Designing a Liebert XD Solution
3.12Liebert XD Refrigerant
The refrigerant used in the Liebert XD system is
! CAUTION
Risk of improper oil use. Can cause equipment damage.
The Liebert XD pumped
All the major components of a Liebert XD system must be installed in a space with a volume of at least 1,000 ft3 (28.3m3) for each 13 pounds of refrigerant in that system from Table 1, ASHRAE Stan- dard
Example
A space is 5,000 square feet, with an 18" raised floor and an 8' 6" suspended ceiling. Liebert XDOs and a Liebert XDP are to be placed in this
The volume of the space is (1.5 + 8.5) x 5,000 or 50,000 cubic feet.
The maximum amount of
Multiple Liebert XD systems can be installed in this space, as long as the amount of
NOTE
Local codes might permit exceeding the maximum refrigerant limit stated above if refrigerant detector and an exhaust system are installed. As an alternative, oxygen sensors may be installed to meet some local codes.
3.13Liebert XD Piping System Design
All piping must be ASTM (American Society for Testing and Materials) Type “L” copper pipe. The typ- ical maximum operating pressure in the system is 90 psi (620kPa).
Piping for the Liebert XD system is arranged in a manner similar to piping for a chilled water system. Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO or Liebert XDV) are connected in parallel between the main return and supply pipes going to and from the Liebert XDP/Liebert XDC. Figure 23 represents a typical configuration. The guidelines provided for pipe size must be strictly followed. Failure to size the main lines and connection lines adequately may result in reduced cooling capacity. The critical aspects of pipe sizing are related to refrigerant volume and pressure drop. Each must be minimized.
22