York TCGD18 THRU 60 warranty FC/MC/PC35 FC/MC/PC37 FC/MC/PC43, AHP30 AHP36

Models: TCGD18 THRU 60

1 18
Download 18 pages 6.5 Kb
Page 13
Image 13

359315-YTG-B-0408

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

TCGD30S41S1(H)

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

 

FC/MC/PC35

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSING

IDCFM

 

 

 

800

 

 

 

 

1000

 

 

 

 

1200

 

 

ENTERING AIR

ID DB (°F)

80

80

 

75

80

80

80

80

75

80

80

80

80

75

80

80

TEMPERATURE

ID WB (°F)

57

62

 

62

67

72

57

62

62

67

72

57

62

62

67

72

 

T.C.

28.4

31.4

 

30.8

33.1

34.4

29.8

31.8

31.4

33.4

34.5

31.2

32.3

32.1

33.7

34.7

65

S.C.

28.8

25.8

 

21.7

21.2

16.0

30.4

28.2

23.6

22.6

17.1

31.9

30.7

25.4

24.0

18.1

 

KW

1.7

1.7

 

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

1.7

 

T.C.

26.4

28.8

 

28.2

30.9

32.6

27.9

29.7

28.9

31.4

32.8

29.5

30.5

29.6

31.8

32.9

75

S.C.

26.9

24.7

 

20.5

20.3

15.4

28.5

27.1

22.6

22.0

16.4

30.2

29.5

24.6

23.7

17.5

 

KW

1.8

1.8

 

1.8

1.9

1.9

1.8

1.8

1.8

1.9

1.9

1.9

1.9

1.9

1.9

1.9

 

T.C.

24.4

26.3

 

25.6

28.8

30.9

26.0

27.5

26.4

29.3

31.0

27.7

28.7

27.1

29.8

31.2

85

S.C.

24.9

23.6

 

19.4

19.4

14.7

26.6

26.0

21.6

21.4

15.8

28.4

28.4

23.9

23.4

16.8

 

KW

2.0

2.0

 

2.0

2.0

2.1

2.0

2.0

2.0

2.0

2.1

2.0

2.0

2.0

2.1

2.1

 

T.C.

22.4

23.8

 

23.0

26.7

29.1

24.2

25.3

23.8

29.0

29.3

26.0

26.9

24.7

27.9

29.4

95

S.C.

22.9

22.5

 

18.2

18.5

14.1

24.8

24.9

20.7

21.2

15.1

26.7

27.3

23.1

23.1

16.2

 

KW

2.1

2.1

 

2.1

2.2

2.3

2.2

2.2

2.2

2.2

2.3

2.2

2.2

2.2

2.2

2.3

 

T.C.

20.5

21.8

 

20.4

23.7

26.3

22.0

23.1

21.3

24.3

26.4

23.6

24.5

22.1

24.8

26.4

105

S.C.

21.0

20.7

 

17.1

17.4

13.2

22.6

22.7

19.1

19.7

14.3

24.3

24.7

21.0

22.0

15.4

 

KW

2.3

2.3

 

2.3

2.4

2.4

2.4

2.4

2.3

2.4

2.5

2.4

2.4

2.3

2.4

2.5

 

T.C.

18.6

19.8

 

17.9

20.9

23.5

19.9

21.0

18.8

21.4

23.5

21.2

22.2

19.6

21.8

23.6

115

S.C.

19.1

18.9

 

15.9

16.4

12.3

20.5

20.5

17.5

18.6

13.5

22.0

22.2

19.1

20.9

14.7

 

KW

2.5

2.5

 

2.4

2.5

2.6

2.5

2.5

2.5

2.5

2.6

2.6

2.6

2.5

2.6

2.6

 

T.C.

16.8

17.9

 

15.4

18.1

20.7

17.8

18.9

16.2

18.5

20.7

18.9

19.9

17.1

18.8

20.7

125

S.C.

17.3

17.2

 

14.8

15.3

11.4

18.4

18.4

16.0

17.6

12.6

19.6

19.6

17.1

19.8

13.9

 

KW

2.7

2.7

 

2.6

2.7

2.8

2.7

2.7

2.6

2.7

2.8

2.7

2.7

2.7

2.7

2.8

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Air Handler

Coil

T.C.

S.C.

KW

FC/MC/PC35

1.00

1.00

1.00

FC/MC/PC37

1.00

1.00

1.00

FC/MC/PC43

1.00

1.00

1.00

HC36

1.00

1.00

1.00

HC42

1.00

1.00

1.00

AHP30

1.00

1.00

1.00

AHP36

1.00

1.00

1.00

AV36

1.02

1.03

0.93

MV12B

FC/MC35B

1.01

1.02

0.92

MV16C

FC/MC35C

1.02

1.02

0.93

MA12B

FC/MC35B

1.00

1.00

1.00

MV12B

FC/MC43B

1.01

1.02

0.92

MV16C

FC/MC43C

1.02

1.02

0.93

MA12B

FC/MC43B

1.00

1.00

1.00

F4FP040

1.00

1.00

1.00

Variable Speed

Coil

T.C.

S.C.

KW

Furnace

 

 

 

 

PV8*A12

FC/MC/PC32A

1.01

1.02

0.92

PV9*A12

FC/MC/PC32A

1.00

1.01

0.91

PV8*B16

FC/MC/PC35B

1.01

1.02

0.92

P(C,V)9*B12

FC/MC/PC35B

1.00

1.01

0.91

PV8*C16

FC/MC/PC35C

1.01

1.02

0.92

PV8*C20

FC/MC/PC35C

1.01

1.02

0.92

P(C,V)9*C16

FC/MC/PC35C

1.01

1.02

0.92

P(C,V)9*C20

FC/MC/PC35C

1.00

1.01

0.91

PV8*A12

FC/MC/PC37A

1.01

1.02

0.92

PV9*A12

FC/MC/PC37A

1.00

1.01

0.91

PV8*B16

FC/MC/PC43B

1.01

1.02

0.92

PV8*C16

FC/MC/PC43C

1.02

1.03

0.93

PV8*C20

FC/MC/PC43C

1.00

1.01

1.00

P(C,V)9*B12

FC/MC/PC43B

1.01

1.02

0.92

P(C,V)9*C16

FC/MC/PC43C

1.01

1.02

0.92

P(C,V)9*C20

FC/MC/PC43C

1.01

1.02

0.92

PV8*B16

HC36

1.01

1.02

0.92

P(C,V)9*B12

HC36

1.01

1.02

0.92

PV8*C16

HC42

1.02

1.03

0.93

PV8*C20

HC42

1.00

1.01

1.00

P(C,V)9*C16

HC42

1.01

1.02

0.92

P(C,V)9*C20

HC42

1.01

1.02

0.92

Johnson Controls Unitary Products

13

Page 13
Image 13
York TCGD18 THRU 60 FC/MC/PC35 FC/MC/PC37 FC/MC/PC43, AHP30 AHP36, MV12B FC/MC35B MV16C FC/MC35C MA12B FC/MC43B FC/MC43C

TCGD18 THRU 60 specifications

The York TCGD18 THRU 60 is a cutting-edge commercial air conditioning system designed to deliver exceptional performance and energy efficiency for a variety of applications. Built to cater to the needs of medium to large buildings, this unit is particularly renowned for its reliability, advanced features, and user-friendly design.

One of the standout features of the York TCGD18 THRU 60 is its versatile cooling capacity. With models ranging from 18 to 60 tons, this system is suitable for a wide range of spaces, from offices and retail stores to industrial facilities. Its ability to provide precise temperature control makes it an ideal choice in environments where maintaining an optimal climate is crucial.

In terms of technology, the TCGD series is equipped with advanced variable speed drive (VSD) technology. This innovation enables the compressor, fan, and pumps to adjust their speed based on the actual cooling demand, leading to significant energy savings. By operating only at the necessary capacity, the system minimizes energy waste and enhances overall efficiency, ultimately leading to lower operating costs.

Moreover, the York TCGD18 THRU 60 features a state-of-the-art microprocessor control system. This control system allows for comprehensive monitoring and diagnostics, making it easier for facility managers to optimize performance and identify potential issues before they escalate into costly repairs. Additionally, the user-friendly interface ensures that operators can quickly access data and adjust settings as needed.

Durability is another hallmark of the TCGD series. The units are constructed with high-quality materials designed to withstand harsh environments and demanding conditions. Corrosion-resistant casing and robust internal components ensure longevity and reliable operation, reducing the frequency of maintenance and replacement.

The design of the York TCGD18 THRU 60 also focuses on ease of installation and serviceability. Modular components offer flexibility during installation, while easily accessible key parts simplify routine maintenance, ensuring minimal downtime and maximal operational efficiency.

In summary, the York TCGD18 THRU 60 represents a blend of efficiency, reliability, and advanced technology. With its variable speed drive technology, intelligent microprocessor control, and durable construction, it is a top choice for commercial HVAC needs. As businesses continue to prioritize energy efficiency and sustainable practices, this model stands out as a leader in modern air conditioning solutions.