Designing a Liebert XD Solution

3.3Selecting Liebert XD Cooling Modules

The next step is to select the Liebert XD cooling modules to be configured into the solution. Liebert XD modules that use pumped refrigerant can be connected to the same Liebert XDP/Liebert XDC pip- ing circuit. This includes the Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV.

Generally, the Liebert XDO is selected for use in new installations or renovations where the unit can be installed on the ceiling or in the overhead space.

The Liebert XDV is designed to permit mounting directly on top of an equipment cabinet, for ease of installation in existing facilities. The Liebert XDV may also be suspended from overhead, using suit- able mounting methods.

The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room. Two modules may be mounted on the rear of a BladeFrame cabinet.

The Liebert XDH is installed among equipment cabinets and is particularly suited to new installa- tions.

3.4Airflow Requirements for Liebert XD Solutions

Computer manufacturers typically specify a temperature change from intake to exhaust (delta T) of 18-27°F (10-15°C) for the air passing through a rack enclosure. The heat generated by electronic equipment combined with the tight quarters of equipment cabinets mean that high volumes of air must move through an enclosure to meet this cooling specification.

A Liebert XD system can supply the cooled air to satisfy this cooling demand, but airflow through the enclosure must be adequate to extract the heat from the cabinet. Liebert’s XDA units can boost the airflow to levels necessary to protect critical equipment. The Liebert XDA is particularly suited to the hot aisle/cold aisle arrangement.

3.5Configuring a Liebert XD System

3.5.1Number of Modules Supported by a Liebert XDP or Liebert XDC

The numerals designating the model size of a Liebert XD unit may be used to configure a cooling sys- tem. For example, a Liebert XDO20 has a model size of 20 and a Liebert XDP160 will accommodate cooling modules with a cumulative model size of 160.

Similarly, the minimum number of modules connected to a Liebert XDP or Liebert XDC may be calcu- lated using the model size number for the Liebert XDP or Liebert XDC and the modules. See Table 2.

Table 2 Maximum and minimum modules supported by a Liebert XDP or Liebert XDC

Cooling

Liebert XDC

Liebert XDP

 

 

 

 

Module Type

Max

Min

Max

Min

 

 

 

 

 

Liebert XDCF

16

6

16

4

 

 

 

 

 

Liebert XDH20

8

4

8

2

 

 

 

 

 

Liebert XDH32

5

2

5

1

Liebert XDO16

10

4

10

2

 

 

 

 

 

Liebert XDO20

8

4

8

2

 

 

 

 

 

Liebert XDV8

20

8

20

4

Liebert XDV10

16

7

16

4

 

 

 

 

 

Different types of Liebert XD cooling modules may be connected to the same Liebert XDP or Liebert XDC as long as the sum of their cooling capacity does not exceed the supporting Liebert XDP’s or Lie- bert XDC’s model size number.

NOTE

Connecting only Liebert XDCF modules to a Liebert XD unit is not recommended because the Liebert XDCF heat loading is dependent on server airflow and server load. Consult factory to determine if sufficient heat load is available from the server for the Liebert XD system to operate effectively.

14

Page 20
Image 20
Emerson Xtreme Density manual Selecting Liebert XD Cooling Modules, Airflow Requirements for Liebert XD Solutions