Specifications
Table 11 GS8048 Inverter Settings
Field
Item
Default
Minimum
Maximum
| 
 | Aux Control | Off | 
 | Off, Auto or On | |
| 
 | Aux Mode | Vent Fan | Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan, | ||
| 
 | DC Divert, IEEE, Source Status, AC Divert | ||||
| 
 | 
 | 
 | |||
| 
 | (Load Shed) ON: Batt > | 56 Vdc | 40 Vdc | 
 | 72 Vdc | 
| 
 | (Load Shed ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (Load Shed) OFF: Batt < | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| 
 | (Load Shed OFF) Delay | 18 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (Gen Alert) ON: Batt < | 44 Vdc | 40 Vdc | 
 | 56 Vdc | 
| 
 | (Gen Alert ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (Gen Alert) OFF: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| Auxiliary Output | (Gen Alert OFF) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (Vent Fan) ON: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| 
 | (Vent Fan) Off Delay | 18 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (DC Divert) ON: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| 
 | (DC Divert ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (DC Divert) OFF: Batt < | 44 Vdc | 40 Vdc | 
 | 56 Vdc | 
| 
 | (DC Divert OFF) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (AC Divert) ON: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| 
 | (AC Divert ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (AC Divert) OFF: Batt < | 44 Vdc | 40 vdc | 
 | 56 Vdc | 
| 
 | (AC Divert OFF) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | Aux Control | Off | 
 | Off, Auto or On | |
| 
 | Aux Mode | Gen Alert | Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan, | ||
| 
 | DC Divert, IEEE, Source Status, AC Divert | ||||
| 
 | 
 | 
 | |||
| 
 | (Load Shed) ON: Batt > | 56 Vdc | 40 Vdc | 
 | 72 Vdc | 
| 
 | (Load Shed ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (Load Shed) OFF: Batt < | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| 
 | (Load Shed OFF) Delay | 18 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (Gen Alert) ON: Batt < | 44 Vdc | 40 Vdc | 
 | 56 Vdc | 
| 
 | (Gen Alert ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| Auxiliary | (Gen Alert) OFF: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| (Gen Alert OFF) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | |
| Relay | 
 | ||||
| (Vent Fan) ON: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | |
| 
 | 
 | ||||
| 
 | (Vent Fan) Off Delay | 18 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (DC Divert) ON: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| 
 | (DC Divert ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (DC Divert) OFF: Batt < | 44 Vdc | 40 Vdc | 
 | 56 Vdc | 
| 
 | (DC Divert OFF) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (AC Divert) ON: Batt > | 56 Vdc | 48 Vdc | 
 | 72 Vdc | 
| 
 | (AC Divert ON) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| 
 | (AC Divert) OFF: Batt < | 44 Vdc | 40 vdc | 
 | 56 Vdc | 
| 
 | (AC Divert OFF) Delay | 30 Secs | 6 Secs | 
 | 1500 Secs | 
| Inverter Stacking | Stack Mode | Master | 
 | Master, Slave | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
| Power Save | Master Power Save Level | 0 | 0 | 
 | 31 | 
| (in Stacking Menu) | Slave Power Save Level | 1 | 1 | 
 | 31 | 
| 
 | Y | 
 | Y or N | ||
| Sell Voltage | 52 Vdc | 40 Vdc | 
 | 60 Vdc | |
| 
 | IEEE | 
 | IEEE or user | ||
| 
 | Input Voltage | 0 | 
 | 7 | |
| Calibrate | Output Voltage | 0 | 
 | 7 | |
| 
 | Battery Voltage | 0 | 
 | 0.8 | |
| 48 | 