Emerson Xtreme Density Supply, return pipe sizes for refrigerant loop, 20ft 6.7m max, in Figure

Models: Xtreme Density

1 84
Download 84 pages 62.71 Kb
Page 29
Image 29
20ft.

Designing a Liebert XD Solution

Figure 23 Piping for Liebert XDP/Liebert XDC used with Liebert XD cooling units

20ft.

(6.7m)

max.

9ft.

(2.7m)

max. 9ft.

Liebert XDP/ Liebert XDC

All supply and return mains must be level with or above the top of all Liebert XDP or Liebert XDC units

Liebert XD

Cooling

Modules

SLOPE—The main supply and return lines to and from the Liebert XDP/Liebert XDC must be sloped downward toward the Liebert XDP/Liebert XDC at a rate of 1-2" per 20 feet (25.4-51mm per 6m) of pipe run. Horizontal connector lines should also be sloped downward from the cooling modules toward the main supply and return lines.

The assembly and connection means used for piping in the Liebert XD system are similar to that of conventional refrigeration systems. All piping should be installed with high temperature brazed joints. Soft solder is not recommended. The lines being brazed MUST be filled with flowing dry nitro- gen during brazing to prevent excessive oxidation and scale formation inside the piping.

Insulate all piping lines to prevent condensation in applications where the dew point approaches the R-134a refrigerant temperature.

Please see Table 5 below for recommended pipe sizes and Figure 24 for piping segment locations.

Table 5

Supply, return pipe sizes for refrigerant loop

 

 

 

 

 

 

 

Key to Piping

 

 

Pipe Function

in Figure 24

Size / Equivalent Pipe Length

Liebert XDP supply line, from Liebert XDP supply

A

1-1/8" OD for lengths up to 60 feet

to farthest Liebert XD cooling module

1-3/8" OD for lengths over 60 but less than 175 feet

 

Liebert XDP return line, from farthest Liebert XD

B

2-1/8" OD for lengths up to 60 feet

cooling module to Liebert XDP return

2-5/8" OD for lengths over 60 but less than 175 feet

 

From any model Liebert XDO/Liebert XDH supply

C

1/2" OD for lengths up to 10 feet

to supply line of Liebert XDP

7/8" OD for lengths over 10 but less than 25 feet

 

From any model Liebert XDO/Liebert XDH return

D

7/8" OD for lengths up to 10 feet

to return line of Liebert XDP

1-1/8" OD for lengths over 10 but less than 25 feet

 

From any model Liebert XDV/Liebert XDCF supply

C

1/2" OD for lengths up to 10 feet

to supply line of Liebert XDP

5/8" OD for lengths over 10 but less than 35 feet

 

From any model Liebert XDV/Liebert XDCF return

D

5/8" OD for lengths up to 10 feet

to return line of Liebert XDP

7/8" OD for lengths over 10 but less than 35 feet

 

For additional information about piping connections, see the unit’s user manual: Liebert XDP, 16641; Liebert XDC, SL-16671; Liebert XDO, SL-16666; Liebert XDV, SL-16626; Liebert XDCF, SL-16678; and Liebert XDH20 and Liebert XDH32, SL-17210.

NOTE

To minimize the amount of refrigerant required, do NOT oversize the piping.

23

Page 29
Image 29
Emerson Xtreme Density manual Supply, return pipe sizes for refrigerant loop, 20ft 6.7m max, Liebert XD Cooling Modules