Emerson SERIES 600T manual DIS Product

Page 15

Figure 2. Alternative Grounding Configuration, 480 or 600 VAC input and output

7.2Alternative Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Distribution Units, Wye-Connected Service

This configuration is similar to that shown in Section 7.1, except that the service entrance neutral is not brought into the UPS module. In this configuration, the UPS output transformer is considered a separately derived source. The UPS module neutral is bonded to the UPS ground, which is connected to a local grounding electrode in accordance with NEC 250-26.

Please note that this configuration represents a price/performance trade-off. Whenever the UPS module transfers to or from bypass, two AC sources (input and bypass) are briefly connected together and circulating current must flow. In the previous configuration, the current flows through the neutral conductor. In this configuration, the current flows through the ground path, possibly tripping ground fault interruptors (GFIs) and distorting the bypass waveform reference. Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping.

This configuration is reserved for those applications which meet all the following criteria:

The facility has Wye-connected service

The module rectifier input and bypass input are fed from the same source

The connected load is strictly 3-wire (such as one or more PDUs) and does not require a neutral from the UPS

Special precautions are taken to prevent trip- ping the ground fault interruptors. The time delay should be set to at least 30 cycles to pre- vent tripping when the UPS performs a transfer or retransfer operation.

CAUTION

Failure to properly set the ground fault interruptors could cause loss of power to the critical load.

Liebert Series 600T UPS, 65-225 kVA, Single Module

9

DISCONTINUED

PRODUCT

Image 15
Contents   DIS Product Installation Manual Table of Contents Figures Product DIS Product Installation Installation Considerations Internal Inspections External InspectionsEquipment Location Battery Safety PrecautionsBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Open-Rack Batteries Configuring Your Neutral and Ground Connections8Installation Manual DIS Product 10Installation Manual Preferred Grounding Configuration, 208 VAC input and output Grounding Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Battery Cabinet Grounding Configuration Preferred Grounding Configuration, Battery SystemsPower Wiring Wiring ConsiderationsTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Battery Wiring Control WiringSpecific Connections Wiring ConnectionsWiring Inspection Torque Specifications Power Wiring Terminals Factory SuppliedONE-HOLE Lugs Field-Supplied LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA DIS Product DIS Product Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA DIS Product Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps DIS Product DIS Product DIS Product Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets DIS Product DIS Product Line-up Detail, 65 & 80 kVA with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA with 3-Breaker MBC DIS Product Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS DIS Product Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA DIS Product Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 DIS Product       
Related manuals
Manual 168 pages 35.62 Kb