CONDENSER FAN DATA
MODEL | PAC036H1081A | PAC048H1081A | PAC060H1081A |
|
|
|
|
RPM | 1,100 | 1,100 | 1,100 |
|
|
|
|
HP | 1/3 | 1/3 | 1/3 |
|
|
|
|
Nameplate FLA | 1.8 | 1.8 | 1.8 |
|
|
|
|
Dia. / No. Blades | 18 / 3 | 20 / 4 | 20 / 4 |
|
|
|
|
CFM @ 0 S.P. | 2,300 | 3,000 | 3,000 |
|
|
|
|
EVAPORATOR COIL DATA
MODEL | PAC036H1081A | PAC048H1081A | PAC060H1081A |
|
|
|
|
Face Area (Sq. Ft.) | 3.61 | 4.67 | 4.67 |
|
|
|
|
Tube Dia. Ins. | 5/16 | 5/16 | 3/8 |
|
|
|
|
Rows Deep | 3 | 4 | 4 |
|
|
|
|
Fins / Inch | 14 | 12 | 12 |
|
|
|
|
Orifice | .071 | .079 | .081 |
|
|
|
|
EVAPORATOR BLOWER DATA
MODEL | PAC036H1081A | PAC048H1081A | PAC060H1081A | |
|
|
|
| |
Motor HP | 3/4 | 3/4 | 3/4 | |
|
|
|
| |
Static Pressure | .5 | .5 | .5 | |
(Inches Water) | ||||
|
|
| ||
|
|
|
| |
Blower Wheel | 10 x 7 | 10 x 7 | 10 x 7 | |
Dia. x Width | ||||
1,200 | 1,500 | 1,600 | ||
Rated CFM | ||||
|
|
| ||
|
|
|
| |
Nameplate FLA | 3.0 | 3.0 | 3.0 | |
|
|
|
|
ELECTRICAL DATA - for Heat Packages Only
| HEATER NUMBER |
|
|
|
| |
|
|
|
|
| ||
Heater Branch Circuit Electrical Service |
| 2 Leads + 1 Ground | 2 Leads + 1 Ground | 2 Leads + 1 Ground | ||
|
|
|
|
|
|
|
| 415 VAC |
| CAPACITY | 17,000 | 34,100 | 51,1000 |
|
|
|
|
|
| |
Output Capacity |
| KW | 5.0 | 10.0 | 15.0 | |
|
| |||||
|
|
|
|
|
| |
380 VAC |
| CAPACITY | 15,600 | 31,200 | 46,800 | |
|
| |||||
|
|
|
|
|
| |
|
| KW | 4.6 | 9.2 | 13.7 | |
|
|
| ||||
|
|
|
|
|
|
|
Circuit Number |
| 1 | 1 | 1 | ||
|
|
|
|
| ||
Nominal Circuit Load - Amps |
| 12.1 | 24.1 | 36.2 | ||
|
|
|
|
| ||
Heater Circuit Maximum Fuse Size |
| 20 | 35 | 45 | ||
|
|
|
|
| ||
Minimum Circuit Ampacity |
| 15.9 | 27.9 | 40.0 | ||
|
|
|
|
| ||
Maximum wire Size |
| 0 - 50 Ft. | 12 | 10 | 8 | |
(60° C) CU |
| 51 - 100 Ft. | 10 | 8 | 6 | |
|
|
|
|
|
|
|
FIELD INSTALLED ACCESSORIES
Refer to price manual for specific model numbers:
Start Assist Kit, Time Delay Kit, Electric Heater Kit and Wall Thermostat.
Electric Heater Kit - Available in 3 different Kw capac- ities (5, 10, 15 Kw).
Wall Thermostat - The units are designed to operate with
4 | Unitary Products Group |