Outback Power Systems GS8048 manual Disconnect Messages, Voltage Maximum

Models: GS8048

1 60
Download 60 pages 15.08 Kb
Page 44
Image 44

Troubleshooting

Disconnect Messages

Disconnect messages explain the reason that the inverter rejected an AC source. The unit returns to inverting mode if turned on. This screen is viewed using the AC INPUT hot key on the MATE3. (See

the MATE3 manual for more instructions.) One or more messages will display Y (yes). If a message says N (no), it is not the cause of the disconnect. The MATE3 system display may generate a concurrent Event and Warning message following the disconnect. (See previous page.) If the AC source is removed, the Warning will be blank, but the cause of the last disconnect will remain.

Disconnect messages only display the reason for the disconnection; they cannot correct it. It is usually the result of external conditions, not an inverter fault. If the condition is corrected, the inverter will reconnect. A few settings can be changed to accommodate problems with the AC source.

The reasons shown in the Sell Status menu for ceasing to sell power (see next page) are not the same as disconnect messages, although they may be caused by the same circumstance. A grid-interactive unit can stop selling and still remain connected to the utility grid.

Table 5 Disconnect Troubleshooting

Message

Definition

Possible Remedy

 

 

 

Frequency Too High

The AC source has exceeded

Check AC source. If it is a generator, reduce speed.

 

66 Hz.

 

 

 

 

Frequency Too Low

The AC source has dropped below

Check AC source. If it is a generator, increase speed.

 

54 Hz.

 

 

 

 

Voltage > Maximum

The AC source has exceeded

Check AC source. The inverter’s acceptance range

 

140 Vac (default value) on either

is adjustable.

 

L1 or L2.

NOTE: Adjusting the range may accommodate a

 

 

 

 

problematic AC source, but it will not fix it.

 

 

 

Voltage < Minimum

The AC source has dropped below

Check AC source. The inverter’s acceptance range

 

108 Vac (default value) on either

is adjustable.

 

L1 or L2.

NOTE: Adjusting the range may accommodate a

 

 

 

 

problematic AC source, but it will not fix it.

 

 

 

Backfeed

Usually indicates another AC

Disconnect the AC OUT wires. Check the wires

 

power source (out of phase with

(not the inverter) with an AC voltmeter. If an AC

 

the inverter) was connected to the

source is present, shut it off. (This is more often

 

unit’s AC output.

accompanied by an AC Output Backfeed error.)

 

Can also occur if an out-of-phase

Check input source and wiring. This can be caused

 

AC source is connected to the

by a source with phase problems. It can also be

 

inverter’s AC input.

caused by transferring from one AC source to

 

 

another before the inverter can synchronize itself.

 

 

 

Phase Lock

The unit cannot remain in phase

Check AC source. This can be caused by a

 

with an erratic AC source.

generator with a poorly regulated output. Some

 

NOTE: This is not an “Error” as

generators behave this way when running out of

 

fuel. If necessary, set the Radian inverter to the

 

defined on page 39 and is not

 

Generator input mode. (See page 9.)

 

accompanied by a shutdown.

 

 

 

 

 

Island Detect

The unit detects something other

Check all input circuit breakers for an open circuit.

 

than normal grid conditions. This

This may (rarely) happen with a generator. If

 

is usually the result of an open AC

necessary, set the inverter to the Generator input

 

input circuit.

mode. (See page 9.)

 

 

 

42

900-0020-01-00 Rev A

Page 44
Image 44
Outback Power Systems GS8048 manual Disconnect Messages, Voltage Maximum