6. PRE-OPERATION CHECK

Before starting, complete the following:

1.Set the generator's Start/stop switch to the Stop position.

2.Turn OFF the utility power supply to the transfer switch using the means provided (such as the utility main line circuit breaker).

3.Check the engine crankcase oil level and, if necessary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.

4.Check the fuel supply. All fuel shutoff valves in the fuel supply lines must be open.

Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.

6.1. Electrical Checks.

Complete electrical checks as follows:

1.Turn on the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).

The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extremely hazardous and possibly fatal electrical shock. Proceed with caution.

2.Use an accurate AC voltmeter to check utility power source voltage across terminals.

the generator’s main circuit breaker to its ON (or closed) position.

Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dangerous and possibly fatal electrical shock.

8.Connect an accurate AC voltmeter and an AC frequency meter across transfer switch terminal lugs and voltage and frequency of the unit must be accord to the specifications of the generator.

9.Connect the AC voltmeter test leads across terminal Lugs and neutral, one by one.

10.Set the generator’s main circuit breaker to its OFF (or open) position. Let the engine run at no load for a few min- utes to stabilize internal engine generator temperatures.

11.Set the generator's Start/stop switch to stop position. The engine should shut down.

NOTE:

It is important that you DO NOT proceed until you are cer- tain that generator AC voltage and frequency are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjustment. If frequency is correct, but voltage is high or low, the generator’s voltage regulator requires adjustment.

6.2. GENERATOR TESTS UNDER LOAD

To test the generator set with electrical loads applied, pro- ceed as follows:

1.Set generator’s main circuit breaker to its OFF (or open) position.

2.Set the generator's Start/stop switch to OFF.

3. Check utility power source voltage across terminals and

3.

Turn OFF the utility power supply to the transfer switch,

the transfer switch neutral lug; then across second terminal

using the means provided (such as a utility main line circuit

and neutral. Nominal line-to neutral voltage should be 120

breaker).

volts AC.

 

Do not attempt manual transfer switch operation

 

 

4. When certain that utility supply voltage is compatible with

 

until all power voltage supplies to the transfer

transfer switch and load circuit ratings, turn OFF the utility

 

switch have been positively turned off. Failure to

power supply to the transfer switch.

 

turn off all power voltage supplies will result in

 

 

extremely hazardous and possibly fatal electrical

5. Set the generator's main circuit breaker to its OFF (or

 

shock.

open) position. Initial tests will be conducted at no-load

4.

Manually set the transfer switch to the STANDBY posi-

condition.

 

tion, i.e., load terminals connected to the generator's termi-

6. On the generator panel Start/stop switch to the to start

nals. The transfer switch operating lever should be down.

position The engine should crank and start when the re-

5.

Set the generator's Start/stop switch to MANUAL. The

mote start input is activated.

 

engine should crank and start immediately.

 

6.

Let the engine stabilize and warm up for a few minutes.

7. Let the engine warm up for about five minutes to

7.

Set the generator’s main circuit breaker to its ON (or

allow internal temperatures to stabilize. Then, set

closed) position. Loads are now powered by the standby

 

 

 

 

 

 

AR-EXP-CUMMINS-07-00

 

OWNERS MANUAL

Image 18
Contents Cummins Series AR-EXP-CUMMINS-07-00 Warranty Certificate AR-EXP-CUMMINS-07-00 Introduction GeneralINSTALLATION, Handling and Towing Fire and ExplosionMechanical ChemicalNoise ElectricalCall First AID for Electric ShockWhat to do BlowSpecial Considerations for Battery Generating SET Installation Location GROUND/FLOOR LoadingMounting Ventilation Outdoor Installations AIR Cooled Units General Electrical System Connecting the GeneratorElectrical System General Rules for Exhaust SystemLocation Installation Checklist Battery InstallationFuel System Electrical ConnectionsAR-EXP-CUMMINS-07-00 Generating SET Operation Maintenance Generator Tests Under Load PRE-OPERATION CheckElectrical Checks ShockGenerator Checking Automatic OperationInstallation and Application ACUM84 ACUM110 ACUM140 ACUM185 ACUM210 Automatic Mode of Operation ShutdownsSettings Fixed Settings Terminal DescriptionEngine Checks During Operation Maintenance ScheduleInstruments Reading Radiator Cooling water CoolantEvery 500 Hours or 6 Months Maintenance Daily or Refueling Maintenance Check4Every 250 Hours or 3 Months Maintenance Check 1 Every 2000 Hours or 2 Years Maintenance CheckCUMMINS/FLEETGUARD Filter Specifications API CG-4/SH, API CD, API Acea E-1Not OK OBSOLETE. do not Alternator Inspection and Maintenace IntervalsMaintennce of Bearings Voltag Regulator USE of Potentiometers

ACUM210, ACUM110, ACUM65, ACUM185, ACUM140 specifications

Armstrong World Industries has established itself as a leader in the design and manufacture of innovative ceiling and wall solutions. Among their notable acoustic ceiling offerings are the ACUM84, ACUM210, ACUM65, ACUM140, and ACUM185 tiles. Each of these products is engineered with distinct features and technologies aimed at enhancing acoustic performance, durability, and aesthetics in various commercial spaces.

The ACUM84 is designed for spaces that prioritize sound absorption and overall acoustic quality. It utilizes advanced sound-dampening technology, making it suitable for environments such as offices, schools, and healthcare facilities. This tile achieves a high Noise Reduction Coefficient (NRC), effectively minimizing sound reverberation, which is essential for maintaining concentration in busy settings.

Similarly, the ACUM210 offers enhanced acoustic properties but with a focus on durability. This tile is constructed with a robust material that is resistant to impact and moisture, making it an excellent choice for high-traffic areas. The fabric-like texture not only adds aesthetic value but also improves its sound-absorbing capabilities, contributing to a quieter environment.

For those seeking a versatile solution, the ACUM65 is an ideal option. This tile is lightweight yet durable, making installation straightforward. Its ecological design ensures minimal environmental impact while providing superior acoustic performance. The ACUM65 is particularly well-suited for retail spaces, where customer experience can be significantly enhanced by better sound control.

ACUM140 is engineered for flexibility and design versatility. With a range of finishes and colors, it allows architects and designers to incorporate acoustic solutions that harmonize with the overall aesthetic of the space. Its high NRC rating ensures a calm auditory environment, making it an excellent fit for restaurants and auditoriums.

Lastly, the ACUM185 combines aesthetics with functionality, offering a sleek design while maintaining outstanding sound absorption capabilities. It meets the demands of contemporary styling without compromising performance. This tile is particularly favored in corporate environments where aesthetics play a crucial role in branding and employee satisfaction.

In conclusion, Armstrong's ACUM product line, including ACUM84, ACUM210, ACUM65, ACUM140, and ACUM185, showcases technologies and characteristics that cater to a variety of applications. With a strong focus on acoustic management, durability, and design versatility, Armstrong continues to provide innovative solutions tailored to the needs of modern commercial spaces.