Emerson SERIES 600T manual Types TW= FEPW= TBS, SA

Page 30

Table 310-16. Allowable Ampacities of Insulated Conductors

Rated 0-2000 Volts, 60to 90C (140to 194F)

Not More Than Three Conductors in Raceway or Cable or

Earth (Directly Buried), Based on Ambient Temperature of 30(86F)

Size

 

 

 

Temperature Rating of Conductor. See Table 310-13.

 

Size

 

60oC

75°C

 

90°C

60°C

75°C

90°C

 

 

 

(140°F)

(167°F)

 

(194°F)

(140°)

(167°F)

(194°F)

 

 

 

TYPES

TYPES

 

TYPES

TYPES

TYPES

TYPES

 

 

 

TW=

FEPW=,

 

TBS, SA,

TW=

RH=, RHW=,

TBS,

 

 

AWG

UF=

RH, RHW=,

 

SIS, FEP=

UF=

THHW=,

SA, SIS,

AWG

 

THHW=,

 

FEPB=, MI,

 

THW=,

THHN=,

kcmil

 

THW=,

 

RHH= RHW-2

 

THWN=,

THHW=,

kcmil

 

 

THWN=,

 

THHN=, THHW=,

 

XHHW=,

THW-2, THWN-2,

 

 

 

 

XHHW=,

 

THW-2, THWN-2,

 

USE=

RHH==, RHW-2,

 

 

 

 

USE=, ZW=

 

USE-2, XHH,

 

 

USE-2,

 

 

 

 

 

 

XHHW=

 

 

XHH, XHHW=,

 

 

 

 

 

 

XHHW-2, ZW-2

 

 

XHHW-2, ZW-2

 

 

 

 

COPPER

 

ALUMINUM OR

COPPER-CLAD ALUMINUM

 

 

18

......

.......

 

14

.......

.......

.......

.......

 

16

......

.......

 

18

.......

.......

.......

.......

 

14*

20

20

 

25

.......

.......

.......

.......

 

12*

25

25

 

30

20

20

25

12*

 

10*

30

35

 

40

25

30

35

10*

 

8

40

50

 

55

30

40

45

8*

 

6

55

65

 

75

40

50

60

6

 

4

70

85

 

95

55

65

75

4

 

3

85

100

 

110

65

75

85

3

 

2

95

115

 

130

75

90

100

2

 

1

110

130

 

150

85

100

115

1

 

 

 

 

 

 

 

 

 

 

 

1/0

125

150

 

170

100

120

135

1/0

 

2/0

145

175

 

195

115

135

150

2/0

 

3/0

165

200

 

225

130

155

175

3/0

 

4/0

195

230

 

260

150

180

205

4/0

 

250

215

255

 

290

170

205

230

250

 

300

240

285

 

320

190

230

255

300

 

350

260

310

 

350

210

250

280

350

 

400

280

335

 

380

225

270

305

400

 

500

320

380

 

430

260

310

350

500

 

600

355

420

 

475

285

340

385

600

 

700

385

460

 

520

310

375

420

700

 

750

400

475

 

535

320

385

435

750

 

800

410

490

 

555

330

395

450

800

 

900

435

520

 

585

355

425

480

900

 

1000

455

545

 

615

375

445

500

1000

 

1250

495

590

 

665

405

485

545

1250

 

1500

520

625

 

705

435

520

585

1500

 

1750

545

650

 

735

455

545

615

1750

 

2000

560

665

 

750

470

560

630

2000

 

 

 

 

 

CORRECTION FACTORS

 

 

 

 

Ambient

 

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities

Ambient

 

Temp °C

 

 

shown above by the appropriate factor shown below.

 

Temp °F

21-25

1.08

1.05

 

1.04

1.08

1.05

1.04

70-77

 

26-30

1.00

1.00

 

1.00

1.00

1.00

1.00

78-86

 

31-35

.91

.94

 

.96

.91

.94

.96

87-95

 

36-40

.82

.88

 

.91

.82

.88

.91

96-104

 

41-45

.71

.82

 

.87

.71

.82

.87

105-113

 

46-50

.58

.75

 

.82

.58

.75

.82

114-122

 

51-55

.41

.67

 

.76

.41

.67

.76

123-131

 

56-60

.......

.58

 

.71

.......

.58

.71

132-140

 

61-70

.......

.33

 

.58

.......

.33

.58

141-158

 

71-80

.......

.......

 

.41

.......

.......

.41

159-176

 

*Unless otherwise specifically permitted in Section 240-3 of this Code, the overcurrent protection for conductor types marked with an asterisk (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.

Reprinted with permission from NEC 1999, NFPA 70, the National Electrical Code , Copyright 1998, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.

24

Installation Manual

DISCONTINUED

PRODUCT

Image 30
Contents   DIS Product Installation Manual Table of Contents Figures Product DIS Product Installation Installation Considerations External Inspections Internal InspectionsBattery Safety Precautions Equipment LocationBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Configuring Your Neutral and Ground Connections Open-Rack Batteries8Installation Manual DIS Product 10Installation Manual Preferred Grounding Configuration, 208 VAC input and output Grounding Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Grounding Configuration, Battery Systems Preferred Battery Cabinet Grounding ConfigurationWiring Considerations Power WiringTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Control Wiring Battery WiringWiring Connections Specific ConnectionsWiring Inspection Power Wiring Terminals Factory Supplied Torque SpecificationsField-Supplied Lugs ONE-HOLE LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA DIS Product DIS Product Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA DIS Product Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps DIS Product DIS Product DIS Product Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets DIS Product DIS Product Line-up Detail, 65 & 80 kVA with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA with 3-Breaker MBC DIS Product Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS DIS Product Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA DIS Product Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 DIS Product       
Related manuals
Manual 168 pages 35.62 Kb

SERIES 600T specifications

The Emerson SERIES 600T, as part of the SERIES 600 line, is a sophisticated device designed to meet the demands of industrial automation and control systems. Renowned for its reliability and versatility, the SERIES 600T excels in various applications across multiple sectors, including oil and gas, chemical processing, and power generation.

One of the most significant features of the SERIES 600T is its advanced measuring capability. It offers exceptional accuracy, typically within ±0.1% of the full scale. This precision makes it suitable for critical applications where measurement integrity is paramount. The SERIES 600T is also equipped with intelligent diagnostics that can predict and monitor the health of the unit, enabling proactive maintenance and minimizing downtime. This technological advancement improves both operational efficiency and safety.

Another standout characteristic is the device's robust construction designed to withstand harsh environments. The SERIES 600T is made with durable materials that provide resistance to corrosion, vibration, and temperature extremes, making it an excellent choice for rugged industrial applications. Coupled with its IP67 rating, the device is fully sealed against dust and moisture, ensuring long-term reliability in challenging conditions.

The SERIES 600 line employs cutting-edge communication protocols, including HART and Foundation Fieldbus, facilitating seamless integration into various control systems. This capability ensures that users can easily access real-time data and manage devices remotely, significantly enhancing operational efficiency.

Additionally, the SERIES 600T supports a wide range of process connections and configurations, catering to diverse installation needs. This adaptability allows for quick deployments and minimizes the time required for system changes or upgrades.

With easy-to-read displays and user-friendly interfaces, operators can quickly interpret data and metrics from the SERIES 600T. This intuitive design helps reduce the learning curve for new users, further underlining the device's legacy of reliability and efficiency.

In essence, the Emerson SERIES 600T exemplifies cutting-edge technology in the realm of industrial measurement and automation. Its combination of accuracy, durability, diagnostic capabilities, and ease of integration makes it an ideal choice for industries that prioritize reliability and precision in their operations. As industrial processes continue to evolve, devices like the SERIES 600T will undoubtedly play a crucial role in advancing efficiency and productivity in various sectors.