Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

Figure 51 Liebert XDP piping access points and external features

To first cooling module

or bypass flow controller **

A - Return From Cooling Modules

17-1/4" (438mm) 16-1/8"

(410mm)

Install replaceable filter dryer assembly in liquid supply line B.

* Orientation

determined

by installer.

B - Supply to Cooling Modules

10" (254mm)

19" (483mm)

Dimensions are approximate

and subject to change without notice.

D - Chilled Water Return

To Chilled Water Source

C - Chilled Water Supply From Chilled Water Source

*Allow 8" (204mm) clearance for filter replacement.

**To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly between the discharge line of the XDP and the first bypass flow controller or the first cooling module.

Table 23 Unit piping outlet connection sizes, inches, OD Cu

Model

 

Pipe Connection Point

 

 

 

 

 

 

50/60 HZ

A

B

C

D

 

 

 

 

 

Liebert

2-1/8

1-1/8

2-5/8

2-5/8

XDP160

 

 

 

 

DPN000767 Pg. 3, Rev. 6

52

Page 58
Image 58
Emerson Xtreme Density manual Unit piping outlet connection sizes, inches, OD Cu, Model Pipe Connection Point 50/60 HZ