Emerson ADTS manual Installation, Controller Ground, Harnesses, Auxiliary Circuits

Page 4

INSTALLATION (continued)

Controller Ground

A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.

Harnesses

The transfer switch is connected to the left side of the control panel by a plug-in harness (two plugs).

Auxiliary Circuits

Connect auxiliary circuit wires to appropriate terminals on the transfer switch. Note the control features that are furnished on this switch. Make the necessary auxiliary connections by referring to the Wiring Diagram.

Engine Starting Contacts

The engine control contact connections (if used) are located on the transfer switch. Connect signal wires to appropriate terminals as specified in Table B and shown in Figures 1–1 and 1–2. See the wiring diagram too.

Table B. Engine start connections

When normal

 

Terminals on

source fails

 

 

transfer switch

contact closes

 

TB1 and TB2

contact opens

 

TB1 and TB3

 

left side of transfer switch

 

COMMON

 

Engine Starting

FEATURE 7

 

Signals

 

5 amps, 32 V DC

closes to start

 

5 amps resistive 28 V DC

FEATURE 8

 

or 120 V AC max.

opens to start

 

 

 

 

COMMON

 

TS Auxiliary Contacts

 

 

FEATURE 14B

 

Feature 14A & 14B

 

10 amps, 32 V DC

closed on emergency

 

 

10 amps 250 V AC

FEATURE 14A

 

 

general purpose

closed on normal

 

 

 

 

COMMON

 

Optional

 

TS Auxiliary Contacts

 

 

FEATURE 14BA

 

Feature 14AA & 14BA

 

10 amps, 32 V DC

closed on emergency

 

10 amps 250 V AC

FEATURE 14AA

 

 

general purpose

closed on normal

Figure 1-1. Connections to engine starting contact terminal block for 150 through 1200 amp.

J & H–design transfer switches.

Engine Starting

TS Auxiliary Contacts

 

 

Signals

Feature 14A & 14B

 

 

5 amps, 32 V DC

10 amps, 32 V DC

 

 

5 amps resistive 28 V DC

10 amps 250 V AC

TB Terminal Block

 

or 120 V AC max.

general purpose

 

 

 

(field connections)

 

 

 

accepts wire range

 

FEATURE 7 closes to start FEATURE 8 opens to start

 

22–12 AWG

 

 

 

 

 

 

 

 

Figure 1-2. Connections to engine starting contact terminal block located on 1600 through 3000 amp.

G–design transfer switches.

1---2

Image 4
Contents Rating Label Table of ContentsNameplate Catalog Number Identification 4ADTS aInstallation Installation Controller GroundHarnesses Auxiliary CircuitsInstallation Functional Test Manual Operation TestDesign 150-600 amp Design 800-1200 ampTransfer Switch Interlocked Shafts Interlocked Weights Shaft IndicatorsPosition HandleNormal contacts Contact position Indicators left side Closed14. Standard controls and indicators Voltage ChecksHow to unlock the User Controls Electrical OperationTesting & Service Preventive MaintenanceReplacement Parts Disconnecting the ControllerTROUBLE-SHOOTING Testing & ServiceManual Load Transfer Index See Controller User’s Guide