Omega CNI16 Stop BIT Submenu, BUS Format Submenu, Modbus Protocol Submenu, Line Feed Submenu

Page 55

STOP BIT SUBMENU:

Press d 15) Display flashes previous selection for “Stop Bit”. Press b 16) Scroll through the available selections: 1-BIT, 2-BIT.

Press d 17) Display shows STRD stored message momentarily and then advances to BUS.F only, if it was changed, otherwise press a to advance to BUS.F Bus Format Submenu.

BUS FORMAT SUBMENU:

Determines Communications Standards and Command/Data Formats for transferring information into and out of the controller via the Serial Communications Bus. Bus Format submenus essentially determine how and when data can be accessed via the Serial Communications of the device.

Press d 18) Display advances to M.BUS Modbus Submenu.

MODBUS PROTOCOL SUBMENU:

Press d 19) Display flashes previous selection for M.BUS. Press b 20) Scroll through the available selections: NO, YES.

Press d 21) Display shows STRD stored message momentarily and then advances to _LF_ only, if it was changed, otherwise press a to advance to _LF_ Line Feed submenu.

To select iSeries Protocol, set Modbus submenu to “No”.

To select Modbus Protocol, set Modbus submenu to “Yes”.

If Modbus Protocol was selected, the following Communications Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not attempt to change these parameters.

LINE FEED SUBMENU:

Determines if data sent from the instrument will have a Line Feed appended to the end - useful for viewing or logging results on separate lines when displayed on communications software at a computer.

Press d 22) Display flashes previous selection for “Line Feed”. Press b 23) Scroll through the available selections: NO, YES.

Press d 24) Display shows STRD stored message momentarily and then advances to ECHO only, if it was changed, otherwise press a to advance to ECHO Echo Submenu.

ECHO SUBMENU:

When valid commands are sent to the instrument, this determines whether the command will be echoed to the Serial Bus. Use of echo is recommended in most situations, especially to help verify that data was received and recognized by the controller.

51

Image 55
Contents User’s Guide Servicing North America Table of Contents List of Tables List of FiguresTIP Description Part IntroductionEMC Considerations Safety ConsiderationsBefore You Begin Front Panel Part SetupOption PowerRear Panel Connections InputMain Power Connections Fuse Requirement see specifications Electrical Installation Power ConnectionsThermocouple Thermocouple Wiring Hookup TC Wire Color ChartOhm Wiring Hookup 3 Two/Three/Four-Wire RTDProcess Voltage Process CurrentWithout Sensor Excitation Use copper conductors Wiring OutputsSnubber Circuits Wiring Hookup RS-232 Output Wiring Hookup b RS-485 Output Wiring Hookup8DH Dual Horizontal 8DV Dual Vertical Dual Display Color SetupUse a jumper for Green or RED, never leave S1 open Turning your Controller On for the First Time Operation Configuration Mode IntroductionButton Function in Configuration Mode PartFlow Chart for ID and Setpoints Menu ConfigurationEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Entering Your NON-DEFAULT Full Security ID NumberID Number Setpoint Set PointsEnter Configuration Menu Configuration MenuInput Type Menu Thermocouple Types Input Type ThermocoupleEnter Input Type Menu Thermocouple SubmenuRTD Value Submenu Input Type RTDRTD Submenu RTD TypesProcess Types Reading ConfigurationInput Type Process Process SubmenuFilter Constant Submenu Enter Reading Configuration MenuTemperature Unit Submenu Decimal Point SubmenuINPUT/READING Scale and Offset Submenu Reading Configuration If Process was selectedRange Conversion Number Conversion TableEnter Alarm 1 Menu AlarmAlarm 1 ABSOLUTE/DEVIATION Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 LATCH/UNLATCH Submenu Active Submenu Contact Closure SubmenuAlarm 1 LOW Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 HI Value Submenu Enter Analog Output Menu Analog Output RetransmissionOUT Analog Output ENABLE/DISABLE SubmenuCURRENT/VOLTAGE Submenu ReadingFor example Alarm 2 ENABLE/DISABLE Submenu Enter Alarm 2 MenuEnter Loop Break Time Menu Loop Break ENABLE/DISABLE SubmenuReading Adjust Submenu Loop Break Time/Field CalibrationThermocouple Field Calibration Submenu Setpoint Deviation ENABLE/DISABLE SubmenuOutput Flow Chart for OutputSelf Submenu Enter Output 1 MenuMINIMUM/PERCENT LOW Submenu Control Type Output MAXIMUM/PERCENT High SubmenuAuto PID Submenu Action Type SubmenuAnti Integral Submenu Proportional Band Submenu Start Auto Tune PIDRate Setup Submenu Reset Setup SubmenuCycle Time Submenu Deadband Submenu Damping Factor SubmenuControl Type Submenu Enter Output 2 MenuAction Type Submenu Cycle Time Submenu Ramp & Soak Ramp ENABLE/DISABLE SubmenuEnter Ramp and Soak Menu Ramp Value Submenu Soak ENABLE/DISABLE SubmenuSoak Value Submenu ID Code Entering or Changing Your NON-DEFAULT ID CodeEnter ID Code Menu Full Security Level Submenu Entering or Changing Your Default ID CodeSETPOINT/ID Security Level Submenu Communication Option 13 Flow Chart for Communication OptionParity Submenu Enter Communication Option MenuCommunication Parameters Submenu Baud SubmenuLine Feed Submenu Stop BIT SubmenuBUS Format Submenu Modbus Protocol SubmenuCommunication Interface Standard Submenu Data Flow Mode SubmenuData Separation Character Submenu Peak Value Submenu Alarm Status SubmenuData Format Submenu Main Reading SubmenuTransmit Time Interval Value Submenu Address Setup SubmenuAddress Value Submenu Transmit Time Interval SubmenuNormal Color Display Submenu Alarm 1 Display Color SubmenuDisplay Color Selection Enter Display Color Selection MenuGreen RED Amber Alarm 2 Display Color SubmenuExample Display Colors change sequencesRED Green Control Part SpecificationsNmrr CmrrSSR Control Output 1Insulation ExcitationGeneral Input Type Range Accuracy Input PropertiesFactory preset value Part Factory Preset ValuesMenu Items Factory Preset Values Notes Measurement Category Part CE Approvals InformationPage Page Return REQUESTS/INQUIRIES WARRANTY/DISCLAIMERData Acquisition TemperaturePRESSURE, Strain and Force FLOW/LEVEL

CNI16, CNI32, CNI8DH, CNI8C, CNI16D specifications

The Omega CNI series, including models CNI8DV, CNI8, CNI8DH, CNI32, and CNI16, represents a cutting-edge line of sensors designed for various industrial applications. Known for their reliability and versatile functionality, these sensors play a crucial role in monitoring and controlling multiple parameters in different environments.

The CNI8DV model is equipped with dual voltage outputs, enabling flexibility in integration with various systems. This feature allows users to choose between standard and high voltage operating conditions, making it suitable for a wide range of applications. Its high precision and quick response times deliver accurate measurements, essential for critical processes where timing and accuracy are paramount.

The CNI8 model offers robust performance with an extensive measurement range. This model is particularly noteworthy for its advanced signal processing technology, which improves measurement stability and accuracy. It utilizes digital filtering and calibration techniques to enhance performance and ensure consistent output, minimizing the effects of environmental fluctuations.

In the CNI8DH variant, enhanced durability is a key characteristic. This model features a more robust housing that protects it from harsh environmental conditions. It is designed to withstand high humidity, dust, and varying temperatures, making it suitable for outdoor applications or environments where exposure to elements is a concern. It also includes real-time diagnostics to monitor its operational health, allowing for proactive maintenance.

The CNI32 model stands out with its higher measurement capacity and greater flexibility in configurations. This sensor can handle multiple input types, including temperature, pressure, and flow rates. Its modular design allows users to customize it for specific applications, making it ideal for industries ranging from manufacturing to energy production.

The CNI16 model is designed for standard applications requiring precision and reliability. Its compact size allows for easy installation in tight spaces, while still delivering high performance. Enhanced connectivity options support integration with various data acquisition systems and industrial networks, enabling seamless data collection and monitoring.

In summary, the Omega CNI series exemplifies state-of-the-art sensor technology, offering a range of features that cater to diverse industrial needs. From versatile voltage outputs in the CNI8DV to the rugged design of the CNI8DH, each model is engineered to provide accurate, reliable readings with the ability to withstand challenging conditions. Whether for monitoring environmental conditions or precise measurements in manufacturing processes, the CNI series continues to be a top choice for professionals seeking high-quality sensors.