3.8Liebert XDCF Placement

Designing a Liebert XD Solution

3.8Liebert XDCF Placement

The Liebert XDCF is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment. Liebert XDCF modules attach to the rear of the Egenera BladeFrame EX cabinet, beside the power modules (see Figure 17). No cutting or drilling is required to attach the modules; all mounting holes, slots and pins required are fabricated at the factory. The Liebert XDCF does not require electrical connections.

The number of Liebert XDCF modules required is determined by the heat load of the cabinet—cabi- nets cannot share cooling from a Liebert XDCF module.

The Egenera BladeFrame EX cabinet has provisions for mounting two Liebert XDCF modules, should the heat load require two modules. If only one Liebert XDCF will be needed, Liebert recommends using the lower Liebert XDCF module.

The complete system consists of Liebert XDCF modules, piping, Liebert XDP or Liebert XDC refriger- ant distribution units and those units’ chillers or drycoolers.

Figure 17 Liebert XDCF unit mounting locations

Liebert XDCF Modules

attached to

Egenera BladeFrame EX Cabinet

Upper Module

Lower Module

18