York SHP48 THRU 60 Models, Min. Circuit Ampacity, 75C Wire Size - AWG, Minimum Circuit Ampacity

Models: AHP18 THRU 60 SHP48 THRU 60

1 12
Download 12 pages 57.31 Kb
Page 10
Image 10

 

 

 

 

 

 

 

255029-YTG-J-1007

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

 

 

 

 

 

 

 

 

 

 

 

 

Heat Kit -

Heater

 

 

Field Wiring

 

 

 

 

 

 

 

 

 

Models

Amps

Min. Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Three Phase

 

240V

 

 

 

 

 

 

 

 

208V

240V

208V

240V

208V

240V

 

 

 

 

 

 

 

 

 

 

 

 

AHP24B**(N,H)21

4HK06501025

23.1

27.1

31.3

30

35

10

8

AHP30B**(N,H)21

4HK06501025

23.1

26.8

30.8

30

35

10

8

4HK065N1525

34.7

40.0

46.1

40

50

8

8

 

AHP36C**(N,H)21

4HK06501025

23.1

27.5

31.6

30

35

10

8

4HK06501525

34.7

40.0

46.1

40

50

8

8

 

 

4HK06501025

23.1

29.1

33.4

30

35

10

8

AHP42C**(N,H)21

4HK06501525

34.7

41.6

47.9

50

50

8

8

 

4HK06501825

41.4

48.9

56.3

50

60

8

6

AHP48D**(N,H)21

4HK06501025

23.1

29.3

33.6

30

35

10

8

4HK06501525

34.7

41.8

48.1

50

50

8

8

SHP48D**N21

4HK06501825

41.4

49.0

56.5

50

60

8

6

 

AHP60D**(N,H)21

4HK06501025

23.1

34.5

38.4

35

40

8

8

SHP60D**N21

4HK06501525

34.7

47.0

52.9

50

60

8

6

1.O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

2.Heaters are 3 Phase.

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-3-60

 

 

Minimum Circuit Ampacity

Max. O.C.P.1 Amps/Type

75°C Wire Size - AWG

Models

Heater

 

 

 

Circuit

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

 

 

 

 

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

208/240

AHP60D**(N,H)21

4HK16501825

31.9 / 35.4

22.4 / 25.9

- / -

35 / 40

25 / 30

- / -

8 / 8

10

/ 10

- / -

SHP60D**N21

 

 

 

 

 

 

 

 

 

 

 

4HK16502525

40.8 / 45.6

31.3 / 36.1

- / -

45 / 50

35 / 40

- / -

8 / 8

8

/ 8

- / -

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

10

Unitary Products Group

Page 10
Image 10