Emerson Xtreme Density manual Liebert XDO20 specifications, Specifications

Models: Xtreme Density

1 84
Download 84 pages 62.71 Kb
Page 75
Image 75
Table 33 Liebert XDO20 specifications

Specifications

Table 33 Liebert XDO20 specifications

 

XDO20DK--*; XDO20BKP-*

 

XDO20BS--*; XDO20DS--*

 

XDO20DKP-*; XDO20BK-E*

 

XDO20BSP-*; XDO20DSP-v

Models

XDO20DK-E*; XDO20BKPE*

 

XDO20BS-E*; XDO20DS-E*

 

XDO20DKPE*

 

XDO20BSPE*; XDO20DSPE*

 

60Hz

 

60Hz

 

50Hz

 

 

 

 

 

Nominal (92°F [33°C] EAT):

Cooling Capacity

Nominal (92°F [33°C] EAT): 20kW / 5.7 Tons

 

17.7kW / 5 Tons

Maximum (100°F [38°C] EAT): 23kW / 6.5 Tons

 

Maximum (103°F [39°C]

 

 

 

 

 

 

 

EAT): 23kW / 6.5 Tons

 

 

 

Conditions

Capacity rating is @ 55ºF (13°C) Entering Fluid Temperature and

 

 

50ºF (10°C) or lower dew point

 

 

 

Electrical Requirements

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

1ph-60Hz-120V

 

1ph-60Hz-220-240V

 

1ph-50 Hz-220-240V

 

 

 

 

Input Power Connections

Terminal blocks provided internal to unit

 

 

 

 

 

 

Full Load Amps

2.7A @ 120V

 

1.64A @ 230V

 

1.47 @ 230V

 

 

 

 

 

 

Wire Size Amps

3.4

 

2.0

 

1.84

 

 

 

 

 

 

Overcurrent Protection Device

15

 

15

 

15

 

 

 

 

 

 

Power consumption,

335

 

350

 

250

nominal, watts

 

 

 

 

 

 

 

Dimensions, inches (mm)

 

 

 

 

 

 

 

 

 

 

 

Length

 

72-1/4 (1835)

 

 

 

 

 

 

 

Width

 

24-1/8 (613)

 

 

 

 

Height

22-1/2 (572) not including electrical and piping access

 

 

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

 

 

 

 

 

Unit only

 

150 (68)

 

 

 

 

 

 

 

 

Shipping weight

238 (108)

 

 

296 (134)

 

 

 

 

 

 

Installed, with refrigerant,

 

155 (70)

 

 

without options

 

 

 

 

 

 

 

 

Number of Fans

 

1

 

1

 

 

 

 

 

 

Airflow, Nominal, ft3/ min

2700 (4587)

 

2250 (3822)

(m3/ hr)

 

 

 

 

 

 

Audible Noise

85 dBa sound power

 

83 dBa sound power

Pipe Connections (without flex pipe)

 

 

 

 

 

 

 

 

 

 

Refrigerant Supply

 

 

1/2" OD, Copper

 

 

from Liebert XDP/Liebert XDC

 

 

 

 

 

 

 

 

 

Refrigerant Return

 

 

7/8" OD, Copper

 

 

to Liebert XDP/Liebert XDC

 

 

 

 

 

 

 

 

 

Serviceable Parts

 

 

Fan and electrical components

 

 

 

 

 

 

Exterior Finish – Bottom,

Black matte finish, heat-fused powder coat

Sides, Front and Rear

 

 

 

 

 

Exterior Finish - Top

 

 

Hot-dipped galvanized steel

 

 

 

 

 

 

Agency

 

 

 

 

 

 

 

 

 

 

Approvals

CSA 60 Hz

 

CE 50Hz

 

 

 

 

 

 

Options

 

 

 

 

 

Lighting Fixtures (ship loose)

2 Liebert XDOs per lighting unit; 120V or 277V; 4’ standard fluorescent tubes (not included)

 

 

 

 

Power, optional lighting fixture

0.9A per 120V light fixture;

 

None

0.4A per 277V light fixture

 

 

 

 

Condensate sensing

Dry contact 24VAC - 1A maximum

(factory-installed)

 

 

 

 

 

Pre-Charged Refrigerant

R-134a Refrigerant, one-shot connections

 

 

 

 

 

 

* = Revision level

 

 

 

 

 

69

Page 75
Image 75
Emerson Xtreme Density manual Liebert XDO20 specifications, Specifications