Emerson Xtreme Density manual Liebert XDC Water/Glycol Piping Connection Sizes

Models: Xtreme Density

1 84
Download 84 pages 62.71 Kb
Page 63
Image 63
Table 26 Liebert XDC Water/Glycol Piping Connection Sizes

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

Figure 58 Positioning a water/glycol Liebert XDC for placement on a floor stand

 

44"

47"

(1118mm)

(1194mm)

6"

(153mm)

Manual background 23" (584mm)

C - Hot Gas

Refrigerant Lines

D - Liquid

Refrigerant Lines

E - ThreadedManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Female

Connections

Customer Manual background

Water

Return

A - Return from

Cooling Units

B - Supply to

Cooling Units

Customer

Water

Manual backgroundManual background Supply

Manual background F - Cup Fitting

Capillary Lines are 48" (1220mm) Limit Valve Distance from Condensers

Customer Provided Piping

DPN001419

 

Pg. 01, Rev. 01

Table 26 Liebert XDC Water/Glycol Piping Connection Sizes

Model

Piping Outlet Connection Sizes, OD Cu, inches

 

 

 

 

 

 

 

50/60Hz

A

B

C

D

E*

F**

 

 

 

 

 

 

 

XDC160

2-1/8

1-1/8

1-3/8

7/8

2-1/2

2-1/8 or 2-5/8

 

 

 

 

 

 

 

*Threaded Female Conection

**2-1/8" for 1" WRV, 2-5/8" for 1-1/4" WRV

57

Page 63
Image 63
Emerson Xtreme Density manual Liebert XDC Water/Glycol Piping Connection Sizes