Snapper 6200 manual Receptacles, Battery Charger, Stopping the Engine

Page 11

Snapper 6200W Portable Generator

Stopping the Engine

1.Turn OFF and unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.

2.Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.

3.Turn engine off according to instructions given in the engine operator’s manual.

4.Move fuel valve to “Off” position.

RECEPTACLES

CAUTION

Receptacles may be marked with rating value greater than generator output capacity.

NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.

DO NOT overload generator. See “Don’t Overload Generator”.

120/240 Volt AC, 30 Amp, Locking Receptacle

Use a NEMA L14–30 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volt AC loads at 30 Amps (or greater) (Figure 6).You can use the same 4–wire cord if you plan to run a 120 Volt load.

Figure 6 — 120/240 Volt AC, 30 Amp Receptacle

4-Wire Cord Set

240V

120V 120V

W (Neutral)

Y (Hot)

X (Hot)

NEMA L14-30

Ground (Green)

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 6,200 watts of power (6.2 kW) at 25.8 Amps for 240 Volts or two independent 120 Volt loads at 25.8 Amps each.The outlet is protected by push–to–reset circuit breakers.

120 Volt AC, 20 Amp, Duplex Receptacles

Each duplex receptacle (Figure 7) is protected against overload by a push–to–reset circuit breaker.

Figure 7 — 120 Volt, 20 Amp Duplex Receptacle

Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 2,400 watts (2.4 kW) at 20 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 20 Amps (or greater).

BATTERY CHARGER

Use battery float charger jack to keep the starting battery charged and ready for use. Battery charging should be done in a dry location, such as inside a garage.

1.Plug charger into unit’s “Battery Float Charger” jack, which is located on the starter switch (Figure 8). Plug battery charger into a 120 Volt AC wall receptacle.

Figure 8 — Battery Charger Jack

2.Unplug charger from unit and wall outlet when generator is being started and while it is in operation.

3.Keep this charger plugged in when generator is not in use to prolong battery life.The charger has a built in float equalizer and will not overcharge the battery, even when plugged in for an extended period of time.

IMPORTANT: See “Battery Maintenance” on page 13 for additional information.

11

Image 11
Contents Watt Generator Equipment Description Table of ContentsSafety Rules When Transporting or Repairing Equipment When Adding or Draining FuelWhen Starting Equipment When Operating EquipmentWhen Testing for Engine Spark When Adjusting or Making Repairs to Your GeneratorKnow Your Generator Electric Start AssemblyCarton Contents Check Battery / Attach Negative Battery WireRefer to and install the wheel kit as follows Install Wheel KitAdd Engine Oil When Adding FuelBefore Starting the Engine Add FuelGenerator Location Using the GeneratorConnecting to a Building’s Electrical System System GroundDo not Overload the GENERATOR. See Don’t Overload Generator Connecting Electrical LoadsOperating Generator Starting the Engine120/240 Volt AC, 30 Amp, Locking Receptacle Battery ChargerReceptacles Stopping the EngineExample Power ManagementDont Overload Generator CapacityGeneral Maintenance Recommendations SpecificationsOther Storage Tips StorageGenerator Storage Engine StorageProblem Cause Correction TroubleshootingSnapper 6200W Portable Generator Equipment Consumer Use Commercial Use Snapper Owner Warranty Policy Effective August 1About your equipment warranty Advertencia Tabla DE ContenidosDescripción DEL Equipo Reglas DE SeguridadCuando Transporte O Repare EL Equipo Cuando Añada Combustible O Vacíe EL DepósitoCuando Ponga EN Funcionamiento EL Equipo Cuando Opere EL EquipoCuando Pruebe LA Bujía DEL Motor PrecauciónCuando Ajuste O Haga Reparaciones a SU Generador Tomacorriente con Dispositivo de Seguridad de Conozca SU GeneradorTapa del Depósito del Aceite Llene el motor con aceite Tomacorriente Dobles de 120 Voltios AC, 20 AmpContenido de la Caja MontajeArranque Eléctrico Desembalaje del GeneradorInstale el Juego de Ruedas Como Sigue Figura Instale el Juego de RuedasCuando Añada Combustible Antes DE Darle Arranque AL MotorAgregar Aceite al Motor Agregue CombustibleConexión al Sistema Eléctrico de un Edificio USO DEL GeneradorTierra del Sistema Ubicación del GeneradorNo Sobrecargue EL GENERADOR.Vea No Sobrecargue Generador Operando EL GeneradorEncienda el Motor Conexion De Cargas Electricas120/240 Voltios AC, 30 Amp, Receptáculo de Seguridad Receptáculos PrecauciónCargador DE Batería Parado Del MotorEjemplo No Sobrecargue GeneradorCapacidad Control de la EnergíaRecomendaciones Generales DE Mantenimiento EspecificacionesOtras Sugerencias Para el Almacenando AlmacenamientoAlmacenando el Generador Almacenando el MotorDiagnositicos DE Averías Problemo Accion CausaAcerca de la seguridad de su equipo Efectiva desde el 1 ro de AgostoEquipo Para Uso Del Consumidor Para Uso Comercial Garantía Limitada