036-21346-001 Rev. A (202)

CONDENSER FAN DATA

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

 

 

 

 

RPM

1,100

1,100

1,100

 

 

 

 

HP

1/3

1/3

1/3

 

 

 

 

Nameplate FLA

1.8

1.8

1.8

 

 

 

 

Dia. / No. Blades

18 / 3

20 / 4

20 / 4

 

 

 

 

CFM @ 0 S.P.

2,300

3,000

3,000

 

 

 

 

EVAPORATOR COIL DATA

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

 

 

 

 

Face Area (Sq. Ft.)

3.61

4.67

4.67

 

 

 

 

Tube Dia. Ins.

5/16

5/16

3/8

 

 

 

 

Rows Deep

3

4

4

 

 

 

 

Fins / Inch

14

12

12

 

 

 

 

Orifice

.071

.079

.081

 

 

 

 

EVAPORATOR BLOWER DATA

MODEL

PAC036H1081A

PAC048H1081A

PAC060H1081A

 

 

 

 

Motor HP -- RPM

3/4 -- 1,000

3/4 -- 1,050

3/4 -- 1,100

 

 

 

 

Static Pressure

.5

.5

.5

(Inches Water)

 

 

 

 

 

 

 

Blower Wheel

10 x 7

10 x 7

10 x 7

Dia. x Width

1,200

1,500

1,600

Rated CFM

 

 

 

 

 

 

 

Nameplate FLA

3.0

3.0

3.0

 

 

 

 

ELECTRICAL DATA - for Heat Packages Only

 

HEATER NUMBER

 

7642-8051 (5.0 KW)

7642-8101 (10.0 KW)

7642-8151 (15.0 KW)

 

 

 

 

 

Heater Branch Circuit Electrical Service

 

2 Leads + 1 Ground

2 Leads + 1 Ground

2 Leads + 1 Ground

 

 

 

 

 

 

 

 

415 VAC

 

CAPACITY

17,000

34,100

51,1000

 

 

 

 

 

 

Output Capacity

 

KW

5.0

10.0

15.0

 

 

 

 

 

 

 

 

380 VAC

 

CAPACITY

15,600

31,200

46,800

 

 

 

 

 

 

 

 

 

 

KW

4.6

9.2

13.7

 

 

 

 

 

 

 

 

 

 

Circuit Number

 

1

1

1

 

 

 

 

 

Nominal Circuit Load - Amps

 

12.1

24.1

36.2

 

 

 

 

 

Heater Circuit Maximum Fuse Size

 

20

35

45

 

 

 

 

 

Minimum Circuit Ampacity

 

15.9

27.9

40.0

 

 

 

 

 

Maximum wire Size

 

0 - 50 Ft.

12

10

8

(60° C) CU

 

51 - 100 Ft.

10

8

6

 

 

 

 

 

 

 

FIELD INSTALLED ACCESSORIES

Refer to price manual for specific model numbers:

Start Assist Kit, Time Delay Kit, Electric Heater Kit and Wall Thermostat.

Electric Heater Kit - Available in 3 different Kw capac- ities (5, 10, 15 Kw).

Wall Thermostat - The units are designed to operate with 24-volt electronic and electric-mechanical thermo- stats.

4

Unitary Products Group

Page 4
Image 4
York PAC036 Condenser FAN Data, Evaporator Coil Data, Evaporator Blower Data, Electrical Data for Heat Packages Only