Emerson 1500VA, 1000VA quick start Replacing the Battery, Troubleshooting, Specifications

Page 2

REPLACING THE BATTERY

To replace the battery:

1.Turn off all connected loads, then turn off the UPS (batteries are NOT hot-swappable).

2.

Use a Phillips head screwdriver to remove the two top cover screws from

Steps 2 and 3

 

the back of the UPS.

 

3.

Slide the top panel backward 1/2" (13mm). Slide the front panel upward,

 

 

then pull outward to remove it.

 

4.

Gently pull the batteries out of the UPS.

 

5.

Remove the black wire from the negative (-) terminal and the red wire from

 

 

the positive (+) terminal.

 

6.

Verify that the replacement battery matches the dimensions and battery

Steps 4 and 5

 

type in the Specifications section below.

 

 

7.Connect the battery leads to the new batteries. Be sure to reconnect the red wire to the positive (+) terminal and the black wire to the negative (-)

terminal.

-

Note: Small sparks may occur at the battery connectors during

reconnection.

 

8.Slide the batteries into the UPS.

9.Reposition the front panel and slide downward until it slides into place. Slide the top panel forward until flush with the front panel. Reinsert the two top cover screws removed in Step 2.

Dispose of the old batteries properly at an appropriate recycling facility.

TROUBLESHOOTING

If the UPS malfunctions during operation, check the following chart for proper adjustment. For further assistance, please contact your local Emerson Network Power representative.

Problem

Possible Causes

Solutions

 

 

 

 

The UPS may not be turned on.

• Press the On/Off button to turn on the UPS.

Utility power is normal, but LED 1 is not illuminated.

The power cord may not be connected properly.

• Connect the power cord securely into a wall outlet.

 

The upstream input circuit breaker may be tripped.

• Reset the input circuit breaker.

 

 

 

LED 2 flashes (amber) every 3 seconds, but there is

Battery voltage may be too low.

• Recharge the UPS for 8 hours.

no output power.

 

 

 

 

 

Alarm buzzer beeps continuously although utility

The UPS may be overloaded (check LED 2).

• Disconnect some equipment from the UPS.

power is normal.

 

 

 

 

 

UPS does not provide expected backup time.

The UPS battery reached end of life.

• Replace the internal battery.

 

 

 

The UPS is on and connected to input power, but fails

Utility power may be outside the unit’s operating range.

• If utility power is normal, try reconnecting input

to operate properly.

power and restarting the UPS.

 

 

 

 

SPECIFICATIONS

Model Number

PSA1000MT3-120U

 

PSA1500MT3-120U

 

 

 

 

Capacity (VA/W)

1000/600

 

1500/900

 

 

 

 

Net Weight, lb. (kg)

23.8 (10.8)

 

27.8 (12.6)

 

 

 

 

Shipping Weight, lb. (kg)

26.0 (11.8)

 

30.0 (13.6)

 

 

 

Dimensions - W x D x H, in. (mm)

5.8 x 14.2 x 9.2 (147 x 360 x 234)

 

 

 

On-Line Input Voltage

 

84-140VAC

 

 

On-Line Frequency

50/60Hz ±5Hz

 

 

Output Voltage (Mains Normal)

Typical 97-129VAC

 

 

Output Voltage (Battery Operation)

120VAC ±5%

 

 

On-Battery Wave Form

Stepped sinewave

 

 

 

 

Battery Type - VDC x Ah x Quantity

12V x 7Ah x 2

 

12V x 9Ah x 2

 

 

 

Typical Recharge Time

6-8 hours to 90%

 

 

 

Battery Run Time* - Full Load

 

6 minutes

 

 

Battery Run Time* - Half Load

12-13 minutes

 

 

Audible and Visual

Audible alarm / LED

 

 

Backup Outlets

NEMA 5-15R (6)

 

 

Surge Outlets

NEMA 5-15R (2)

 

 

Operating Temperature, °F (°C)

32 to 104 (0 to 40)

 

 

Storage Temperature, °F (°C)

5 to 104 (-15 to 40)

 

 

Operating / Storage Relative Humidity

0%-90%, non-condensing

 

 

EMI Classification

FCC Part 15 Class B

 

 

 

 

Agency

 

 

 

 

 

 

Safety

UL 1778, c-UL Listed

 

 

Transportation

ISTA Procedure 1A Certification

 

 

 

 

* Battery run time may vary depending on load

 

 

 

© 2008 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

® Liebert is a registered trademark of Liebert Corporation.

All names referred to are trademarks or registered trademarks of their respective owners.

SL-23301_REV0_04-08

Technical Support / Service

United States

800-222-5877 (Outside U.S. 614-841-6755)

1050 Dearborn Drive

upstech@emersonnetworkpower.com

P.O. Box 29186

Web site: www.liebert.com

Columbus, OH 43229

Image 2
Contents UPS Controls and Connections Important Safety InstructionsSetup Specifications Replacing the BatteryTroubleshooting

1000VA, 1500VA specifications

Emerson 1000VA and 1500VA uninterruptible power supplies (UPS) are high-quality power protection solutions designed to ensure the smooth operation and reliability of critical electronic equipment. These models are particularly favored in industries where downtime can result in significant losses.

One of the main features of the Emerson 1000VA and 1500VA UPS units is their robust power capacity. The 1000VA model is capable of supporting essential equipment such as routers, servers, and workstations, making it ideal for small to medium-sized businesses. The 1500VA model, with its higher capacity, is suited for larger operations with more demanding power needs. Both models offer a reliable backup power supply, which automatically switches on during a power failure, ensuring that connected devices continue to operate without interruption.

In addition to their power capabilities, these UPS systems come equipped with advanced technologies designed to enhance performance and user experience. The Emerson UPS units feature line-interactive technology, which allows them to automatically adjust voltage fluctuations, providing a stable power output to connected devices. This is particularly beneficial in environments where power quality is inconsistent, as it helps in prolonging the lifespan of equipment.

Both models boast intuitive LCD displays that provide real-time information on power status, battery health, and load levels. This allows users to monitor their UPS systems easily and make informed decisions regarding maintenance and usage. Additionally, they come with USB communication ports, enabling seamless integration with management software for enhanced monitoring and control.

Safety is also a major concern with Emerson UPS systems. They are equipped with features such as overload protection, short-circuit protection, and battery management systems that ensure safe operation and protect against potential hazards. The built-in surge protection safeguards against electrical surges, protecting sensitive electronic equipment from damage.

In summary, the Emerson 1000VA and 1500VA UPS systems offer reliable power protection solutions with a combination of robust performance, advanced technologies, and critical safety features. They are an essential investment for any organization that values uninterrupted power supply and the protection of its electronic assets.