York SHP48 THRU 60 YTG-J-1007, Physical & Electrical Data, ELECTRICAL DATA - COOLING ONLY 60 Hz

Models: AHP18 THRU 60 SHP48 THRU 60

1 12
Download 12 pages 57.31 Kb
Page 6
Image 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

255029-YTG-J-1007

PHYSICAL & ELECTRICAL DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

 

 

 

 

 

AHP18B**(N,H)21

 

AHP24B**(N,H)21

 

AHP30B**(N,H)21

 

 

AHP36C**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower - Diameter x Width

 

 

 

9 x 6

 

 

10 x 9

 

 

10 x 9

 

 

10 x 10

Motor

 

HP

 

 

 

1/3 HP

 

 

1/4 HP

 

 

1/2 HP

 

 

3/4 HP

 

Nominal RPM

 

 

 

1075

 

 

1075

 

1075

 

1075

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

230

 

 

 

 

 

 

Amps

 

Full Load (230)

 

 

 

1.9

 

 

 

1.5

 

2.2

 

3.6

 

 

 

Type

 

 

 

 

 

 

 

DISPOSABLE OR PERMANENT

 

 

 

 

Filter1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

 

 

 

16 x 20 x 1

 

 

16 x 20 x 1

 

 

16 x 20 x 1

 

 

20 x 20 x 1

 

 

Permanent Type Kit

 

 

 

1PF0601BK

 

 

1PF0601BK

 

 

1PF0601BK

 

 

1PF0602BK

Shipping / Operating Weight (lbs.) - AHP*****N1

 

128 / 122

 

 

132 / 126

 

139 / 133

 

162 / 156

 

Shipping / Operating Weight (lbs.) - AHP*****H1

 

131 / 125

 

 

135 / 129

 

142 / 136

 

165 / 159

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

 

 

 

 

 

AHP42C**(N,H)21

 

AHP48D**(N,H)21

 

AHP60D**(N,H)21

 

 

 

 

 

 

 

 

 

 

 

SHP48D**N21

 

 

SHP60D**N21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower - Diameter x Width

 

 

 

10 x 10

 

 

10 x 10

 

 

11 x 10

 

 

 

 

Motor

 

HP

 

 

 

3/4 HP

 

 

3/4 HP

 

 

1 HP

 

 

 

 

 

Nominal RPM

 

 

 

1075

 

 

1075

 

1050

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

230

 

 

 

 

 

 

 

Amps

 

Full Load (230)

 

 

 

3.8

 

 

 

3.8

 

7.6

 

 

 

 

 

 

Type

 

 

 

 

 

DISPOSABLE OR PERMANENT

 

 

 

 

Filter1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

 

 

 

20 x 20 x 1

 

 

22 x 20 x 1

 

 

22 x 20 x 1

 

 

 

 

 

 

Permanent Type Kit

 

 

 

1PF0602BK

 

 

1PF0603BK

 

 

1PF0603BK

 

 

 

 

Shipping / Operating Weight (lbs.) -

 

164 / 158

 

 

AHP - 186 / 175

 

AHP - 189 / 178

 

 

 

 

AHP*****N1 and SHP*****N21

 

 

 

 

 

SHP - 182 / 171

 

SHP - 185 / 174

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shipping / Operating Weight (lbs.) - AHP*****H1

 

167 / 161

 

 

190 / 179

 

193 / 182

 

 

 

 

1. Field Supplied.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA - COOLING ONLY (60 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Motor Amps

 

Minimum Circuit Ampacity

 

Max. O.C.P.1

 

 

Minimum Wire

 

 

Models

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 Hertz

 

 

 

 

60 Hertz

 

 

 

 

 

 

 

 

 

 

 

Amps/Type

 

 

Size A.W.G.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208V

 

230V

 

208V

 

230V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AHP18B**(N,H)21

 

1.7

 

 

1.9

 

2.1

 

2.4

 

 

15

 

 

14

 

AHP24B**(N,H)21

 

1.4

 

 

1.5

 

1.8

 

1.9

 

 

15

 

 

14

 

AHP30B**(N,H)21

 

2

 

 

2.2

 

2.5

 

2.8

 

 

15

 

 

14

 

AHP36C**(N,H)21

 

3.3

 

 

3.6

 

4.1

 

4.5

 

 

15

 

 

14

 

AHP42C**(N,H)21

 

3.4

 

 

3.8

 

4.3

 

4.8

 

 

15

 

 

14

 

AHP48D**(N,H)21

 

3.4

 

 

3.8

 

4.3

 

4.8

 

 

15

 

 

14

 

SHP48D**N21

 

3.4

 

 

3.8

 

4.3

 

4.8

 

 

15

 

 

14

 

AHP60D**(N,H)21

 

7.6

 

 

7.6

 

9.5

 

9.5

 

 

15

 

 

14

 

SHP60D**N21

 

7.6

 

 

7.6

 

9.5

 

9.5

 

 

15

 

 

14

 

1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.