York PAC036 dimensions Physical and Electrical Data, Model, 036H1081A, 048H1081A, 060H1081A

Models: PAC036

1 8
Download 8 pages 18.19 Kb
Page 2
Image 2
Physical and Electrical Data

036-21346-001 Rev. A (202)

Physical and Electrical Data

MODEL

 

 

036H1081A

048H1081A

060H1081A

 

 

 

 

 

 

Unit Supply Voltage

 

 

 

380/415 - 3 - 50

 

 

 

 

 

 

 

Normal Voltage Range 1

 

 

 

342 - 455

 

Minimum Circuit Ampacity

12.4

14.8

16.8

 

 

 

 

Max. Overcurrent Device Amps 2

15

20

25

Compressor Type 3

 

 

Recip

Recip

Recip

Compressor Amps

 

Rated Load

6.1

8.0

9.6

 

 

 

 

 

 

Locked Rotor

39.0

53.0

79.0

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

No

No

No

 

 

 

 

 

 

Fan Motor Amps

 

Rated Load

1.8

1.8

1.8

 

 

 

 

 

 

Fan Diameter Inches

 

 

18“

20”

20”

 

 

 

 

 

 

 

 

 

 

Rated HP

1/3

1/3

1/3

Fan Motor

 

 

 

 

 

 

Nominal RPM

1,100

1,100

1,100

 

 

 

 

 

 

 

 

 

 

Nominal CFM

2,300

3,000

3,000

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

9.25

11.24

11.24

 

 

 

 

 

 

Condenser

 

Rows Deep

1

2

2

Coil Data

 

Fin / Inches

18

15

15

 

 

 

 

 

 

 

 

 

 

Tubing Diameter

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

3.61

4.67

4.67

 

 

 

 

 

 

Evaporator

 

Rows Deep

3

4

4

Coil Data

 

Fin / Inches

14

12

12

 

 

 

 

 

 

 

 

 

 

Tubing Diameter

5/16

5/16

5/16

 

 

 

 

 

 

 

 

 

Motor HP / RPM

3/4 / 1,000

3/4 / 1,050

3/4 / 1,100

 

 

 

 

 

 

Blower Data

 

Max. Static Pressure In. Water

.80

.80

.80

 

 

 

 

 

 

 

Dia. x Width (in.) / Rated CFM

10 x 7/1,200

10 x 7/1,500

10 x 7/1,600

 

 

 

 

 

 

 

 

 

 

Motor Full Load AMPS

3.0

3.0

3.0

 

 

 

 

 

 

 

Shipping Weight (lbs.)

 

 

 

270

354

360

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.)

 

 

4-4

7-0

7-10

 

 

 

 

 

 

Minimum Wire Size 4

 

 

#14 (0-80 ft.)

#14 (0-60 ft.)

#12 (0-60 ft.)

75º C Copper @ 400 Volt

 

 

#12 (81-130 ft.)

#12 (61-90 ft.)

#10 (61-100 ft.)

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker.

3.Rated under standard A.R.I. conditions of 80º DB/67º WB indoor, 95º outdoor.

4.Other temperature ratings of wire will have different rated ampacities. Refer to NEC for proper wire sizing recommendations. If using type NM or NM-B cable, wires must be sized to 60º C ampacities per NEC Article 336, Section 26. NEC and Local Codes superced any wire recommendations made in these specifications.

 

A

B

 

 

HEATER

 

D

ACCESSORY

 

KNOCK-OUTS

 

C

 

 

CONTROL

 

 

WIRING

 

 

OPENINGS

 

 

3/4” NPT FEMALE

G

12” DIAMETER

 

DRAIN OPENING

E

RETURN

 

 

F

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

UNIT DIMENSIONS (INCHES)

UNIT

A

B

C

D

E

F

G

 

 

 

 

 

 

 

 

036

44

30

26 5/8

24 1/8

7 3/4

22 1/2

12 5/8

 

 

 

 

 

 

 

 

048

46

32

28 5/8

26 1/8

7 3/4

22 1/8

12 5/8

 

 

 

 

 

 

 

 

060

46

32

28 5/8

26 1/8

7 3/4

22 1/8

12 5/8

 

 

 

 

 

 

 

 

2

Unitary Products Group

Page 2
Image 2
York PAC036 dimensions Physical and Electrical Data, Model, 036H1081A, 048H1081A, 060H1081A