Generac How to Set the Exercise Timer for Your Portable Generator

Page 18

Section 3 — Operation

Generac Air-cooled 7 kW, 12 kW and 15 kW Generators

DANGER

Do not attempt to activate the transfer switch manually until all power voltage supplies

to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.

5.Use the manual transfer handle inside the trans- fer switch to move the main contacts back to their “Utility” position, i.e., loads connected to the util- ity power source (Figure 3.2).

6.Turn ON the utility power supply to the transfer switch using the means provided.

7.Set the system to automatic operation as outlined in “Automatic Transfer Operation,” Section 3.3.

3.6SETTING THE EXERCISE TIMER

The generator is equipped with an exercise timer. Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed. During this exercise period, the unit runs for approx- imately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle.

A switch on the control panel (see Figure 3.1) allows for selection of the day and time for system exercise. To select the desired day and time of day, the follow- ing sequence must be done at that time.

1.Verify that the AUTO/OFF/MANUAL switch is set to AUTO.

2.Hold down the set timer switch until the genera- tor starts (approximately 10 seconds) and then release.

3.The generator will start and run for approximately 12 minutes and then shut down on its own. The exerciser will then be set to run at that time of day every week.

NOTE:

The exerciser will only work in the AUTO mode and will not work unless this procedure is per- formed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected. The exerciser WILL NOT work if dip switch 2 (Remote Not Auto) on the controller printed circuit board is ON.

3.7PROTECTION SYSTEMS

‹3.7.1 LOW OIL PRESSURE SWITCH

This switch (Figure 3.3) has normally closed contacts that are held open by engine oil pressure during crank- ing and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.

‹3.7.2 HIGH TEMPERATURE SWITCH

This switch’s contacts (Figure 3.3) close if the tem- perature should exceed approximately 140º C (284º F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.

Figure 3.3 – Low Oil Pressure and

High Temperature Switches

Low Oil Switch

 

High Temp Switch

 

 

 

 

 

 

Loosen

Oil

Drain

Hose

Oil Filter

‹3.7.3 OVERCRANK

This feature prevents the generator from damaging itself when it continually attempts to start and anoth- er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED will light indicating an overcrank failure. The AUTO/OFF/MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.

NOTE:

If the fault is not repaired, the overcrank feature will continue to activate.

16 Generac® Power Systems, Inc.

Image 18
Contents Installation Introduction Authorized Dealer LocationTroubleshooting Post Installation Start-up AdjustmentsMaintenance Introduction Inside Front CoverGeneral Hazards Electrical Hazards ‹ Standards IndexUNPACKING/INSPECTION Protection SystemsSystem SET LED Generator GfciSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Fuel Consumption Reconfiguring the Fuel SystemFuel Requirements Recommendations 1 7 KW, 410CCGenerator Transfer SwitchLocation 2.1 7 kW, 12 kW and 15 kW UnitsBattery Installation BatteryCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic OperationAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units Voltage Regulator Adjustment 2 12 KW and 15 KW UnitsSequence of Automatic Operation BREAK-IN ProcedureAutomatic Transfer Operation ‹ 3.2.1 Auto Position‹ 3.5.2 Transfer Back to Utility Power Source Manual Transfer Operation‹ 3.7.2 High Temperature Switch Setting the Exercise Timer‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.3 OvercrankApproximate Crank Cycle Times Checking the Engine OIL LevelChanging the Engine OIL ‹ 3.7.4 Overspeed‹ 4.3.2 OIL Change Procedure Changing the OIL Filter‹ 4.5.1 7 KW, 12 KW and 15 KW Generators Battery Maintenance Spark PlugsAdjusting Valve Clearance Cooling System‹ 4.12.1 Removal from Service OUT of Service Procedure‹ 4.12.2 Return to Service Corrosion ProtectionService Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR SW1 Exploded Views and Parts Lists Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description 1310 Sleeve Exploded Views and Parts Lists Item Part NO. QTY. Description 14 20 QTY Description Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists PIN, Piston D20 Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome Exploded Views and Parts Lists CASTING, Twin Regulator Housing Dimensions Generac Air-cooled 7 kW, 12 kW and 15 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule
Related manuals
Manual 59 pages 50.68 Kb

04674-2, 04675-3, 04673-2 specifications

Generac, a prominent name in the power equipment sector, offers a range of reliable and efficient energy solutions, including the models Generac 04673-2, 04675-3, and 04674-2. These models are designed to meet diverse consumer needs, from residential applications to larger commercial setups, providing dependable backup power during outages.

The Generac 04673-2 is a standout home standby generator specifically engineered for residential use. It boasts an automatic operation feature, ensuring that power is restored within seconds of an outage. This model operates on a robust Generac engine, delivering a reliable power output that can support essential household appliances and systems, including HVAC units, refrigerators, and sump pumps. One of the main characteristics of this generator is its Quiet Test mode, which runs at a lower RPM to minimize noise while conducting weekly self-tests, ensuring that the system is always ready when needed.

Moving on to the Generac 04675-3, this model offers enhanced features tailored for users needing higher power output. With a larger capacity, it can handle more demanding power needs, making it suitable for larger homes or small businesses. The 04675-3 is equipped with advanced technologies, including the Mobile Link™ remote monitoring system, which enables users to check the status and performance of their generator from anywhere using a smartphone or computer. This connectivity empowers users with real-time information and alerts regarding their generator's operational performance.

The Generac 04674-2 model rounds out the trio, engineered for those who need a powerful standby generator with a slightly different configuration. It features the same robust engine as the other models, ensuring reliability and user-friendly operation. Its standout feature is the integrated transfer switch capability, which allows for seamless transfer of power from the grid to the generator without manual intervention. This model also supports various fuel types, providing flexibility depending on user preference and availability.

All three Generac models focus on safety and efficiency, incorporating features such as excellent ventilation systems, all-weather enclosures, and user-friendly control panels. They are designed for low maintenance, ensuring long-lasting performance without extensive upkeep. With Generac's commitment to innovation and quality, these generators offer peace of mind, enabling users to maintain their lifestyles and operations without interruption during power outages. Whether for home or business use, the Generac 04673-2, 04675-3, and 04674-2 models represent a reliable choice in emergency power solutions.