Electrical Connections Continued
Table
Model | Electrical Connection Information (Receptacle Provided at Panel) | |||
|
|
|
|
|
| Straight 120VAC | Twist Lock 120VAC | Twist Lock 120/240VAC | Rated Watts/ |
| (20Amp) | (30Amp) | (30Amp) | (Full load Amps |
|
|
|
| 120/240) |
|
|
|
|
|
PC30H | 3- 15AMP 120VAC |
|
| 3000 / |
PC40H | 2- | 1- | 1- | 4000 / (33.3/16.7) |
PC50H | 2- | 1- | 1- | 5000 / (33.3/16.7) |
PC60H | 2- | 1- | 1- | 6000 / (45.8/22.9) |
PC90VE | 2- | 1- | 1- | 9000 / (66.7/33.4) |
Note: GFCI is Ground Fault Protected power.
Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.
Figure 3-2 Receptacle Connections
| W |
| (GOLD) |
| (SILVER) |
| |
| G | X | |
|
| ||
| NEMA |
| NEMA |
|
| ||
| 125V | 125/250V | |
| 30A |
| 30A |
G | X | Y | W |
NEMA | (GOLD) | (GOLD) | (SILVER) |
125V 20A |
|
|
|
Frame Ground Connection
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power before you ensure that grounds are connected. Electrical shock can cause serious or fatal injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be connected to an approved earth ground. Local codes may also require proper grounding of generator systems.
The NEC requires that the frame and exposed metal surfaces be at local ground reference potential to avoid electrical shock hazard. A local ground reference may require a driven earth ground conductor at the generator installation site. Make the ground connection as shown in Figure
WARNING: Do not connect the generator output neutral to the frame or local ground. The generator output is isolated from ground. NEC and local codes require that the generator output remain isolated from local ground reference.
Figure 3-3 Frame Ground Connection
Nut
Washer
Ground Wire Lug
Washer
Stud
Frame
Earth Ground
MN2413 | Receiving & Installation |