Emerson Xtreme Density manual Liebert XDP piping access points and external features

Models: Xtreme Density

1 84
Download 84 pages 62.71 Kb
Page 58
Image 58
Figure 51 Liebert XDP piping access points and external features

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

Figure 51 Liebert XDP piping access points and external features

To first cooling module

or bypass flow controller **

A - Return From Cooling Modules

17-1/4" Table 23 Unit piping outlet connection sizes, inches, OD Cu (438mm) 16-1/8"

(410mm)

Install replaceable filter dryer assembly in liquid supply line B.

Manual backgroundManual backgroundManual backgroundManual backgroundManual background * Orientation

determined

by installer.

B - Supply to Cooling Modules

10" (254mm) Manual backgroundManual backgroundManual backgroundManual backgroundManual background

Manual background 19" (483mm) Manual background

Dimensions are approximate

and subject to change without notice.

D - Chilled Water Return

To Chilled Water Source

Manual backgroundManual backgroundManual background C - Chilled Water Supply From Chilled Water Source

*Allow 8" (204mm) clearance for filter replacement.

**To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly between the discharge line of the XDP and the first bypass flow controller or the first cooling module.

Table 23 Unit piping outlet connection sizes, inches, OD Cu

Model

 

Pipe Connection Point

 

 

 

 

 

 

50/60 HZ

A

B

C

D

 

 

 

 

 

Liebert

2-1/8

1-1/8

2-5/8

2-5/8

XDP160

 

 

 

 

DPN000767 Pg. 3, Rev. 6

52

Page 58
Image 58
Emerson Xtreme Density manual Liebert XDP piping access points and external features