Emerson 60HZ, 480V 8.13Pop-UpWindows, 8.13.3System Self-Test, Battery Capacity Test Confirmation

Page 84
8.13Pop-Up Windows
This operation leads to output shutdown, Confirm or cancel
Transfer with Interrupt, please confirm or cancel

Operator Control and Display Panel

8.13Pop-Up Windows

Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This section describes the pop-up windows.

8.13.1 From Bypass to Inverter Mode With Power Interruption

If the bypass voltage or frequency exceeds the synchronized range and utility voltage or frequency is normal, the inverter cannot be in syn- chronization with the bypass, and the output can transfer to inverter only after an interruption of about 15ms when the user presses the INVERTER ON button. Before transferring, the system will let the

user confirm whether the interruption can be accepted, as shown at right. If the bypass voltage returns to normal before the user makes confirmation, the UPS will transfer to inverter mode auto- matically. At the same time, the prompt window will close.

8.13.2 From Inverter to Bypass Mode With Interruption

If the bypass voltage or frequency exceeds the synchronized range and the UPS is in inverter mode, the user must confirm and accept the power interruption danger before pressing the INVERTER OFF but- ton to shut down the output of the inverter. The user can also cancel the shutdown operation, as shown at right. If the bypass voltage returns to normal before the user makes the confirmation, the UPS

will transfer to bypass operation mode automatically, and at the same time the prompt window will close disappear soon.

8.13.3System Self-Test

When a system self-test is completed, a pop-up window reports the results of the test, as shown at right.

Press the F4 (Enter) key and the pop-up window closes.

System Self-Test finished,

Everything is OK

8.13.4 Battery Capacity Test Confirmation

When a battery capacity test is started from the Command menu, the battery will be discharged to low-battery warning level. The Liebert NX asks for confirmation before the test is started, as shown at right.

To confirm the choice and begin the battery capacity test, press the F4 (Enter) key and the pop-up window disappears.

To cancel the test, press the F1 (ESC) key. The pop-up window closes.

NOTE

Battery will be depleted,

Confirm or cancel

For a battery capacity test to function properly, the load must be between 20% and 100%.

8.13.5Battery Self-Test Aborted, Condition Not Met

When a battery capacity test is started from the Command menu and the battery self-test criteria are not met, the Liebert NX will not per- form a battery test. User should check whether the battery state is boost charging and whether the load level is greater than 20 percent.

Press the F4 (Enter) key and the pop-up window closes.

Battery Self-Test aborted, Conditions not met

8.13.6Battery Refresh Charge Aborted, Condition Not Met

When a battery refreshening charge is started from the Command menu and battery refreshening condition fails to meet requirements, the Liebert NX will not perform a battery refreshening charge. User should check if boost charging condition has not met the test criteria, such as (No battery, charger failed, etc.).

Press the F4 (Enter) key and the pop-up window closes.

Battery Refresh Charge aborted,

Conditions not met

76

Image 84
Contents Liebert NX UPS AC PowerUser Manual–40-200kVA, 480V,60Hz For Business-CriticalContinuityPage TABLE OF CONTENTS 4.0 OPTIONS 9.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FIGURES Figure 39 Main component location drawing Liebert NX 480V, CB2, CB3, CB4 configurations . . . . . . . . . TABLES SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONSBattery Cabinet Precautions • Remove watches, rings and other metal objects GLOSSARY OF SYMBOLS Risk of electrical shockAC input AC output Requests the user to consult the manual1.0INSTALLATION 1.1External Inspections1.2.1Storing for Delayed Installation 1.2Internal Inspections1.3Preliminary Checks 1.4UPS LocationBattery Location 1.5Considerations in Moving the Liebert NX1.6Mechanical Considerations 1.4.3Special Considerations for Parallel Systems1.6.2Floor Installation 1.6.1Clearances1.6.3Cable Entry System CompositionFront of Units Battery Cabinet LiebertLiebert NX Bypass2.1Power Cabling 2.0ELECTRICAL CONNECTIONS2.1.1Cable Rating Lug Size and Torque Requirements2.1.2UPS Input Configuration 2.1.3Cabling GuidelinesLiebert NX 40-120kVAConnections Liebert NX 160-200kVAConnections2.1.4Cable Connections Figure 4 Input and output busbars2.1.5Safety Ground 2.1.7Cabling Procedure2.1.6Protective Devices UPS Rectifier and Bypass Input SupplyCommon Input Connections Dual Input ConnectionsFrequency Converter Mode 2.2.1Monitor Board Features 2.2Control CablesFigure 5 Monitor board U2 2.3Dry Contacts 2.3.2Maintenance Bypass Cabinet Interface Table 2 Maintenance bypass cabinet interface2.3.1Input Dry Contacts Figure 7 Input dry contacts2.3.3Battery Circuit Breaker Control Interface 2.3.4Output Dry ContactsTable 3 BCB control interface Output dry contact relaysFigure 9 EPO wiring 2.3.5EPO Input—OptionalEPO - NO EPO - NC3.2Safety 3.0BATTERY INSTALLATION3.1Introduction 3.3External Battery Cabinet Installation 3.3.1Battery CabinetsFigure 10 Battery cabinets for Liebert NX 3.3.2Connecting the Batteries 3.3.3Installation ConsiderationsFigure 11 Battery cabinet—details 3.3.4Connecting the Battery Cabinet to the UPS Figure 12 Battery tray and supports3.4Non-StandardBatteries 3.5BCB Shunt TripThis power must be UPS protected 3.6Alber Monitoring System—Optional4.1.2LBS Cable and Settings 4.1Load Bus Synchronization4.0OPTIONS 4.1.1Performance Requirements4.2Configuring Parallel System Operation 4.2.2Features of Parallel System4.2.1General 480V, 3W Input 480V DC Battery Input Figure 15 Parallel system block diagramLiebert NX UPS 40-200kVA 480V, 3W UOB Output•Battery Mode Operation •Maintenance Bypass Mode Operation4.2.3Operating Principles Redundancy Paralleling 4.2.4Operation Modes Summary4.3Installing Parallel System 4.3.2Cabinet Installation4.3.4Power Cables 4.3.1Conditions for Parallel SystemFor startup procedure, 9.2 - UPS Startup Auxiliary Dry Contact Cables4.3.6Emergency Power Off EPO Figure 20 Connecting EPO push buttonX2:3 X2:45.0UPS SPECIFICATIONS Environmental characteristicsUPS mechanical characteristics 5.4UPS Electrical Characteristics Table 8 UPS terminalTable 9 Rectifier input power 5.4.1Input RectifierUPS terminal continued Table 10 Input voltage window with deratingTable 11 Liebert approved replacement batteries 5.4.2DC Intermediate Circuit5.4.3Inverter Output Table 12 DC intermediate circuit5.4.4 Bypass Input Table 14 Bypass inputLeft Side FrontFront Detail AParallel Board FRONT VIEW LEFT VIEW1239mm 2000mmTOP VIEW Front of UPS BOTTOM VIEW Front of UPSInstallation Drawings DETAIL A DETAIL A 224mm8.83 609.3 24 872.2 34.3 U3819205 RIGHT SIDE FRONTSECTION A-A TOP VIEWDetail A Top ViewDetail B without BCB Cover Plate49 Battery Cabinet Right-SideViews A D NX 160-200KVAUPS Module Front View A CBB D CDInstallation Drawings Front Top Right Side845 33.2 965 38 2000 78.7 Right Side FrontFront RearSystem Input UPS OutputWithout Covers FRONT UPS Output Breakers Ground BusbarSystem Kirk-KeyFRONT Door OpenREAR A B1-B4 FRONT Without Covers LEFT SIDE Without Exterior Panels 965 38 in 2000 78.7 inRIGHT SIDE Without Exterior Panels LEFT SIDE Isometric View7.1General Description 7.0OPERATIONBattery Mode 7.1.1Bypass Supplies7.1.2Operating Modes Normal ModeMaintenance Mode Parallel Redundancy Mode System Expansion8.0OPERATOR CONTROL AND DISPLAY PANEL 8.1.1Display Panel LayoutFigure 45 Overview of control panel Liquid Crystal Display LCD Mimic display LED2Figure 47 Mimic display indicators location Bypass indicatorLoad indicator Inverter indicatorInverter Off button Fault Clear button Figure 48 Location of control buttonsButton cover EPO button Silence On/Off button Inverter On buttonData and settings Figure 49 Buzzer locationFigure 50 Sections of the LCD UPS systemTable 17 Icons for navigation keys 8.8LCD Menus and Data Items Figure 51 Menu treeOperator Control and Display Panel 8.9Language Selection Figure 52 Language selection8.10Current Date and Time Figure 53 Set date and timeCurrent StatusMessages History Log records menu8.12.2Default Screen Figure 56 Default screen8.12Types of LCD Screens 8.12.1Opening DisplayPress any key back to main menu 8.12.3UPS Help Screen8.12.4Screen Saver Window Figure 57 Help screen8.13.4 Battery Capacity Test Confirmation 8.13.5Battery Self-TestAborted, Condition Not Met8.13Pop-UpWindows 8.13.3System Self-Test9.1Liebert NX Operating Modes 9.0OPERATING INSTRUCTIONSTable 20 UPS operating modes 9.2.1Startup Procedure 9.2UPS Startup9.1.1Circuit Breakers Figure 59 Circuit breakers•Close CB5 CB1, CB2, CB3 and CB5 are closed Switch from Normal Mode to Bypass Mode Switch from Bypass Mode to Normal Mode9.4Auto Restart 9.5Emergency Shutdown With EPO9.7Battery Protection 9.8Multi-ModuleSystem Procedures9.7.1Battery Undervoltage Pre-Warning 9.7.2Battery End-of-DischargeEOD Protection3.Close Input breaker CB1 9.9Commissioning a Parallel System 9.10Parallel System Startup10.1.2Power Output 10.1Communication and Other User Terminals10.0OPTIONS 10.1.1Analog Input Interface10.1.5Configuring Baud Rates 10.1.4Communication and MonitoringTable 21 Liebert NX communication options Figure 62 Liebert IntelliSlot Web card display Table 22 Relay Card pin configuration Table 23 Relay card jumper configurationRelay Card MultiPort 4 Card Figure 63 MultiPort 4 card pin assignment10.2.1Remote Alarm Monitor Figure 64 Dust filter replacement10.2LBS Mode—LoadBus Synchronization 10.3Replacing Dust Filters11.0SPECIFICATIONS AND TECHNICAL DATA Table 24 Torque specificationsTable 25 Battery torque rating Specifications and Technical DataTable 27 Parallel system current table 11.3Cable size and tightening torques Specifications and Technical Data 11.4Battery Run Times Table 37 Enersys battery run times in minutesTable 38 C&D Dynasty battery run times in minutes Table 38 C&D Dynasty battery run times in minutes APPENDIX A - UPS STATUS MESSAGES Table 39 UPS status messagesUPS Status Messages Table 39 UPS status messages UPS Status MessagesEvent Message Description / Suggested Action if anyTable 39 UPS status messages UPS Status MessagesTable 39 UPS status messages UPS Status MessagesTable 39 UPS status messages UPS Status MessagesUPS Status Messages Page Ensuring The High Availability Of Mission-CriticalData And ApplicationsTechnical Support/ Service reducedcapitalequipment andoperatingcosts
Related manuals
Manual 2 pages 62.47 Kb Manual 108 pages 52.85 Kb

60HZ, 480V specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.