Generac 04673-2, 04675-3 Fuel Requirements Recommendations, Fuel Consumption, 1 7 KW, 410CC

Page 9

Section 1 — General Information

Generac Air-cooled 7 kW, 12 kW and 15 kW Generators

1.6FUEL REQUIREMENTS

AND RECOMMENDATIONS

With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank.

The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See Section 1.9 for instructions on reconfiguration of the fuel system.

Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.

Required fuel pressure for natural gas is 5 inches to 7 inches water colum (0.18 to 0.25 psi); and for

3.Remove the battery (if installed).

4.Disconnect wire #0 and wire #14 from the gas solenoid on top of the demand regulator.

5.Remove the carburetor fuel hose from the outlet port of the demand regulator.

6.Remove the demand regulator by removing the fastener that retains the regulator mounting bracket.

7.Remove the square headed steel pipe plug from outlet port #1 and the brass hose barb fitting from outlet port #2.

8.Refit the brass hose barb fitting to outlet port #1 and the square headed steel pipe plug to outlet port #2.

9.Reverse procedure steps 1-5 to reinstall demand regulator.

10.Reverse the procedure to convert back to natural gas.

Figure 1.3 – Demand Regulator

liquid propane, 11 inches to 14 inches of water column (0.4 to 0.5 psi).

NOTE:

Any piping used to connect the generator to the fuel supply should be of adequate size to ensure the fuel pressure NEVER drops below 4 inches water colum for natural gas or 10 inches water col- umn for liquid propane for all load ranges.

1.7FUEL CONSUMPTION

FUEL HOSE

BRASS HOSE FITTING

ADJUSTMENT SCREW

HOSE & PLUG

SWITCHED SIDES

PIPE

FUEL HOSE

PLUG

 

BRASS HOSE

FITTING

OUTLET

PORT

FUEL JET

 

Model #

Nat. Gas (*)

LP Vapor (**)

 

 

 

1/2 Load

Full Load

1/2 Load

Full Load

 

 

04673

66

119

0.82/30

1.47/54

 

 

04674

152

215

1.53/56

2.08/76

 

 

04675

156

220

1.58/58

2.40/88

 

*Natural gas is in cubic feet per hour.

**LP is in gallons per hour/cubic feet per hour.

1.8RECONFIGURING THE FUEL SYSTEM

1.8.1 7 KW, 410CC

To reconfigure the fuel system from NG to LP, follow these steps (Figure 1.3):

NOTE:

The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres- sure of 11 to 14 inches of water column (0.4 to 0.5 psi) to the fuel inlet of the generator MUST BE SUPPLIED.

NG FUEL SYSTEM

LP FUEL SYSTEM

NOTE:

The natural gas adjustment screw is preset during installation and should not need any further adjustment.

1.8.2 12KW AND 15KW, V-TWIN ENGINES

To reconfigure the fuel system from NG to LP, follow these steps:

NOTE:

The primary regulator for the propane supply is NOT INCLUDED with the generator. A fuel pres- sure of 11 to 14 inches of water column (0.4 to 0.5 psi) to the fuel inlet of the generator MUST BE SUPPLIED.

1.Turn off the gas supply. (if connected)

2.Open the roof and remove the door.

1.Turn off the main gas supply (if connected).

2.Open the roof and remove the door.

3. Remove the battery. (if installed)

Generac® Power Systems, Inc. 7

Image 9
Contents Installation Authorized Dealer Location IntroductionMaintenance Post Installation Start-up AdjustmentsTroubleshooting Introduction Inside Front CoverGeneral Hazards ‹ Standards Index Electrical HazardsUNPACKING/INSPECTION Protection SystemsSystem SET LED Gfci GeneratorSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Fuel Requirements Recommendations Reconfiguring the Fuel SystemFuel Consumption 1 7 KW, 410CCLocation Transfer SwitchGenerator 2.1 7 kW, 12 kW and 15 kW UnitsBattery Battery InstallationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Checking Automatic Operation Generator Tests Under LoadAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units 2 12 KW and 15 KW Units Voltage Regulator AdjustmentAutomatic Transfer Operation BREAK-IN ProcedureSequence of Automatic Operation ‹ 3.2.1 Auto PositionManual Transfer Operation ‹ 3.5.2 Transfer Back to Utility Power Source‹ 3.7.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 3.7.2 High Temperature Switch ‹ 3.7.3 OvercrankChanging the Engine OIL Checking the Engine OIL LevelApproximate Crank Cycle Times ‹ 3.7.4 Overspeed‹ 4.3.2 OIL Change Procedure Changing the OIL Filter‹ 4.5.1 7 KW, 12 KW and 15 KW Generators Spark Plugs Battery MaintenanceCooling System Adjusting Valve Clearance‹ 4.12.2 Return to Service OUT of Service Procedure‹ 4.12.1 Removal from Service Corrosion ProtectionSYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR SW1 Exploded Views and Parts Lists Part NO. QTY. Description Exploded Views and Parts Lists Part NO. QTY Description 1310 Sleeve Exploded Views and Parts Lists Item Part NO. QTY. Description 14 20 QTY Description Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists PIN, Piston D20 Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome Exploded Views and Parts Lists CASTING, Twin Regulator Housing Dimensions Generac Air-cooled 7 kW, 12 kW and 15 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule
Related manuals
Manual 59 pages 50.68 Kb

04674-2, 04675-3, 04673-2 specifications

Generac, a prominent name in the power equipment sector, offers a range of reliable and efficient energy solutions, including the models Generac 04673-2, 04675-3, and 04674-2. These models are designed to meet diverse consumer needs, from residential applications to larger commercial setups, providing dependable backup power during outages.

The Generac 04673-2 is a standout home standby generator specifically engineered for residential use. It boasts an automatic operation feature, ensuring that power is restored within seconds of an outage. This model operates on a robust Generac engine, delivering a reliable power output that can support essential household appliances and systems, including HVAC units, refrigerators, and sump pumps. One of the main characteristics of this generator is its Quiet Test mode, which runs at a lower RPM to minimize noise while conducting weekly self-tests, ensuring that the system is always ready when needed.

Moving on to the Generac 04675-3, this model offers enhanced features tailored for users needing higher power output. With a larger capacity, it can handle more demanding power needs, making it suitable for larger homes or small businesses. The 04675-3 is equipped with advanced technologies, including the Mobile Linkā„¢ remote monitoring system, which enables users to check the status and performance of their generator from anywhere using a smartphone or computer. This connectivity empowers users with real-time information and alerts regarding their generator's operational performance.

The Generac 04674-2 model rounds out the trio, engineered for those who need a powerful standby generator with a slightly different configuration. It features the same robust engine as the other models, ensuring reliability and user-friendly operation. Its standout feature is the integrated transfer switch capability, which allows for seamless transfer of power from the grid to the generator without manual intervention. This model also supports various fuel types, providing flexibility depending on user preference and availability.

All three Generac models focus on safety and efficiency, incorporating features such as excellent ventilation systems, all-weather enclosures, and user-friendly control panels. They are designed for low maintenance, ensuring long-lasting performance without extensive upkeep. With Generac's commitment to innovation and quality, these generators offer peace of mind, enabling users to maintain their lifestyles and operations without interruption during power outages. Whether for home or business use, the Generac 04673-2, 04675-3, and 04674-2 models represent a reliable choice in emergency power solutions.