Specifications

Table 38 Liebert XDV8 dimensions—domestic and export

 

Shipping Dimensions

Unit Dimensions Unpacked

 

Length x Width x Height

Length x Width x Height

 

inches (mm)

inches (mm)

Model

 

 

 

Domestic

Export

Unit Only

 

 

 

 

All Models

48 x 40 x 24-1/4

45-4/5 x 30-3/4 x 33

39-1/2 x 22-7/8 x 14

(1219 x 1016 x 616)

(1163 x 781 x 839mm)

(1003 x 581 x 356)

 

Table 39 Liebert XDV10 dimensions—domestic and export

 

Shipping Dimensions

Unit Dimensions Unpacked

 

Length x Width x Height

Length x Width x Height

 

inches (mm)

inches (mm)

Model

Domestic

Export

Unit Only

All Models

48 x 40 x 24-1/4

45-4/5 x 30-3/4 x 33

39-1/2 x 22-7/8 x 14

(1219 x 1016 x 616)

(1163 x 781 x 839mm)

(1003 x 581 x 356)

 

Table 40 Liebert XDCF specifications

 

XD-CF-10-TP-0, XD-CF-10-TPE-0

Models

XD-CF Top EXP, XD-CF-10-BPE-0

 

XD-CF BTM EXP, XD-CF-10-BP-0

Cooling capacity, maximum

10kWH / 2.8 Tons / 34,000 BTUh

 

 

Conditions

55°F (13°C) entering fluid temperature,

50°F (10°C) or lower dew point

 

Dimensions, inches (mm)

 

 

 

Height – including pipe connections

31-3/8" (797mm)

 

 

Width

13-7/16" (341mm)

 

 

Depth

7-5/16" (186mm)

 

 

Weight, lb (kg)

 

 

 

Unit only

18 (8.2)

 

 

Shipping weight

30 lb. (13.06 kg)

 

 

Pipe connections

 

 

 

Refrigerant Supply

1/2" threaded one-shot coupling on the unit

from Liebert XDP/Liebert XDC

 

Refrigerant Return

5/8" threaded one-shot coupling on the unit

to Liebert XDP/Liebert XDC

 

Cabinet exterior finish

Gray

 

 

Agency

 

 

 

Safety

CSA — CE

 

 

73

Page 79
Image 79
Emerson Xtreme Density manual Liebert XDV8 dimensions-domestic and export, Liebert XDV10 dimensions-domestic and export