

 

 

 

 

Maximum Fuse Size (Amp)

15

20

20

 

 

 

 

Maximum Circuit Breaker Size (Amp)

15

20

25

 

 

 

 

 

Min. Wire Size (AWG) Copper (75_C) Size -- Ft.

#14--0--80

#14--0--60

#12--0--60

#12--81--130

#12--61--90

#10--61--100

 

 

 

 

 

 

 

Total Input @ Rated Conditions

Running Amps

7.4

10.2

11.3

 

 

 

 

Running Watts

4,050

5,870

6,650

 

 

 

 

 

 

CONDENSER COIL DATA

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

 

 

 

 

Face Area, Sq. Ft.

9.25

11.24

11.24

 

 

 

 

Tube Diameter Inches

3/8

3/8

3/8

 

 

 

 

Rows Deep

1

2

2

 

 

 

 

Fins / Inch

18

15

15

 

 

 

 

Unitary Products Group

3

Page 3
Image 3