4--6 Description of Operation

Delayed–Transition Automatic Transfer (4ADTS, 7ADTS, 7ADTB)

NORMAL FAILED

TEST MODE

TEST CIRCUIT 5 Waiting for Emerg Acceptable

TEST MODE

TEST CIRCUIT 5

TD Load Disconnect

__min __s

TEST MODE

TEST CIRCUIT 5

Load on Emerg

Load Transfer To Emergency

The sequence for load transfer to the emergency source begins automatically when the controller detects a normal source failure or a transfer test signal.

Normal Source Failure. The Normal source is considered unacceptable when any one of six voltage, frequency, or phase rotation conditions occur (see page 3–1).

Transfer Test Signal. Test transfer signal can be from the Transfer Control switch (Feature 5), the engine–generator exerciser clock (Feature 11C), or via the serial port (Feature 72A). When using the Transfer Control switch, it must be held in the Transfer Test position until the emergency source becomes available (within 15 seconds).

The controller begins the load transfer sequence by de–energizing the SE and SE2 relays and starting the Feature 1C time delay. Feature 1C time delay on engine starting prevents nuisance starting of the engine–generator set and load transfer to emergency due to momentary failures of the normal source. If the normal source is restored (voltage returns above the dropout point) while Feature 1C time delay is running, the SE and SE2 relays are re–energized and the transfer sequence is terminated. (For transfer test the Feature 1C time delay is bypassed.)

Engine Start Signal. When the Feature 1C time delay ends, the controller de–energizes the NR relay which signals the engine–generator to start. The controller monitors the emergency source, waiting for it to become acceptable. Both voltage and frequency must reach preset pickup points before the emergency source is accepted. Usually about 10 seconds elapse from dropout of the NR relay to acceptance of the emergency source. This interval occurs because the engine–generator must crank, start, and run up to nominal pickup points. If the emergency source is available immediately, the controller will accept it as soon as the NR relay drops out.

When the emergency source becomes acceptable, the controller starts the Feature 2B time delay on transfer to emergency (if desired). Feature 2B time delay allows the emergency source to stabilize before load transfer. If the emergency source fails while Feature 2B time delay is running, the controller again waits for the emergency source to become acceptable again and restarts Feature 2B.

At the conclusion of the Feature 2B time delay, the controller is ready to transfer the load to emergency.

Load Transfer. To transfer the load to the emergency source in a delayed–transition mode the controller energizes ER relay first. The transfer switch CN coil energizes and opens the CN transfer switch contacts. The load is disconnected from both sources. The load disconnect time delay starts. When this time delay ends, the controller energizes the ER relay. The transfer switch CE coil energizes and closes the CE transfer switch main contacts. The transfer switch is now supplying the load from emergency source.

Image 26
Contents Description 381333-126 KControl Overview Power Control Center display and keypad Left-Right ArrowsEnter/Save Settings Up-Down ArrowsSettings Overview How to Change a Setting TipNormal Frequency Voltage & Frequency SettingsNormalvoltageunbal Emerg FrequencyNormal Frequency CP SettingsNormal Voltage Normal Voltage UnbalanceTime Delay Settings TD EN Xfer Signal Standard Time DelaysTD NE Xfer Signal Bypass Currently Running TDFeatures Settings Commit to Xfer After TD Normal Fail see Phase Rotation MonitorIn-Phase Monitor Shed LoadGeneral Settings Primary Failure Detection not shownChange Password Default to Factory SettingsReset Engine Exerc Programs Menu Language not shownPresent DATE/TIME Engine Exerciser SettingsJAN P1 Engine ExerciserP1-7 Engine Exercisers Engine Exerciser Settings MenusPresent Date/Time Event Types View Event LogLogged Events Event ReasonsATS Statistics Service Statistics / DiagnosticsView Service Data Source StatisticsService Factory Selectable Features ATS Status Status InformationSource Acceptability Normal Source StatusDisplay Messages and their Meaning Wrong Password Test Mode Serial CommTest Mode Test Circuit XTD Parallel AlarmOpen-Transition 2-position Automatic Transfer 4ATS,7ATS,7ATB Load Transfer To EmergencyOpen-Transition 2-position Automatic Transfer Switches Load Retransfer To NormalClosed-Transition Automatic Transfer 4ACTS, 7ACTS, 7ACTB Closed-Transition Automatic Transfer Switches Closed-Transition Load Retransfer To Normal Bypass Closed-Transition Load TransferDelayed-Transition Automatic Transfer 4ADTS, 7ADTS, 7ADTB Delayed-Transition Automatic Transfer Switches Controller Cover Removal Figure A-1. Cover release latchesNominal Source Voltage Selection DIP Switch ActuatorsTransfer Switch Type Frequency of Sources Phases of Normal & Emergency SourcesLost or Forgotten Password Data Input LockVoltage Jumper Blocks Figure A-3. Location of jumper blocksIndex
Related manuals
Manual 172 pages 36.16 Kb Manual 12 pages 23.06 Kb Manual 28 pages 10.34 Kb Manual 9 pages 27.84 Kb

4000, 7000 specifications

The Emerson 7000 series is a versatile and advanced automation solution designed for modern industrial environments. Renowned for its reliability, scalability, and performance, the Emerson 7000 series is tailored to meet the complex demands of various industries, including oil and gas, chemical manufacturing, power generation, and food and beverage.

At the heart of the Emerson 7000 series is its powerful and flexible architecture. This series integrates seamlessly with existing systems, allowing for easy upgrades without disrupting ongoing processes. The modular design enables users to customize their setups according to their specific needs, providing unmatched adaptability in dynamic operations.

One of the standout features of the Emerson 7000 is its intelligent diagnostics capabilities. This technology leverages advanced algorithms and machine learning to predict equipment failures and maintenance needs, thus minimizing unplanned downtime. By continuously monitoring critical parameters, the system provides operators with actionable insights, enhancing operational efficiency and safety.

The Emerson 7000 series also focuses on user-friendly interfaces. Its intuitive design allows operators to quickly navigate complex data and analytics, facilitating quicker decision-making. The human-machine interface (HMI) provides a clear visual representation of processes, empowering users to manage operations effectively.

Another cutting-edge technology in the Emerson 7000 series is its cybersecurity measures. With the increasing threat of cyber-attacks in industrial environments, Emerson has prioritized the integration of robust security protocols. These features protect sensitive data and ensure the integrity of operations, safeguarding organizations from potential breaches.

Additionally, the Emerson 7000 series supports a wide range of communication protocols, making it compatible with various devices and systems. This interoperability allows for greater collaboration between different technologies within a facility, streamlining workflows and enhancing productivity.

Lastly, the Emerson 7000 emphasizes sustainability and energy efficiency. By providing insights into energy consumption and operational performance, the system helps organizations minimize their environmental impact and reduce operational costs.

In summary, the Emerson 7000 series stands out as a comprehensive automation solution that combines cutting-edge technologies, user-friendly interfaces, robust cybersecurity, and a commitment to sustainability. With its ability to adapt to diverse industrial needs and enhance operational efficiency, the Emerson 7000 continues to be a preferred choice for businesses seeking to navigate the complexities of modern manufacturing and process automation.