Emerson 60HZ 1.2Internal Inspections, 1.3Preliminary Checks, 1.4UPS Location, 1.3.1Identification

Page 14
1.2Internal Inspections

Installation

1.2Internal Inspections

1.Remove any packaging material, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper and to Liebert immediately.

2.Check the nameplate inside the cabinet door to verify that the model number and rating correspond to the ones specified. Record the model number and serial number in the front of this installation manual. This information is necessary should service be required.

3.Check for loose connections or unsecured components in the cabinet.

4.Check for shipping damage to internal components.

1.2.1Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the Liebert NX from excessive moisture (see 5.2 - UPS Environmental).

! CAUTION

If the battery cabinet must remain disconnected from power for more than six (6) months, the battery must be recharged before use. To charge the batteries, the battery cabinet must be connected to the Liebert NX UPS and the UPS must be connected to utility power and started up because the charger operates only while the Liebert NX UPS is operating.

! CAUTION

When batteries are installed in a cabinet adjacent to the UPS unit, the battery—not the UPS—dictates the designed maximum ambient operating temperature.

1.3Preliminary Checks

1.3.1Identification

The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS.

1.4UPS Location

1.4.1Positioning the UPS

Choose a location for the UPS that offers:

Easy connection to inputs, outputs and auxiliary equipment

Enough space to service the UPS

Air circulation sufficient to expel heat produced by UPS

Protection against moisture and excessive humidity

Protection against dust and other particulate matter

Compliance with fire prevention regulations and practices

Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency

1.4.2Environmental Considerations

Before installing the Liebert NX, verify that the UPS room satisfies the environmental conditions stipulated in 5.2 - UPS Environmental, paying particular attention to the ambient temperature and air exchange system.

The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).

For optimal UPS and battery system performance and service life, maintain the operating tempera- ture within the range of 74-80°F, (23-27°C).

The Liebert NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 8 in. (203mm).

See Table 7 for details on heat dissipation.

6

Image 14
Contents User Manual–40-200kVA, 480V,60Hz Liebert NX UPSAC Power For Business-CriticalContinuityPage TABLE OF CONTENTS 4.0 OPTIONS 9.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FIGURES Figure 39 Main component location drawing Liebert NX 480V, CB2, CB3, CB4 configurations . . . . . . . . . TABLES SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONSBattery Cabinet Precautions • Remove watches, rings and other metal objects AC input AC output GLOSSARY OF SYMBOLSRisk of electrical shock Requests the user to consult the manual1.0INSTALLATION 1.1External Inspections1.3Preliminary Checks 1.2.1Storing for Delayed Installation1.2Internal Inspections 1.4UPS Location1.6Mechanical Considerations Battery Location1.5Considerations in Moving the Liebert NX 1.4.3Special Considerations for Parallel Systems1.6.3Cable Entry 1.6.2Floor Installation1.6.1Clearances System CompositionFront of Units Liebert NX Battery CabinetLiebert Bypass2.1.1Cable Rating 2.1Power Cabling2.0ELECTRICAL CONNECTIONS Lug Size and Torque Requirements2.1.2UPS Input Configuration 2.1.3Cabling Guidelines2.1.4Cable Connections Liebert NX 40-120kVAConnectionsLiebert NX 160-200kVAConnections Figure 4 Input and output busbars2.1.6Protective Devices 2.1.5Safety Ground2.1.7Cabling Procedure UPS Rectifier and Bypass Input SupplyFrequency Converter Mode Common Input ConnectionsDual Input Connections Figure 5 Monitor board U2 2.2.1Monitor Board Features2.2Control Cables 2.3Dry Contacts 2.3.1Input Dry Contacts 2.3.2Maintenance Bypass Cabinet InterfaceTable 2 Maintenance bypass cabinet interface Figure 7 Input dry contactsTable 3 BCB control interface 2.3.3Battery Circuit Breaker Control Interface2.3.4Output Dry Contacts Output dry contact relaysEPO - NO Figure 9 EPO wiring2.3.5EPO Input—Optional EPO - NC3.1Introduction 3.2Safety3.0BATTERY INSTALLATION Figure 10 Battery cabinets for Liebert NX 3.3External Battery Cabinet Installation3.3.1Battery Cabinets Figure 11 Battery cabinet—details 3.3.2Connecting the Batteries3.3.3Installation Considerations 3.4Non-StandardBatteries 3.3.4Connecting the Battery Cabinet to the UPSFigure 12 Battery tray and supports 3.5BCB Shunt TripThis power must be UPS protected 3.6Alber Monitoring System—Optional4.0OPTIONS 4.1.2LBS Cable and Settings4.1Load Bus Synchronization 4.1.1Performance Requirements4.2.1General 4.2Configuring Parallel System Operation4.2.2Features of Parallel System Liebert NX UPS 40-200kVA 480V, 3W Input 480V DC Battery InputFigure 15 Parallel system block diagram 480V, 3W UOB Output4.2.3Operating Principles Redundancy Paralleling •Battery Mode Operation•Maintenance Bypass Mode Operation 4.2.4Operation Modes Summary4.3.4Power Cables 4.3Installing Parallel System4.3.2Cabinet Installation 4.3.1Conditions for Parallel SystemFor startup procedure, 9.2 - UPS Startup Auxiliary Dry Contact CablesX2:3 4.3.6Emergency Power Off EPOFigure 20 Connecting EPO push button X2:4UPS mechanical characteristics 5.0UPS SPECIFICATIONSEnvironmental characteristics 5.4UPS Electrical Characteristics Table 8 UPS terminalUPS terminal continued Table 9 Rectifier input power5.4.1Input Rectifier Table 10 Input voltage window with derating5.4.3Inverter Output Table 11 Liebert approved replacement batteries5.4.2DC Intermediate Circuit Table 12 DC intermediate circuit5.4.4 Bypass Input Table 14 Bypass inputLeft Side FrontFront Detail AParallel Board 1239mm FRONT VIEWLEFT VIEW 2000mmTOP VIEW Front of UPS BOTTOM VIEW Front of UPSInstallation Drawings DETAIL A 8.83 DETAIL A224mm 609.3 24 872.2 34.3 U3819205 SECTION A-A RIGHT SIDEFRONT TOP VIEWDetail B Detail ATop View without BCB Cover Plate49 Battery Cabinet Right-SideViews A D NX 160-200KVAUPS Module Front View A CBB D CDBattery Breaker 845 33.2 965 38 2000 78.7 FrontTop Right Side Right Side FrontSystem Input FrontRear UPS OutputWithout Covers System FRONTUPS Output Breakers Ground Busbar Kirk-KeyREAR FRONTDoor Open A B1-B4 FRONT Without Covers RIGHT SIDE Without Exterior Panels LEFT SIDE Without Exterior Panels 965 38 in 200078.7 in LEFT SIDE Isometric View7.1General Description 7.0OPERATION7.1.2Operating Modes Battery Mode7.1.1Bypass Supplies Normal ModeMaintenance Mode Parallel Redundancy Mode System ExpansionFigure 45 Overview of control panel 8.0OPERATOR CONTROL AND DISPLAY PANEL8.1.1Display Panel Layout Liquid Crystal Display LCD Mimic display LED2Load indicator Figure 47 Mimic display indicators locationBypass indicator Inverter indicatorButton cover EPO button Inverter Off button Fault Clear buttonFigure 48 Location of control buttons Silence On/Off button Inverter On buttonFigure 50 Sections of the LCD Data and settingsFigure 49 Buzzer location UPS systemTable 17 Icons for navigation keys 8.8LCD Menus and Data Items Figure 51 Menu treeOperator Control and Display Panel 8.9Language Selection Figure 52 Language selection8.10Current Date and Time Figure 53 Set date and timeMessages CurrentStatus History Log records menu8.12Types of LCD Screens 8.12.2Default ScreenFigure 56 Default screen 8.12.1Opening Display8.12.4Screen Saver Window Press any key back to main menu8.12.3UPS Help Screen Figure 57 Help screen8.13Pop-UpWindows 8.13.4 Battery Capacity Test Confirmation8.13.5Battery Self-TestAborted, Condition Not Met 8.13.3System Self-TestTable 20 UPS operating modes 9.1Liebert NX Operating Modes9.0OPERATING INSTRUCTIONS 9.1.1Circuit Breakers 9.2.1Startup Procedure9.2UPS Startup Figure 59 Circuit breakers•Close CB5 CB1, CB2, CB3 and CB5 are closed Switch from Normal Mode to Bypass Mode Switch from Bypass Mode to Normal Mode9.4Auto Restart 9.5Emergency Shutdown With EPO9.7.1Battery Undervoltage Pre-Warning 9.7Battery Protection9.8Multi-ModuleSystem Procedures 9.7.2Battery End-of-DischargeEOD Protection3.Close Input breaker CB1 9.9Commissioning a Parallel System 9.10Parallel System Startup10.0OPTIONS 10.1.2Power Output10.1Communication and Other User Terminals 10.1.1Analog Input InterfaceTable 21 Liebert NX communication options 10.1.5Configuring Baud Rates10.1.4Communication and Monitoring Figure 62 Liebert IntelliSlot Web card display Relay Card Table 22 Relay Card pin configurationTable 23 Relay card jumper configuration MultiPort 4 Card Figure 63 MultiPort 4 card pin assignment10.2LBS Mode—LoadBus Synchronization 10.2.1Remote Alarm MonitorFigure 64 Dust filter replacement 10.3Replacing Dust FiltersTable 25 Battery torque rating 11.0SPECIFICATIONS AND TECHNICAL DATATable 24 Torque specifications Specifications and Technical DataTable 27 Parallel system current table 11.3Cable size and tightening torques Specifications and Technical Data Table 38 C&D Dynasty battery run times in minutes 11.4Battery Run TimesTable 37 Enersys battery run times in minutes Table 38 C&D Dynasty battery run times in minutes UPS Status Messages APPENDIX A - UPS STATUS MESSAGESTable 39 UPS status messages Event Message Table 39 UPS status messagesUPS Status Messages Description / Suggested Action if anyTable 39 UPS status messages UPS Status MessagesTable 39 UPS status messages UPS Status MessagesTable 39 UPS status messages UPS Status MessagesUPS Status Messages Page Technical Support/ Service Ensuring The High AvailabilityOf Mission-CriticalData And Applications reducedcapitalequipment andoperatingcosts
Related manuals
Manual 2 pages 62.47 Kb Manual 108 pages 52.85 Kb

60HZ, 480V specifications

The Emerson 40-120KVA UPS is a high-performing uninterruptible power supply designed to ensure the reliability and continuity of critical operations across various industries. This UPS operates at 480VAC and 60Hz, making it suitable for environments where high-power demands are common.

One of the standout features of this UPS system is its modular design, which allows for easy scalability. Organizations can expand their power capacity as their needs grow, making the Emerson 40-120KVA UPS a future-proof investment. The system operates with high efficiency, minimizing energy consumption and operational costs. This is vital for data centers and industrial applications where energy management is increasingly important.

The Emerson UPS incorporates advanced digital signal processing technology, delivering real-time monitoring and control. This enhances the overall performance and reliability of the system, providing seamless power protection against voltage fluctuations, surges, and interruptions. With a total harmonic distortion of less than 5%, the UPS ensures a clean and stable power output, preserving the integrity of sensitive electronic equipment.

Another noteworthy characteristic of the Emerson 40-120KVA is its redundancy features. The system supports N+1 redundancy, allowing for one extra module to ensure uninterrupted service in case of a failure. This design offers peace of mind for critical applications, ensuring that there is no single point of failure.

User-friendliness is also a significant aspect of the Emerson UPS. The intuitive graphical user interface simplifies monitoring and management, allowing operators to assess system performance and status at a glance. Additionally, remote monitoring capabilities enable real-time tracking of system health and performance from anywhere, providing flexibility and oversight for facility managers.

The Emerson 40-120KVA UPS also meets stringent safety and compliance standards, ensuring reliable operation in demanding environments. Its robust design is suitable for a variety of applications, including information technology, telecommunications, and industrial processes. Overall, the Emerson 40-120KVA UPS stands out as a reliable, efficient, and versatile solution for businesses aiming to safeguard their critical power supply against any disruption.