Outback Power Systems GS8048 Error Messages, Error Troubleshooting Message Causes Possible Remedy

Models: GS8048

1 60
Download 60 pages 15.08 Kb
Page 41
Image 41

Troubleshooting

Error Messages

An Error is caused by a critical fault. In most cases when this occurs, the unit will shut down. The MATE3 system display will show an Event and a specific Error message. This screen is viewed using the MATE3 Home screen’s soft keys. (See the MATE3 manual for more instructions.) One or more messages will display Y (yes). If a message says N (no), it is not the cause of the error.

NOTE: The Radian series has no external indicators and requires a system display to identify an Error.

It is possible to clear an error by resetting the inverter. The inverter must be turned off, and then on, to reset it. Other possible steps are shown below (although it is still necessary to reset the inverter).

Table 3 Error Troubleshooting

Message

Causes

Possible Remedy

 

 

 

Low Output Voltage

Inverter’s AC regulation cannot be maintained

Check loads and measure current draw.

 

under high load conditions.

Remove loads as necessary.

 

 

 

AC Output Shorted

Inverter exceeded its maximum surge current

Check the loads and wiring. This issue is usually

 

due to severe overload.

the result of a wiring problem (a short), as

 

 

opposed to a poorly-sized load.

 

 

 

AC Output Backfeed

Usually indicates another AC power source (out

Disconnect the AC OUT wires from the inverter.

 

of phase with the inverter) was connected to

Check the wires (not the inverter) with an AC

 

the unit’s AC output.

voltmeter. If an AC source is present, shut it off.

 

 

 

Stacking Error

Programming problem among stacked units.

Check stacking programming and designation

 

(Often occurs if there is no master.)

of master. (See page 25.)

 

Can also occur when AC Output Backfeed

Check for output backfeed from an external

 

occurs.

source. Donnect output if necessary.

 

 

 

Low Battery V

DC voltage is below low battery cut-out set

If this error accompanies other errors, treat

 

point, usually due to battery discharge.

those conditions as appropriate.

 

This error can be triggered by other causes. It

If it occurs by itself: Recharge the batteries. The

 

can appear along with Low Output Voltage, AC

error will clear automatically if an external AC

 

Output Shorted, or AC Output Backfeed errors.

source is connected and the inverter’s charger

 

 

comes on.

 

 

 

High Battery V

DC voltage exceeded acceptable level (specified

Check the charging source. This problem is

 

on page 15).

usually the result of external charging. This

 

 

error will clear automatically if conditions are

 

 

removed.

 

 

 

Over Temperature

Inverter has exceeded its maximum allowed

Allow the inverter to remain off for a short time

 

operating temperature.

to reduce the temperature, or add external

 

 

cooling.

 

 

 

Phase Loss

A slave was ordered to transfer to AC by the

Check the AC voltage on the inverter input

 

master, but no AC is present. The unit continues

terminals. If AC voltage is not present, problem

 

inverting. This is the only “Error” that is not

is external. If AC voltage is present, the unit may

 

accompanied by a shutdown.

be damaged. Contact OutBack Technical

 

 

Support (see inside front cover of this manual).

 

 

 

900-0020-01-00 Rev A

39

Page 41
Image 41
Outback Power Systems GS8048 manual Error Messages, Error Troubleshooting Message Causes Possible Remedy