Emerson SERIES 600T manual Appendix a Site Planning Data KVA Single Module Systems

Page 79

Appendix A: Site Planning Data

65-225 kVA Single Module Systems

Notes

1.Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current limits are defined in NEC 100. Maximum input current is controlled by current limit setting which is adjustable. Values shown for maximum setting are 125% of nominal input current. Standard factory setting is 115%.

2.Nominal AC output current (considered continuous) is based on full rated output load. Maximum current includes nominal output current and overload current for 10 minutes.

3.Bypass AC input current (considered continuous) is based on full rated output load.

4.Feeder protection (by others in external equipment) for rectifier AC input and bypass AC input is recommended to be provided by separate overcurrent protection devices.

5.UPS output load cables must be run in separate conduit from input cables.

6.Power cable from module DC bus to battery should be sized for a total maximum 2.0 volt line drop (measured at the module) at maximum discharge current.

7.Grounding conductors to be sized per NEC 250-122. Neutral conductors to be sized for full capacity -- per NEC 310-15 (b)(4) -- for systems with 4-wire loads and half capacity for systems with 3-wire loads.

8.Rectifier AC Input:3-phase, 3-wire, plus ground

AC Output to Load: 3-phase, 3 or 4-wire, plus ground Bypass AC Input:3-phase, 3 or 4-wire, plus ground

Module DC Input from Battery:2-wire, (positive and negative) plus ground

9.All wiring is to be in accordance with National and Local Electrical Codes.

10.Minimum overhead clearance is 2 feet above UPS.

11.Top and bottom cable entry standard through removable access plates. However, SpaceSaver versions of the 100-225 kVA modules are 8” narrower (48” vs. 56”) and are top-entry only. Tables show SpaceSaver modules, where available. Cut access plates to suit conduit size.

12.Control wiring and power cables must be run in separate conduits. Control wiring must be stranded tinned conductors.

13.7% maximum reflected input harmonic current and 0.92 lagging input power factor at full load with optional input filter.

Liebert Series 600T UPS, 65-225 kVA, Single Module

A-1

DISCONTINUED

PRODUCT

Image 79
Contents   DIS Product Installation Manual Table of Contents Figures Product DIS Product Installation Installation Considerations Internal Inspections External InspectionsEquipment Location Battery Safety PrecautionsBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Open-Rack Batteries Configuring Your Neutral and Ground Connections8Installation Manual DIS Product 10Installation Manual Preferred Grounding Configuration, 208 VAC input and output Grounding Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Battery Cabinet Grounding Configuration Preferred Grounding Configuration, Battery SystemsPower Wiring Wiring ConsiderationsTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Battery Wiring Control WiringSpecific Connections Wiring ConnectionsWiring Inspection Torque Specifications Power Wiring Terminals Factory SuppliedONE-HOLE Lugs Field-Supplied LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA DIS Product DIS Product Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA DIS Product Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps DIS Product DIS Product DIS Product Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets DIS Product DIS Product Line-up Detail, 65 & 80 kVA with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC DIS Product Line-up Detail, 100-225 kVA with 3-Breaker MBC DIS Product Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS DIS Product Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA DIS Product Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 DIS Product       
Related manuals
Manual 168 pages 35.62 Kb

SERIES 600T specifications

The Emerson SERIES 600T, as part of the SERIES 600 line, is a sophisticated device designed to meet the demands of industrial automation and control systems. Renowned for its reliability and versatility, the SERIES 600T excels in various applications across multiple sectors, including oil and gas, chemical processing, and power generation.

One of the most significant features of the SERIES 600T is its advanced measuring capability. It offers exceptional accuracy, typically within ±0.1% of the full scale. This precision makes it suitable for critical applications where measurement integrity is paramount. The SERIES 600T is also equipped with intelligent diagnostics that can predict and monitor the health of the unit, enabling proactive maintenance and minimizing downtime. This technological advancement improves both operational efficiency and safety.

Another standout characteristic is the device's robust construction designed to withstand harsh environments. The SERIES 600T is made with durable materials that provide resistance to corrosion, vibration, and temperature extremes, making it an excellent choice for rugged industrial applications. Coupled with its IP67 rating, the device is fully sealed against dust and moisture, ensuring long-term reliability in challenging conditions.

The SERIES 600 line employs cutting-edge communication protocols, including HART and Foundation Fieldbus, facilitating seamless integration into various control systems. This capability ensures that users can easily access real-time data and manage devices remotely, significantly enhancing operational efficiency.

Additionally, the SERIES 600T supports a wide range of process connections and configurations, catering to diverse installation needs. This adaptability allows for quick deployments and minimizes the time required for system changes or upgrades.

With easy-to-read displays and user-friendly interfaces, operators can quickly interpret data and metrics from the SERIES 600T. This intuitive design helps reduce the learning curve for new users, further underlining the device's legacy of reliability and efficiency.

In essence, the Emerson SERIES 600T exemplifies cutting-edge technology in the realm of industrial measurement and automation. Its combination of accuracy, durability, diagnostic capabilities, and ease of integration makes it an ideal choice for industries that prioritize reliability and precision in their operations. As industrial processes continue to evolve, devices like the SERIES 600T will undoubtedly play a crucial role in advancing efficiency and productivity in various sectors.