York YCAS0230 manual Control Power Supply, Circuit

Models: YCAS0230

1 28
Download 28 pages 46.49 Kb
Page 9
Image 9
CONTROL POWER SUPPLY

FORM 201.18-W1

OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION WITH FIELD SUPPLIED CIRCUIT PROTECTION

(One Field Provided Power Supply Circuit to the chiller. Field Connection to Power Terminal Block or Disconnect Switch in the ‘Option Panel’.

No internal Branch Circuit Protection per Motor Control Center.)

 

 

 

 

 

FIELD SUPPLIED WIRING

 

 

 

SYSTEM #1

 

 

SYSTEM #2

 

MODEL

VOLTS

FIELD PROVIDED POWER SUPPLY

FACTORY PROVIDED (LUGS) WIRE RANGE

COMPRESSOR

FANS

COMPRESSOR

 

FANS

YCAS

MCA1

MIN NF

D.E. FUSE

TERMINAL BLOCK

 

NF SERV DISC SW

 

DATA

DATA

 

DATA

 

DATA

 

 

 

 

 

 

 

DISC SW2

MIN3

MAX4

(LUGS) WIRE RANGE7

 

RATING2

(LUGS) WIRE RANGE7

RLA

 

X-LRA

FLA (EA)

RLA

 

X-LRA

 

FLA (EA)

 

 

 

 

 

 

 

0130EC

460

273

400

300

400

# 1 - 500

 

400

(2) 3/0-250

107

 

579

4.0

107

 

579

 

4.0

575

217

250

250

350

# 1 - 500

 

250

# 6 AWG - 350

86

 

463.2

3.1

86

 

463

 

3.1

 

 

 

 

 

0140EC

460

293

400

350

450

(2) # 2 - 300

 

400

(2) 3/0-250

116

 

579

4.0

116

 

579

 

4.0

575

234

250

300

350

# 1 - 500

 

250

# 6 AWG - 350

93

 

463.2

3.1

93

 

463

 

3.1

 

 

 

 

 

0150EC

460

307

400

350

450

(2) # 2 - 300

 

400

(2) 3/0-250

128

 

856

4.0

115

 

579

 

4.0

575

246

400

300

350

# 1 - 500

 

250

# 6 AWG - 350

103

 

715

3.1

92

 

463

 

3.1

 

 

 

 

 

0160EC

460

320

400

400

450

(2) # 2 - 300

 

400

(2) 3/0-250

128

 

856

4.0

128

 

856

 

4.0

575

257

400

300

400

# 1 - 500

 

400

(2) 3/0-250

103

 

715

3.1

103

 

715

 

3.1

 

 

 

 

 

0170EC

460

335

400

400

500

(2) # 2 - 300

 

400

(2) 3/0-250

140

 

856

4.0

128

 

856

 

4.0

575

268

400

300

400

# 1 - 500

 

400

(2) 3/0-250

112

 

715

3.1

103

 

715

 

3.1

 

 

 

 

 

0180EC

460

347

400

400

500

(2) # 2 - 300

 

400

(2) 3/0-250

140

 

856

4.0

140

 

856

 

4.0

575

277

400

350

400

(2) # 2 - 300

 

400

(2) 3/0-250

112

 

715

3.1

112

 

715

 

3.1

 

 

 

 

 

0200EC

460

375

400

450

600

(2) # 1 - 500

 

400

(2) 3/0-250

149

 

856

4.0

149

 

856

 

4.0

575

299

400

350

450

(2) # 2 - 300

 

400

(2) 3/0-250

119

 

715

3.1

119

 

715

 

3.1

 

 

 

 

 

0210EC

460

393

600

450

600

(2) # 1 - 500

 

400

(2) 3/0-250

163

 

856

4.0

149

 

856

 

4.0

575

313

400

350

450

(2) # 2 - 300

 

400

(2) 3/0-250

130

 

715

3.1

119

 

715

 

3.1

 

 

 

 

 

0230EC

460

407

600

450

600

(2) # 1 - 500

 

630

(3) 2/0-400

163

 

856

4.0

163

 

856

 

4.0

575

324

400

400

500

(2) # 2 - 300

 

400

(2) 3/0-250

130

 

715

3.1

130

 

715

 

3.1

 

 

 

 

 

LEGEND

ACR-LINE C.B.

D.E.

DISC SW

FACT MOUNT CB FLA

HZ

MAX

MCA

MIN MIN NF RLA S.P. WIRE

UNIT MTD SERV SW WYE-DELTA X-LRA

Y-LRA

ACROSS THE LINE START

 

CONTROL POWER SUPPLY

 

CIRCUIT BREAKER

UNIT

CONTROL

MIN

MAX DUAL

NON-FUSED

DUAL ELEMENT FUSE

POWER

CIRCUIT

ELEMENT

DISC. SW.

DISCONNECT SWITCH

VOLTAGE

SUPPLY

AMPACITY

FUSE SIZE

SIZE

FACTORY-MOUNTED CIRCUIT BREAKER

 

Standard

 

 

 

 

FULL LOAD AMPS

 

 

 

 

HERTZ

Models w/o

115-1-60

20A

20A

30A

MAXIMUM

Transformers

 

 

 

 

MINIMUM CIRCUIT AMPACITY

 

 

 

 

 

MINIMUM

 

 

 

 

 

MINIMUM NON-FUSED

 

 

VOLTAGE CODE

 

RUNNING LOAD AMPS

 

 

 

 

 

-17 = 200-3-60

 

SINGLE-POINT WIRING

 

 

 

 

 

-28 = 230-3-60

 

UNIT-MOUNTED SERVICE (NON-FUSED DISCONNECT SWITCH)

 

-40 = 380-3-60

 

WYE-DELTA START

 

 

 

 

 

-46 = 460-3-60

 

ACROSS-THE-LINE INRUSH LOCKED ROTOR AMPS

 

 

 

-58 = 575-3-60

 

WYE-DELTA INRUSH LOCKED ROTOR AMPS

 

 

 

 

 

 

 

 

YORK INTERNATIONAL