York YCAS0230 manual ELECTRICAL DATA Continued

Models: YCAS0230

1 28
Download 28 pages 46.49 Kb
Page 8
Image 8

ELECTRICAL DATA (Continued)

OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER

(One Field Provided Power Supply Circuit to the chiller. Field Connection to Circuit Breaker in ‘Option Panel’.

No internal Branch Circuit Protection per Motor Control Center.)

MODEL

 

 

FIELD SUPPLIED WIRING

 

SYSTEM #1

 

 

SYSTEM #2

 

VOLTS

 

FACTORY SUPPLIED BREAKER

COMPRESSOR

FANS

COMPRESSOR

FANS

YCAS

MCA1

 

RATING2

WIRE RANGE7 (LUGS)

RLA

X-LRA

FLA (EA)

RLA

X-LRA

FLA (EA)

 

 

 

0130EC

460

273

400

(2) 3/0-250

107

579

4.0

107

579

4.0

575

217

250

# 6 AWG - 350

86

463

3.1

86

463

3.1

 

0140EC

460

293

400

(2) 3/0-250

116

579

4.0

116

579

4.0

575

234

400

(2) 3/0-250

93

463

3.1

93

463

3.1

 

0150EC

460

307

400

(2) 3/0-250

128

856

4.0

115

579

4.0

575

246

400

(2) 3/0-250

103

715

3.1

92

463

3.1

 

0160EC

460

320

400

(2) 3/0-250

128

856

4.0

128

856

4.0

575

257

400

(2) 3/0-250

103

715

3.1

103

715

3.1

 

0170EC

460

335

400

(2) 3/0-250

140

856

4.0

128

856

4.0

575

268

400

(2) 3/0-250

112

715

3.1

103

715

3.1

 

0180EC

460

347

400

(2) 3/0-250

140

856

4.0

140

856

4.0

575

277

400

(2) 3/0-250

112

715

3.1

112

715

3.1

 

0200EC

460

375

630

(3) 2/0-400

149

856

4.0

149

856

4.0

575

299

400

(2) 3/0-250

119

715

3.1

119

715

3.1

 

0210EC

460

393

630

(3) 2/0-400

163

856

4.0

149

856

4.0

575

313

400

(2) 3/0-250

130

715

3.1

119

715

3.1

 

0230EC

460

407

630

(3) 2/0-400

163

856

4.0

163

856

4.0

575

324

400

(2) 3/0-250

130

715

3.1

130

715

3.1

 

NOTE: Wye-Delta Compressor Start not available with this option.

NOTES (pages 2 - 7)

1.Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If a Factory Mounted Control Transformer is provided, add the following to the system #2 MCA values in the YCAS Tables: -17, add 10 amps; -28, add 9 amps; -40, add 5 amps; -46, add 4 amps; -58, add 3 amps.

2.The recommendation disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the circuit, per N.E.C. 440 - 12A1.

3.Minimum fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs (U.L. Standard 1995, Section 36.1). Minimum fuse rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

4.Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

5.Minimum circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit, per circuit per U.L. 1995 Fig. 36.2. Minimum circuit breaker rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# fans x each fan motor FLA).

6.Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit, per U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + ( # fans x each fan motor FLA).

7.The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2), or (3) indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must be determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based on the National Electric Code and using copper connectors only. Field wiring must also comply with local codes.

8.A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control circuit grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.

9.The field supplied disconnect is a “Disconnecting Means” as defined in N.E.C. 100.B, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.

10.Units equipped with Star-Delta compressor motor start must also include Factory provided circuit breakers in each motor control center.

11.The wiring recommendations are based on the National Electrical Code using copper connectors only. Field wiring must also comply with local codes.

8

YORK INTERNATIONAL

Page 8
Image 8
York YCAS0230 manual ELECTRICAL DATA Continued