9. WIRING CONNECTIONS

9.1 Warnings

DANGER

VERIFY THAT ALL INCOMING HIGH AND LOW VOLTAGE POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE INSTALLING CABLES OR MAKING ELECTRICAL CONNECTIONS.

ALL POWER CONNECTIONS MUST BE COMPLETED BY A LICENSED ELECTRICIAN EXPERIENCED IN WIRING UPS EQUIPMENT, AND IN ACCORDANCE WITH ALL APPLICABLE NATIONAL AND LOCAL ELECTRICAL CODES.

IMPROPER WIRING MAY CAUSE DAMAGE TO THE UPS OR INJURY TO PERSONNEL.

CAUTION

All shielded cables, non-shielded cables, non-shielded control wires, non-shielded battery breaker control wires, and non- shielded remote control wires must be housed in individual, separate, steel conduits. Placing multiple cables in the same conduit with other control or power wiring may cause system failure.

9.2 Specific Connections

Refer to the drawings in this manual and any other drawings provided by Liebert for this installation. Make all of the following connections:

a.AC power cables from input power source circuit breaker to UPS Module Input. Observe phase rotation.

CAUTION

See Section 7 of this Manual for an explanation of proper grounding techniques.

b.AC power cables from bypass power source cir- cuit breaker to UPS Module Bypass input. Observe phase rotation.

c.AC power cables from UPS Module Output to critical load. Observe phase rotation.

NOTE

If your installation includes a Maintenance Bypass Cabinet, Switchboard or Panelboard, some (or all) power cables will be terminated in these cabinet(s). Make sure all required wiring between UPS module and the optional cabinet(s) is completed. Observe phase rotation.

d.The UPS Module Output Neutral must be con- nected to one common point and solidly grounded per requirements of the National Electrical Code. See Section 7.

CAUTION

UPS bypass and output neutral must be connected to only one common point in the UPS. This neutral line must be grounded at the source.

e.For Battery Cabinets:

DC power cables and ground from Battery Cab- inet to UPS Module, and between Battery Cab- inets. Observe polarity. DC power cables should be installed in matched pairs (positive and negative).

20

Installation Manual

DISCONTINUED

PRODUCT

Image 26
Contents   DIS Product Installation Manual Table of Contents Figures Product DIS Product Installation Installation Considerations External Inspections Internal InspectionsBattery Safety Precautions Equipment LocationBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Configuring Your Neutral and Ground Connections Open-Rack Batteries8Installation Manual DIS Product 10Installation Manual Preferred Grounding Configuration, 208 VAC input and output Grounding Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Grounding Configuration, Battery Systems Preferred Battery Cabinet Grounding ConfigurationWiring Considerations Power WiringTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Control Wiring Battery WiringWiring Connections Specific ConnectionsWiring Inspection Power Wiring Terminals Factory Supplied Torque SpecificationsField-Supplied Lugs ONE-HOLE LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA DIS Product DIS Product Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA DIS Product Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps DIS Product DIS Product DIS Product Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets DIS Product DIS Product Line-up Detail, 65 & 80 kVA with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA with 3-Breaker MBC DIS Product Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS DIS Product Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA DIS Product Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 DIS Product       