Emerson 60HZ, 480V user manual Operator Control and Display Panel

Page 78
Manual background

 

 

Operator Control and Display Panel

Table 19 Descriptions of UPS menus and data window items

 

 

 

Menu Type

Item Type

Explanation

 

 

 

 

L-N current (A)

Phase current

Mains

Frequency (Hz)

Input frequency

(input)

L-L voltage (v

Line-line voltage

 

 

 

 

Power factor

Power factor

TX Input

L-L voltage (V)

Line-line voltage

Bypass

Frequency (Hz)

Bypass frequency

 

 

L-L voltage (A)

Line-line voltage

 

 

L-N current (A)

Phase current

Output

Frequency (Hz)

Output frequency

 

 

L-L voltage (V)

Line-line voltage

 

 

Power factor

Power factor

TX Output

L-L voltage (V)

Line-line voltage

 

Sout (kVA)

Sout: Apparent power

 

Pout (kW)

Pout: Active power

Load

 

 

Qout (kVAR)

Qout: Reactive power

 

Loadlevel %

The percent of the UPS rating load

 

Crest factor

Output current Crest Factor

 

Sout (kVA)

Sout: Apparent power

 

 

 

System

Pout (kW)

Pout: Active power

Qout (kVAR)

Qout: Reactive power

 

 

 

 

 

Single unit, no parallel data

When configured as a single unit, UPS has only native load, no system load.

 

Battery voltage (V)

Battery bus voltage

 

Battery current (A)

Battery bus current

 

 

 

 

Battery temperature (°C)

Internal battery temperature °C

Battery

 

 

Remain Time Min.

Battery run time remaining

 

Battery boost charging

Battery is boost charging

 

 

 

 

Battery float charging

Battery is float charging

 

 

 

 

Battery disconnected

Battery is not connected

Records

(History Log)

Displays all records in the history log

Language

(choices for text displayed)

User may select any of 12 languages for LCD text.

 

Display contrast

Adjust the LCD contrast

 

Date format set

Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

 

 

 

 

Date & time

Set the date and time

 

 

 

 

Comm1 baud rate

Communication baud rate setting for Liebert IntelliSlot 1

 

Comm2 baud rate

Communication baud rate setting for Liebert IntelliSlot 2

 

 

 

 

Comm3 baud rate

Communication baud rate setting for Liebert IntelliSlot 3

 

 

 

 

Communication address

This setting is applicable to RS485 communication mode

 

 

 

Settings

Communication mode

Communication Mode Setting

 

 

Callback times

When Liebert IntelliSlot 1 Communication mode is Modem, this parameter

 

 

 

sets the number of times a number is redialed to send an alarm notification.

 

 

 

 

Phone No.1

When Liebert IntelliSlot 1 Communication mode is Modem, this is the first

 

 

phone number to be dialed (to send an alarm notification).

 

Phone No.2

When Liebert IntelliSlot 1 Communication mode is Modem, this is the second

 

 

phone number to be dialed (to send an alarm notification).

 

Phone No.3

When Liebert IntelliSlot 1 Communication mode is Modem, this is the third

 

 

phone number to be dialed (to send an alarm notification).

 

Command password

User can modify the command password.

 

 

 

70

Image 78
Contents User Manual–40-200kVA, 480V,60Hz Liebert NX UPSAC Power For Business-CriticalContinuityPage TABLE OF CONTENTS 4.0 OPTIONS 9.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FIGURES Figure 39 Main component location drawing Liebert NX 480V, CB2, CB3, CB4 configurations . . . . . . . . . TABLES SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONSBattery Cabinet Precautions • Remove watches, rings and other metal objects AC input AC output GLOSSARY OF SYMBOLSRisk of electrical shock Requests the user to consult the manual1.0INSTALLATION 1.1External Inspections1.3Preliminary Checks 1.2.1Storing for Delayed Installation1.2Internal Inspections 1.4UPS Location1.6Mechanical Considerations Battery Location1.5Considerations in Moving the Liebert NX 1.4.3Special Considerations for Parallel Systems1.6.3Cable Entry 1.6.2Floor Installation1.6.1Clearances System CompositionFront of Units Liebert NX Battery CabinetLiebert Bypass2.1.1Cable Rating 2.1Power Cabling2.0ELECTRICAL CONNECTIONS Lug Size and Torque Requirements2.1.2UPS Input Configuration 2.1.3Cabling Guidelines2.1.4Cable Connections Liebert NX 40-120kVAConnectionsLiebert NX 160-200kVAConnections Figure 4 Input and output busbars2.1.6Protective Devices 2.1.5Safety Ground2.1.7Cabling Procedure UPS Rectifier and Bypass Input SupplyCommon Input Connections Dual Input ConnectionsFrequency Converter Mode 2.2.1Monitor Board Features 2.2Control CablesFigure 5 Monitor board U2 2.3Dry Contacts 2.3.1Input Dry Contacts 2.3.2Maintenance Bypass Cabinet InterfaceTable 2 Maintenance bypass cabinet interface Figure 7 Input dry contactsTable 3 BCB control interface 2.3.3Battery Circuit Breaker Control Interface2.3.4Output Dry Contacts Output dry contact relaysEPO - NO Figure 9 EPO wiring2.3.5EPO Input—Optional EPO - NC3.2Safety 3.0BATTERY INSTALLATION3.1Introduction 3.3External Battery Cabinet Installation 3.3.1Battery CabinetsFigure 10 Battery cabinets for Liebert NX 3.3.2Connecting the Batteries 3.3.3Installation ConsiderationsFigure 11 Battery cabinet—details 3.4Non-StandardBatteries 3.3.4Connecting the Battery Cabinet to the UPSFigure 12 Battery tray and supports 3.5BCB Shunt TripThis power must be UPS protected 3.6Alber Monitoring System—Optional4.0OPTIONS 4.1.2LBS Cable and Settings4.1Load Bus Synchronization 4.1.1Performance Requirements4.2Configuring Parallel System Operation 4.2.2Features of Parallel System4.2.1General Liebert NX UPS 40-200kVA 480V, 3W Input 480V DC Battery InputFigure 15 Parallel system block diagram 480V, 3W UOB Output4.2.3Operating Principles Redundancy Paralleling •Battery Mode Operation•Maintenance Bypass Mode Operation 4.2.4Operation Modes Summary4.3.4Power Cables 4.3Installing Parallel System4.3.2Cabinet Installation 4.3.1Conditions for Parallel SystemFor startup procedure, 9.2 - UPS Startup Auxiliary Dry Contact CablesX2:3 4.3.6Emergency Power Off EPOFigure 20 Connecting EPO push button X2:45.0UPS SPECIFICATIONS Environmental characteristicsUPS mechanical characteristics 5.4UPS Electrical Characteristics Table 8 UPS terminalUPS terminal continued Table 9 Rectifier input power5.4.1Input Rectifier Table 10 Input voltage window with derating5.4.3Inverter Output Table 11 Liebert approved replacement batteries5.4.2DC Intermediate Circuit Table 12 DC intermediate circuit5.4.4 Bypass Input Table 14 Bypass inputLeft Side FrontFront Detail AParallel Board 1239mm FRONT VIEWLEFT VIEW 2000mmTOP VIEW Front of UPS BOTTOM VIEW Front of UPSInstallation Drawings DETAIL A DETAIL A 224mm8.83 609.3 24 872.2 34.3 U3819205 SECTION A-A RIGHT SIDEFRONT TOP VIEWDetail B Detail ATop View without BCB Cover Plate49 Battery Cabinet Right-SideViews A D NX 160-200KVAUPS Module Front View A CBB D CDBattery Breaker Front Top Right Side845 33.2 965 38 2000 78.7 Right Side FrontSystem Input FrontRear UPS OutputWithout Covers System FRONTUPS Output Breakers Ground Busbar Kirk-KeyFRONT Door OpenREAR A B1-B4 FRONT Without Covers RIGHT SIDE Without Exterior Panels LEFT SIDE Without Exterior Panels 965 38 in 200078.7 in LEFT SIDE Isometric View7.1General Description 7.0OPERATION7.1.2Operating Modes Battery Mode7.1.1Bypass Supplies Normal ModeMaintenance Mode Parallel Redundancy Mode System ExpansionFigure 45 Overview of control panel 8.0OPERATOR CONTROL AND DISPLAY PANEL8.1.1Display Panel Layout Liquid Crystal Display LCD Mimic display LED2Load indicator Figure 47 Mimic display indicators locationBypass indicator Inverter indicatorButton cover EPO button Inverter Off button Fault Clear buttonFigure 48 Location of control buttons Silence On/Off button Inverter On buttonFigure 50 Sections of the LCD Data and settingsFigure 49 Buzzer location UPS systemTable 17 Icons for navigation keys 8.8LCD Menus and Data Items Figure 51 Menu treeOperator Control and Display Panel 8.9Language Selection Figure 52 Language selection8.10Current Date and Time Figure 53 Set date and timeMessages CurrentStatus History Log records menu8.12Types of LCD Screens 8.12.2Default ScreenFigure 56 Default screen 8.12.1Opening Display8.12.4Screen Saver Window Press any key back to main menu8.12.3UPS Help Screen Figure 57 Help screen8.13Pop-UpWindows 8.13.4 Battery Capacity Test Confirmation8.13.5Battery Self-TestAborted, Condition Not Met 8.13.3System Self-Test9.1Liebert NX Operating Modes 9.0OPERATING INSTRUCTIONSTable 20 UPS operating modes 9.1.1Circuit Breakers 9.2.1Startup Procedure9.2UPS Startup Figure 59 Circuit breakers•Close CB5 CB1, CB2, CB3 and CB5 are closed Switch from Normal Mode to Bypass Mode Switch from Bypass Mode to Normal Mode9.4Auto Restart 9.5Emergency Shutdown With EPO9.7.1Battery Undervoltage Pre-Warning 9.7Battery Protection9.8Multi-ModuleSystem Procedures 9.7.2Battery End-of-DischargeEOD Protection3.Close Input breaker CB1 9.9Commissioning a Parallel System 9.10Parallel System Startup10.0OPTIONS 10.1.2Power Output10.1Communication and Other User Terminals 10.1.1Analog Input Interface10.1.5Configuring Baud Rates 10.1.4Communication and MonitoringTable 21 Liebert NX communication options Figure 62 Liebert IntelliSlot Web card display Table 22 Relay Card pin configuration Table 23 Relay card jumper configurationRelay Card MultiPort 4 Card Figure 63 MultiPort 4 card pin assignment10.2LBS Mode—LoadBus Synchronization 10.2.1Remote Alarm MonitorFigure 64 Dust filter replacement 10.3Replacing Dust FiltersTable 25 Battery torque rating 11.0SPECIFICATIONS AND TECHNICAL DATATable 24 Torque specifications Specifications and Technical DataTable 27 Parallel system current table 11.3Cable size and tightening torques Specifications and Technical Data 11.4Battery Run Times Table 37 Enersys battery run times in minutesTable 38 C&D Dynasty battery run times in minutes Table 38 C&D Dynasty battery run times in minutes APPENDIX A - UPS STATUS MESSAGES Table 39 UPS status messagesUPS Status Messages Event Message Table 39 UPS status messagesUPS Status Messages Description / Suggested Action if anyTable 39 UPS status messages UPS Status MessagesTable 39 UPS status messages UPS Status MessagesTable 39 UPS status messages UPS Status MessagesUPS Status Messages Page Technical Support/ Service Ensuring The High AvailabilityOf Mission-CriticalData And Applications reducedcapitalequipment andoperatingcosts
Related manuals
Manual 2 pages 62.47 Kb Manual 108 pages 52.85 Kb

60HZ, 480V specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.