The acceptance ranges are selected using the system display. In the MATE3, the options are IEEE

and user.

The IEEE option allows a range of 108 – 132 Vac at 59.3 – 60.5 Hz

The user option does not have a fixed voltage setting. It follows the upper and lower limit settings in the Grid AC Input Mode and Limits menu. The default is a range of 108 – 132 Vac.

Reconnection delay is 6 seconds. Sell delay is 5 minutes. These settings are not adjustable.

Firmware Revision

This manual applies to Radian series inverter/chargers with a firmware version of 001.000.xxx or higher.

Default Settings and Ranges

 

Table 11

GS8048 Inverter Settings

 

 

 

 

 

 

 

 

 

Field

Item

 

Default

Minimum

 

Maximum

INVERTER Hot Key

Inverter Mode

 

Off

On, Off, or Search

CHARGER Hot Key

Charger Control

 

On

 

On or Off

AC Input Hot Key

AC Input Mode

 

Use

 

Drop or Use

 

Sensitivity (see page 16 for increments)

10

0

 

250

Search

Pulse Length

 

8 AC cycles

4 AC cycles

 

20 AC cycles

 

Pulse Spacing

 

60 AC cycles

4 AC cycles

 

120 AC cycles

 

Input Priority

 

Grid

 

Grid or Gen

AC Input and

Grid Input AC Limit

 

50 Aac

5 Aac

 

55 Aac

Current Limit

Gen Input AC Limit

 

50 Aac

5 Aac

 

55 Aac

 

Charger AC Limit

 

30 Aac

0 Aac

 

30 Aac

 

Input Mode

 

Grid Tied

Generator, Support, Grid Tied, UPS, Backup,

 

 

 

Mini Grid

 

 

 

 

 

Grid AC Input

Voltage Limit Lower

 

108 Vac

70 Vac

 

110 Vac

Mode and Limits

(Voltage Limit)Upper

 

132 Vac

125 Vac

 

140 Vac

 

Transfer Delay

 

6 AC cycles

0 AC cycles

 

240 AC cycles

 

Connect Delay

 

0.2 minutes

0.2 minutes

 

15 minutes

 

Input Mode

 

Generator

Generator, Support, Grid Tied, UPS, Backup,

 

 

 

Mini Grid

 

 

 

 

 

Gen AC Input

Voltage Limit Lower

 

108 Vac

70 Vac

 

110 Vac

Mode and Limits

(Voltage Limit) Upper

 

140 Vac

125 Vac

 

140 Vac

 

Transfer Delay

 

6 AC cycles

0 AC cycles

 

240 AC cycles

 

Connect Delay

 

0.5 minutes

0.2 minutes

 

15 minutes

AC Output

Output Voltage

 

240 Vac

220 Vac

 

260 Vac

Low Battery

Cut-Out Voltage

 

42 Vdc

36 Vdc

 

48 Vdc

Cut-In Voltage

 

50 Vdc

40 Vdc

 

56 Vdc

 

 

 

 

Absorb Voltage

 

57.6 Vdc

52 Vdc

 

64 Vdc

 

(Absorb) Time

 

1.0 hours

0.0 hours

 

24.0 hours

Battery Charger

Float Voltage

 

54.4 Vdc

48 Vdc

 

60 Vdc

 

(Float) Time

 

1.0 hours

0.0 hours

 

24.0 hours

 

Re-Float Voltage

 

50 Vdc

48 Vdc

 

52 Vdc

Battery Equalize

Equalize Voltage

 

58.4 Vdc

56 Vdc

 

68 Vdc

(Equalize) Time

 

1.0 hours

0.0 hours

 

24.0 hours

 

 

 