Emerson dimensions Specification for SiteLink-12

Page 1

Specification for SiteLink-12

DESCRIPTION: The SiteLink-12 is a 32-bit microprocessor-based communications device that provides an interface for up to twelve Liebert Unit Controllers (IGM’s). The SiteLink-12 communicates to either the SiteScan Monitoring System, or a third party software program utilizing a designated open standard protocol (i.e. Modbus or BACnet). This device communicates to the SiteScan Monitoring System via a twisted pair called the ARC156 network through an EIA-485 port at either 156K / 9600 or 38.4kbps baud. It communicates to the third party software monitoring system via a 9-pin DTE male EIA-232 connector (Portal Interface) or at the 5 pin EIA485 port communicating at either 9600bps or 38.4kbps baud. Twelve EIA-422 ports are provided to connect Liebert Information Gathering Modules.

DIMENSIONS:

Module:

7 1/2" H x 11 1/4" W

 

 

19.05cm H x 28.58cm W

 

Enclosure:

12”H x 14.25" W x 2.85" D

 

(Painted steel)

419.1mm x 301.3mm x 78.6mm

 

See Enclosure Diagrams for mounting options.

POWER:

24VAC ± 10%, 50-60 Hz, 7.2VA power consumption.

 

(120/24VAC 40VA Transformer available)

ENVIRONMENTAL

OPERATING RANGE: 0° to 130° F (-17.8°to 54.4° C), 10 to 90% relative humidity, non-condensing

COMMUNICATION: CMnet EIA-485 Port - Control Module network screw terminals Switch selectable baud rates ARC156 / 9600 or 38.4bps Recommended wire is: MAGNUM Cable pn A3-ARC-156-2

Two (2) Portal Interface – One EIA-232, One EIA-485 2 / 4 wire (for Third Party software selectable baud rate, 9600bps or 38.4kbps

One (1) Access port (for diagnostics)

Twelve (12) EIA-422 Ports (for Liebert unit connection) - screw terminal

MEMORY:1024 kB Flash memory and 1024 kB non-volatile battery-backed RAM.

PROTECTION: Voltage, current, and ESD protection on incoming power and ARC156 network

BATTERY: Seven-year lithium battery provides a minimum or 10,000 hours or data retention during power outages.

Liebert Corporation

Page 1 of 5

SL-27216 Rev. 4; 7/03

Image 1
Contents Specification for SiteLink-12 Module Dimensions and Layout Communications Wiring Diagram Specification for SiteLink-12 Enclosure Wall Mounting Specification for SiteLink-12 Enclosure Floor Mounting