System Description

1.4Liebert XDV—Vertical, Above-Cabinet Cooling Module

The Liebert XDV is installed on top of or above a rack enclosure. It is available with optional flexible metal pipes with automatic shutoff with quick-connect couplings at the ends for easy connection to the refrigerant distribution pipes. The Liebert XDV may be set up in either of two ways:

The Liebert XDV can take hot air directly from an equipment enclosure, cool the air and dis- charge it downward into the cold aisle.

OR

The Liebert XDV can draw hot air from the room, cool the air and discharge the cool air down- ward into the cold aisle.

Figure 5 Top-mounted Liebert XDV modules with fixed piping in hot aisle-cold aisle arrangement

Hot aisles and cold aisles

Cold Aisle

alternate, taking advantage

of airflow properties to

Hot Aisle

increase cooling efficiency

 

Cold Aisle

Hot Aisle

Cold Aisle

Figure 6 Top-mounted Liebert XDV modules with flexible piping in hot aisle-cold aisle arrangement

Cold Aisle

Hot Aisle

 

Hot aisles and cold aisles alternate,

Cold Aisle

taking advantage of airflow propertiesHot Aisle to increase cooling efficiency

4